7.4

7.2 Connection on heating side

ATTENTION!

The heating system must be flushed prior to connecting the heat pump.

Before completing the heat pump connections on the heating
water side, the heating installation must be flushed in order to re-
move any impurities that may be present, as well as residues of
sealing material, and the like. Any accumulation of deposits in
the condenser may result in a total failure of the heat pump.
Once the installation on the heating side has been completed,
the heating system must be filled, de-aerated and pressure-
tested.
Consideration must be given to the following points when filling
the system:

„

Untreated filling water and make-up water must be of drin-
king water quality (colourless, clear, free of sediments).

„

Filling water and make-up water must be pre-filtered (max.
pore size 5µm).

Scale formation in domestic hot water heating systems cannot be
completely avoided, but in systems with flow temperatures below
60°C, the problem can be disregarded.
With medium and high-temperature heat pumps, even tempera-
tures above 60°C can be reached.
The following standard values should therefore be adhered to re-
garding the filling water and make-up water (according to VDI
2035, sheet 1):

Minimum heating water flow

The minimum heating water flow through the heat pump must be
assured in all operating states of the heating system. This can be
accomplished, for example, by installing either a manifold without
differential pressure or an overflow valve. The procedure for ad-
justing an overflow valve is described in the chapter "Start-up".

Frost protection for installations prone to frost

Provided the controller and heating circulating pumps are ready
for operation, the frost protection feature of the controller is ac-
tive. If the heat pump is taken out of service or in the event of a
power failure, the system has to be drained. In heat pump instal-
lations where a power failure cannot be readily detected (holiday
house), the heating circuit must contain a suitable antifreeze
product.

7.3 Connection on heat source 

side

The following procedure must be observed when making the
connection:
Connect the well pipes to the heat pump's flow and return.

ATTENTION!

It is essential that the dirt trap included in the accessories pack is
installed in the return (inlet).

ATTENTION!

The well water must comply with the required water quality standards.

The hydraulic plumbing diagram must be adhered to.

7.4 Electrical connection

The following electrical connections must be established on the
heat pump:

„

Control line connection in the heat pump's switch box to the
X2 terminals: L/N/PE.

„

Mains cable connection in the heat pump's switch box to the
X1 terminals: L1/L2/L3/PE.

„

Connection of the well pump mains cable on the heat
pump's control panel via terminal X1: L11/L21/L31/PE.

„

Connection of the well pump (to be provided by the custo-
mer) on the heat pump's control panel via terminal X1: PE
and pump contactor K5: 2/4/6.

Ensure that the supply voltage for these terminals cannot be
switched off by the tariff contactor when connecting the mains
cable for the well pump, in order to safeguard the switch-off delay
of the well pump.
All electrical components required for the operation of the heat
pump are located in the control box.
For more detailed instructions concerning the connection and
functioning of the heat pump controller (e.g. the supplied external
wall sensor) please refer to the enclosed operating manual of the
controller.
A circuit breaker with common tripping for all external conductors
must be installed in the incoming supply. All poles must be dis-
connected, and there must be a contact gap of at least 3 mm.
The same is true for any utility blocking contactors which might
be installed in addition, e.g. in the case of utility company shut-off
times. The required conductor cross-section is to be selected ac-
cording to the power consumption of the heat pump and the tech-
nical connection requirements of the respective utility company,
in addition to all applicable regulations. Details on the power con-
sumption of the heat pump are listed on both the product infor-
mation sheet and the type plate. The connection terminals are
designed for the appropriate currents.

ATTENTION!

The clockwise phase sequence must be observed when connecting the
load lines (the heat pump will deliver no output and will be very noisy
when the phase sequence is incorrect).

The power cable must be run through the guide tubes, inserted
into the side of the control box and secured by means of the
strain relief.

Total heat

output in [kW]

Total alkaline earths

in mol/m³ and/or

mmol/l

Total

hardness in dH

bis 200

≤ 

2,0

≤ 

11,2

200 bis 600

≤ 

1,5

≤ 

8,4

> 600

< 0,02

< 0,11

Summary of Contents for WI 100TU

Page 1: ...utilisation Installation and Operating Instructions Wasser Wasser W rmepumpe f r Innenaufstellung WI 50TU WI 100TU Water to Water Heat Pump for Indoor Installation Pompe chaleur eau eau pour installa...

Page 2: ......

