EN-10
English
12
12 Device Information
1
Type and order code
WI 9ME
WI 14ME
2
Design
2.1
Degree of protection according to EN 60 529
IP 20
IP 20
2.2
Installation Location
Indoors
Indoors
3
Performance data
EN 255
EN 14511
EN 255
EN 14511
3.1
Operating temperature limits:
Heating water flow
°C
Up to 55
Up to 55
Cold water (heat source)
° C
+7 to +25
+7 to +25
3.2
Temperature spread of heating waterat W10 / W35
K
9.5
5.0
8.8
5.0
3.3
Heat output / COP
at W7 / W55
1
kW / ---
1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation should
also be taken into consideration. The specified values, e.g. W10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
6.9 / 2.5
12.2 / 2.3
at W10 / W50
1
kW / ---
7.7 / 3.2
13.4 / 3.4
at W10 / W45
1
kW / ---
7.7/ 3.7
13.4 / 3.8
at W10 / W35
1
kW / ---
8.3 / 5.1
8.2 / 4.8
13.6 / 5.0
13.5 / 4.7
3.4
Heating water flow with an internal pressure differential of m³/h / Pa
0.75 / 7000
1.4 / 24000
1.3 / 7000
2.3 / 22000
3.5
Cold water flow rate at an internal pressure differential of
(heat source)
m³/h / Pa
2.0 / 6200
3.3 / 19000
3.6
Refrigerant; total filling weight
type / kg
R407C / 1.7
R407C / 1.9
3.7
Lubricant; total filling weight
type / litres
Polyolester (POE) / 1.0
FV68S / 1.7
4
Dimensions, connections and weight
4.1
Device dimensions without connections
2
H x W x L mm
2. Note that additional space is required for pipe connections, operation and maintenance.
1445 x 650 x 575
1445 x 650 x 575
4.2
Device connections to heating system
Inch
G 1¼" external
G 1¼" external
4.3
Device connections to heat source
Inch
G 1¼" external
G 1¼" external
4.4
Weight of the transportable unit(s) incl. packing
kg
156
165
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
230 / 16
230 / 25
5.2
Nominal power consumption
1
W10 W35
kW
1.62
1.69
2.72
2.87
5.3
Starting current with soft starter
A
26
45
5.4
Nominal current W10 W35 / cos
ϕ
A / ---
0.8
9.18
14.8
16.6
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
3
7
Additional model features
7.1
Water in device protected against freezing
4
4. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes
Yes
7.2
Performance levels
1
1
7.3
Controller internal/external
Internal
Internal
Summary of Contents for WI 14ME
Page 2: ......
Page 14: ...D 12 Deutsch 13...
Page 36: ...FR 12 Fran ais 12...
Page 42: ...A VI Anhang Appendix Annexes 3 2 3 2 Last Load Charge 3 3 3 UXQGIRV 0 63 0 63...
Page 49: ...www dimplex de A XIII Anhang Appendix Annexes 5...
Page 50: ...A XIV Anhang Appendix Annexes 5...
Page 51: ...www dimplex de A XV Anhang Appendix Annexes 5...