SI 50 - 70 TUR
English
6
Electrical connection
6.1
Nominal voltage / fusing / type
3-/PE 400V (50Hz) / C40A / A
3-/PE 400V (50Hz) / C63A / A
6.2
Control voltage / fusing / type
1-/N/PE 230V (50Hz) / C13A / A
1-/N/PE 230V (50Hz) / C13A / A
6.3
Degree of protection according to EN 60 529
IP21
IP21
6.4
Starting current with soft starter
A
49
62
6.5
Nominal power consumption
B0 W35 / max. power consumption kW
10,8 / 19,1
15.9 / 30.5
6.6
Nominal current
B0 W35 / cos
ϕ
A / ---
19,5 / 0,8
28.7 / 0.8
6.7
Power consumption of compressor protection (per compressor)
W
90; thermostatically controlled
90; thermostatically controlled
6.8
Power consumption of pumps
kW
up to 0,75
up to 1.0
7
Complies with the European safety regulations
7
8
Additional model features
8.1
Water in device protected against freezing
8
Yes
Yes
8.2
max. operating overpressure (heat source/heat sink)
bar
3,0
3.0
1. 1-compressor operation
2. 2-compressor operation
3. These data indicate the size and capacity of the system according to EN 14511.
For an analysis of the economic and energy efficiency of the system, the bivalence point and the regulation should be taken into consideration.
These figures are only achieved with clean heat exchangers.
Information on maintenance, commissioning and operation can be found in the respective sections of the installation and operating instructions.
The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
4. The coefficients of performance are valid with the circulating pumps included in the scope of supply
5. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35° C.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A) depending on the installation location.
6. Please note that additional space is required for pipe connections, operation and maintenance
7. see CE declaration of conformity
8. The heat circulating pump and the heat pump manager must always be ready for operation.
Summary of Contents for SI 50TUR
Page 2: ......
Page 34: ...EN 16 452237 66 38 FD 9705 www dimplex de English SI 50 70 TUR...
Page 50: ...FR 16 452237 66 38 FD 9705 www dimplex de Fran ais SI 50 70 TUR...
Page 66: ...A XVI 452237 66 38 FD 9705 www dimplex de Anhang Appendix Annexes SI 50 70 TUR...
Page 67: ...www dimplex de 452237 66 38 FD 9705 A XVII SI 50 70 TUR Anhang Appendix Annexes...