Page 3: ...1 Anschlussflansche D 4 5 Transport D 4 6 Aufstellung D 4 6 1 Allgemein D 4 6 2 Schallemissionen D 4 7 Montage D 5 7 1 Allgemein D 5 7 2 Heizungsseitiger Anschluss D 5 7 3 W rmequellenseitiger Anschl...

Page 4: ...uktschriften n derungen oder Umbauten am Ger t sind zu unterlassen 1 3 Gesetzliche Vorschriften und Richtlinien Die W rmepumpe entspricht allen relevanten DIN VDE Vor schriften und EG Richtlinien Dies...

Page 5: ...gt das K ltemittel in den Verfl ssiger und ber tr gt hier wiederum seine W rmeenergie an das Heizwasser Abh ngig vom Betriebspunkt erw rmt sich so das Heizwasser auf bis zu 58 C 2K 2 3 Funktionsbeschr...

Page 6: ...en Drehverschl ssen zu ffnen und nur leicht vom Ger t weg zu kippen Danach k nnen sie nach oben aus der Hal terung gehoben werden 6 Aufstellung 6 1 Allgemein Das Ger t ist grunds tzlich in Innenr umen...

Page 7: ...ist beim Anschluss einzuhalten Die Brunnenleitungen am Vor und R cklauf der W rmepumpe anschlie en ACHTUNG Der im Beipack mitgelieferte Schmutzf nger ist unbedingt im R cklauf Eintritt einzubauen ACHT...

Page 8: ...ustand vorliegt Dies sind in der Regel die Heizkreise der R ume auf der S d und Westseite Mindestens ein Heizkreis muss ge ffnet bleiben z B Bad Das berstr mventil ist so weit zu ffnen dass sich bei d...

Page 9: ...m eine Verockerung der W rmequel lenanlage zu verhindern Der Einsatz von Oberfl chenwasser oder salzhaltigen Gew s sern ist nicht erlaubt Erste Hinweise ber eine m gliche Nut zung des Grundwassers k n...

Page 10: ...den zust ndigen Kundendienst ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden ACHTUNG Vor ffnen des Ger tes sind alle Stromkreise span...

Page 11: ...chter Betrieb 43 3 3 5 86 7 3 3 kW 6 6 1 Verdichter Betrieb 22 2 3 6 40 2 3 0 bei W10 W45 kW 5 45 5 4 5 90 9 4 1 kW 6 23 7 4 6 47 6 4 3 bei W10 W35 kW 5 49 0 6 1 47 3 5 7 98 5 5 6 95 5 5 3 kW 6 26 3 6...

Page 12: ...e Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach besse...

Page 13: ...ssories E 4 4 1 Connecting flanges E 4 5 Transport E 4 6 Installation E 4 6 1 General E 4 6 2 Sound emissions E 4 7 Assembly E 4 7 1 General E 4 7 2 Connection on heating side E 5 7 3 Connection on he...

Page 14: ...beyond that intended by the manufacturer is prohibited This requires the user to abide by the manufacturers product information Please refrain from tampering with or alter ing the device 1 3 Legal reg...

Page 15: ...its heat energy to the heating water The heating water is heated depending on the operating point to a maximum of 58 C 2K 2 3 Functional description for integrated thermal energy metering The compres...

Page 16: ...ntly tilting the covers away from the device Then lift them up out of the mount ings 6 Installation 6 1 General As a rule the unit must be installed indoors on a level smooth and horizontal surface Th...

Page 17: ...p included in the accessories pack is installed in the return inlet ATTENTION The well water must comply with the required water quality standards The hydraulic plumbing diagram must be adhered to 7 4...

Page 18: ...mp controller and can be corrected as described in the operating manual of the heat pump controller 9 Cleaning maintenance 9 1 Maintenance The heat pump is maintenance free To prevent malfunctions due...

Page 19: ...water is compatible for the evaporator of a heat pump compare table If one characteristic is negative or two char acteristics are 0 the water quality is not sufficient for the heat pump Table Resistan...

Page 20: ...les service technician ATTENTION Any work on the heat pump may only be performed by authorised and qualified after sales service technicians ATTENTION Disconnect all electrical circuits from the power...

Page 21: ...peration with 1 compressor 22 2 3 6 40 2 3 0 at W10 W45 kW 5 45 5 4 5 90 9 4 1 kW 6 23 7 4 6 47 6 4 3 at W10 W35 kW 5 49 0 6 1 47 3 5 7 98 5 5 6 95 5 5 3 kW 6 26 3 6 3 25 1 5 9 52 8 6 1 51 7 5 8 4 4 S...

Page 22: ...E 10 English 12...

Page 23: ...F 4 4 1 Brides de raccordement F 4 5 Transport F 4 6 Installation F 4 6 1 G n ralit s F 4 6 2 missions sonores F 4 7 Montage F 4 7 1 G n ralit s F 4 7 2 Raccordement c t chauffage F 5 7 3 Raccordemen...

Page 24: ...on conforme La documentation accompagnant les produits doit galement tre prise en compte Toute modification ou transfor mation sur l appareil est proscrire 1 3 Dispositions l gales et directives La po...

Page 25: ...nnement l eau de chauffage peut atteindre ainsi des temp ratures allant jusqu 58 C 2 K 2 3 Description des fonctions du compteur de chaleur int gr Les sp cifications de puissance du fabricant de compr...

Page 26: ...ale l appareil doit tre install l int rieur sur une surface plane lisse et horizontale Ici le ch ssis de la pompe chaleur doit adh rer au sol sur toute sa circonf rence afin de ga rantir une isolation...

Page 27: ...tour de la pompe chaleur ATTENTION Il est imp ratif de monter le collecteur d impuret s fourni dans le circuit retour entr e ATTENTION L eau de puits doit tre conforme la qualit de l eau requise Suivr...

Page 28: ...l de temp rature entre le circuit de d part et de retour du chauffage indiqu dans le tableau suivant en fonction de la tem p rature actuelle de la source de chaleur Il faut mesurer l cart de temp ratu...

Page 29: ...rensei gnements sur une exploitation ventuelle de l eau de la nappe phr atique Les analyses d eau sont effectu es par des labora toires sp cialis s dans les techniques de l eau Un circuit interm diai...

Page 30: ...x sur la pompe chaleur doivent tre effectu s uniquement par des SAV agr s et qualifi s ATTENTION Avant d ouvrir l appareil assurez vous que tous les circuits lectriques sont bien hors tension 11 Mise...

Page 31: ...nement 1 compresseur 22 2 3 6 40 2 3 0 pour W10 W45 kW 5 45 5 4 5 90 9 4 1 kW 6 23 7 4 6 47 6 4 3 pour W10 W35 kW 5 49 0 6 1 47 3 5 7 98 5 5 6 95 5 5 3 kW 6 26 3 6 3 25 1 5 9 52 8 6 1 51 7 5 8 4 4 Niv...

Page 32: ...F 10 Fran ais 12...

Page 33: ...uerung Standardregler Control for standard controller commande r gulateur standard WI 100TU A XI 3 7 Steuerung Standardregler Control for standard controller commande r gulateur standard WI 100TU A XI...

Page 34: ...DQJ LQ 3 LQWHUQDO H WHUQDO WKUHDG HDW UHWXUQ QSXW LQWR 3 LQWHUQDO H WHUQDO WKUHDG HDW IORZ 2XWSXW IURP 3 OHFWULF FDEOHV LQWHUQDO H WHUQDO WKUHDG HDW VRXUFH 2XWSXW IURP 3 LQWHUQDO H WHUQDO WKUHDG HDW V...

Page 35: ...QDO H WHUQDO WKUHDG HDW UHWXUQ QSXW LQWR 3 LQWHUQDO H WHUQDO WKUHDG HDW IORZ 2XWSXW IURP 3 OHFWULF FDEOHV LQWHUQDO H WHUQDO WKUHDG HDW VRXUFH 2XWSXW IURP 3 LQWHUQDO H WHUQDO WKUHDG HDW VRXUFH QSXW LQW...

Page 36: ...LVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH HL ZDVVHUGXUFKIOXVV LQ P K HDWLQJ ZDWHU IORZ UDWH LQ P K pELW G HDX...

Page 37: ...RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH HL ZDVVHUGXUFKIOXVV LQ P K HDWLQJ ZDWHU IORZ UDWH LQ P K pELW G HDX GH FKDXIIDJH H...

Page 38: ...dardregler Control for standard controller commande r gulateur standard WI 50TU 1 12 12 12 5 7 5 7 1 1 95 9 WHUP 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 1 7 1 3 SF 5 1 3 1 7 DDDD EEEE FFFF GGG HHH III...

Page 39: ...ardregler Control for standard controller commande r gulateur standard WI 50TU 1 1 1 1 12 1 12 1 12 12 12 5 1 1 5 9 DW 12 20 95HI 1 6 6 6 3RZHU 6XSSO 6 1 7 5 1 S 5 5 G 3 3 3 1 1 1 3 1 9 FRQQHFWLRQ QDO...

Page 40: ...A VIII Anhang Appendix Annexes 3 3 3 3 Last Load Charge WI 50TU 4 1 a 0 0 Q 8 9 1 1 3 9 3 3 9 3 a 0 7 7 7 0 1 20 7 7 8 7 9 7 1 12 5 6 a 0 7 7 7 1 0 1 20 7 7 8 7 9 7 1 12 5 6...

Page 41: ...lectrique r gulateur standard WI 50TU 12 12 12 5 7 5 7 1 1 95 9 WHUP 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 7 7 1 3 7 1 1 3 SF 5 1 3 1 3 9 1 1 7 DDDD EEEE FFFF GGG HHH IIII JJJ 1 3 0 0 0 1 1 3 0 0 0...

Page 42: ...m for standard controller sch ma lectrique r gulateur standard WI 50TU 1 1 1 1 12 1 12 1 12 12 12 5 G 1 G 5 5 1 1 5 9 DW 12 20 95HI 1 6 6 6 3RZHU 6XSSO 6 1 7 5 1 S 5 5 G 3 3 0 3 1 0 1 1 3 1 9 FRQQHFWL...

Page 43: ...Control for standard controller commande r gulateur standard WI 100TU 1 12 12 12 5 7 5 7 1 1 95 9 WHUP 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 1 7 1 3 SF 5 1 3 1 7 DDDD EEEE FFFF GGG HHH IIII JJJ 1 3...

Page 44: ...r Control for standard controller commande r gulateur standard WI 100TU 1 1 1 1 12 1 12 1 12 12 12 5 1 1 5 9 DW 12 20 95HI 1 6 6 6 3RZHU 6XSSO 6 1 7 5 1 S 5 5 G 3 3 3 1 1 1 3 1 9 FRQQHFWLRQ QDORJ LJLW...

Page 45: ...www dimplex de A XIII Anhang Appendix Annexes 3 8 3 8 Last Load Charge WI 100TU 4 1 a 0 0 Q 8 9 1 1 3 9 3 1 7 7 7 1 7 7 7 3 9 3 a 0 0 a 0 0...

Page 46: ...lectrique r gulateur standard WI 100TU 12 12 12 5 7 5 7 1 1 95 9 WHUP 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 7 7 1 3 7 1 1 3 SF 5 1 3 1 3 9 1 1 7 DDDD EEEE FFFF GGG HHH IIII JJJ 1 3 0 0 0 1 1 3 0 0...

Page 47: ...it diagram for standard controller sch ma lectrique r gulateur standard WI 100TU 1 1 1 1 12 1 12 1 12 12 12 5 G 1 G 5 5 1 1 5 9 DW 12 20 95HI 1 6 6 6 3RZHU 6XSSO 6 1 7 5 1 S 5 5 G 3 3 0 3 1 0 1 1 3 1...

Page 48: ...ct de signalisation de d faut N7 F13 St rmeldekontakt N8 Fault messaging contact N8 Contact de signalisation de d faut N8 F20 Thermostat Schaltkasten Thermostat for switch box Thermostat bo tier lectr...

Page 49: ...etour circuit primaire R25 Drucksensor K ltekreis Niederdruck pO Pressure sensor for refrigerating circuit low pressure pO Capteur de pression circuit r frig rant basse pression pO R26 Drucksensor K l...

Page 50: ...W rmepumpenanlage mit drei Heizkreisen und Warmwasserbereitung Heat pump system with three heating circuits and DHW preparation installation de pompes chaleur avec trois circuits de chauffage et prod...

Page 51: ...lex de A XIX Anhang Appendix Annexes 4 2 4 2 W rmepumpenanlage mit einem Heizkreis Heat pump system with one heating circuit installation de pompe chaleur avec un circuit de chauffage 7 7 5 5 0 0 5 5...

Page 52: ...hermique de piscine K21 Sch tz Flanschheizung Contactor for flange heater Contacteur cartouche chauffante M11 Prim rumw lzpumpe Primary circulating pump Circulateur primaire M13 Heizungsumw lzpumpe He...

Page 53: ...www dimplex de A XXI Anhang Appendix Annexes 5 5 Konformit tserkl rung Declaration of Conformity D claration de conformit...

Page 54: ...ge in kg __________________________________________ Total content weight in kg Quantit de remplissage en kg Hermetisch geschlossen ja nein hermetically sealed yes no Herm tiquement ferm oui non Folgen...

Page 55: ...www dimplex de A XXIII Anhang Appendix Annexes 6...

Page 56: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: