7.6 Electrical connection 

7.6.1 General

All  electrical  installation  work  must  be  carried  out  by  a  trained
electrician  or  a  specialist  for  the  specified  tasks  in  accordance
with the 

installation and operating instructions, 

country-specific installation regulations (e.g. VDE 0100),

technical connection conditions of the energy suppliers and
supply grid operators (e.g. TAB) and

local conditions. 

To  ensure  that  the  frost  protection  function  of  the  heat  pump
works properly, the heat pump manager must remain connected
to the power supply and the flow must be maintained through the
heat pump at all times.
The switching contacts of the output relay are interference-sup-
pressed. Therefore, depending on the internal resistance of the
measuring instrument, a voltage can also be measured when the
contacts are open. However, this will be much lower than the line
voltage.
Extra-low voltage is applied on the controller terminals N1-J1 to
N1-J11; N1-J19; N1-J20; N1-J23 to N1-J26; N17-J1 to N17-J4;
N17-J9;  N17-J10;  N0-J2  to  N0-J14  and  the  terminal  strips  X3
and X5.1. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be de-
stroyed.

7.6.2 Electrical installation work 

1)

The 4-core electrical supply cable for the output section of
the heat pump is fed from the heat pump meter via the utility
company blocking contactor (if required) into the heat pump.
Connection  of  the  mains  cable  to  the  contact  plate  of  the
heat pump via terminals X1: L1/L2/L3/PE.
An  all-pole  disconnecting  device  with  a  contact  gap  of  at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for
all external conductors must be installed in the power supply
for the heat pump (tripping current and characteristic in com-
pliance with the device information).

ATTENTION!

Ensure the rotary field is clockwise when connecting the mains cables (if
the rotary field is not clockwise, the heat pump will not work properly, is
very loud and may cause damage to the compressor).

2)

The 3-core electric supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump.
Connection of the  control cable to  the  contact  plate of  the
heat pump via terminal X2: L/N/PE. 
Details  on  the  power  consumption  of  the  heat  pump  are
listed  on  both  the  product  information  sheet  and  the  type
plate.
The supply cable (L/N/PE~230 V, 50 Hz) for the heat pump
manager must have a continuous voltage. For this reason, it
should be tapped upstream from the utility blocking contac-
tor or be connected to the household current, because oth-
erwise important protection functions could be lost during a
utility block.

3)

The utility blocking contactor (K22) with 3 main contacts (1/
3/5  //  2/4/6)  and  an  auxiliary  contact  (NO  contact  13/14)
should be dimensioned according to the heat pump output
and must be supplied on-site.
The  NO  contact  of  the  utility  blocking  contactor  (13/14)  is
looped  from  terminal  strip  X3/G  to  controller  N1/J5-ID3.

CAUTION! Extra-low voltage!

4)

The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG 2) should be dimensioned according to
the radiator output and must be provided on-site. It is con-
trolled (230 V AC) from the  heat  pump manager via  termi-
nals X2/N and contact N1/J13-NO4 on the heat pump man-
ager.

5)

The contactor (K21) for the flange heater (E9) in the domes-
tic  hot  water  cylinder  should  be  dimensioned  according  to
the radiator output and must be provided on-site. It is con-
trolled (230 V AC) from the  heat  pump manager via  termi-
nals X2/N and contact N1/J16-NO10.

6)

The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. Mains cables for
installed heating systems must be designed and protected in
accordance with the valid standards and regulations.

7)

All installed electric cables must have permanent wiring.

8)

The heat circulating pump (M13) is activated via the contact
N1-J13/NO5. Connection points for the pump are coupling
relays KM13/14 and X2/N.

9)

The auxiliary circulating pump (M16) is activated via the con-
tact N1-J16/NO9. Connection points for the pump are cou-
pling relays KM16/14 and X2/N. 

10) The domestic hot water circulating pump (M18) is activated

via the contact N1-J13/NO6. Connection points for the pump
are coupling relays KM18/14 and X2/N.

11) The brine or well pump (M11) is activated via the contact re-

frigeration circuit controller N0/J18-Out3. A coupling relay is
already integrated in this output. If an additional well pump is
used,  the  protective  motor  switch  at  the  site  must  be
checked and replaced if necessary.
Ensure that the power supply for these terminals cannot be
switched  off  by  the  tariff  contactor  when  connecting  the
mains  cable  for  the  well  pump,  in  order  to  safeguard  the
switch-off delay of the well pump.

12) A return sensor is integrated into the heat pumps. The de-

mand  sensor must be installed in  the immersion  sleeve in
the manifold only when a dual differential pressureless man-
ifold  is  used.  The  single-core  wires  are  then  connected  to
terminals X3/GND and controller N1/J2-U2.

13) The external sensor (R1) is connected to terminals X3/GND

and controller N1/J2-U1.

14) The domestic hot water sensor (R3) is included with the do-

mestic hot water cylinder and is connected to terminals X3/
GND and controller N1/J2-U3.

15) The connector cable (or the connector) of the hydraulic 4-

way reversing valve must be connected to the receptacle of
the device mounted at the "top" in the rear wall.

Summary of Contents for SI 50TUR

Page 1: ...und Gebrauchsanweisung Installation and Operating Instruction Instruction d installation et d utilisation Reversible Sole Wasser W rmepumpe f r Innenaufstellung Reversible Brine to Water Heat Pump for...

Page 2: ......

Page 3: ...hallemissionen DE 6 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Montage des hydraulischen 4 Wege Umschaltventil DE 6 7 3 Heizungsseitiger Anschluss DE 9 7 4 W rmequellenseitiger Anschluss DE 9 7 5 Temperatu...

Page 4: ...enmanager ACHTUNG Vor ffnen des Ger tes sind alle Stromkreise spannungsfrei zu schalten 1 2 Bestimmungsgem er Gebrauch Dieses Ger t ist nur f r den vom Hersteller vorgesehenen Ver wendungszweck freige...

Page 5: ...e W rme an das K l temittel im K ltekreislauf abgegeben Dabei k hlt sich die Sole wieder ab so dass sie im Solekreis wieder W rmeenergie auf nehmen kann Das K ltemittel wird vom elektrisch angetrieben...

Page 6: ...und Steuerspannung ist bauseits zu verlegen Die im Lieferumfang enthaltenen Umw lzpumpen Sole und Heizwasserseite sind gem den Hydraulikschemen siehe Kap 3 auf S XI bzw nach den Projektierungsunterlag...

Page 7: ...penmanager sind folgende Netzwerkverbin dungen m glich Modbus EIB KNX Ethernet ACHTUNG Bei einer externen Ansteuerung der W rmepumpe bzw der Umw lzpumpen ist ein Durchflussschalter vorzusehen der das...

Page 8: ...der W rmepumpe sind folgende Anschl sse herzustellen Vor R cklauf Sole W rmequellenanlage Montage des hydraulischen 4 Wege Umschaltventil Y12 mit den beiliegenden Doppelnippeln 2 k nnen alle An schl...

Page 9: ...ese Rohrbaugruppen sind wie in Abb 7 3 auf S 7 ge zeigt mit den Gewindeflanschen zu verbinden 7 2 3 Montage Abb 7 3 Hierbei sind die in Abb 7 3 auf S 7 gezeigten Abstandsma e durch den Eindichtvorgang...

Page 10: ...nten gerichteten HW Vorlauf Installatiosvarianten ist im Vorlauf rohr oder im anschlie enden Heizkreis eine geeignete Entl ftungsvorrichtung zu intallieren Abb 7 6 hydraulisches 4 Wege Umschaltventil...

Page 11: ...rmepumpe f hren Es wird empfohlen an der Heizwasserr cklaufseite des montier ten hydraulischen 4 Wege Umschaltventil einen Schmutzf nger zu montieren Mindestheizwasserdurchsatz Der Mindestheizwasserd...

Page 12: ...im Lieferumfang der W rmepumpe enthalten aber nicht eingebaut sind Die Anlegef hler k nnen als Rohranlegef hler montiert oder in die Tauchh lse des Kompaktverteilers eingesetzt werden Montage als Rohr...

Page 13: ...nktionen au er Betrieb sind 3 Das EVU Sperrsch tz K22 mit 3 Hauptkontakten 1 3 5 2 4 6 und einem Hilfskontakt Schlie er 13 14 ist entspre chend der W rmepumpenleistung auszulegen und bauseits beizuste...

Page 14: ...riebnahme 8 1 Allgemein Um eine ordnungsgem e Inbetriebnahme zu gew hrleisten sollte diese von einem vom Werk autorisierten Kundendienst durchgef hrt werden Unter bestimmten Bedingungen ist damit eine...

Page 15: ...des Verfl ssigers der W rme pumpe anzuschlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigungsmit...

Page 16: ...5 2 5 38 1 2 4 26 8 2 3 56 9 2 5 bei B0 W55 47 kW 22 1 2 9 43 2 2 7 33 6 2 9 64 5 2 8 bei B0 W45 40 kW 23 5 3 7 45 5 3 5 34 9 3 6 66 6 3 4 bei B0 W35 30 kW 25 1 4 9 48 4 4 5 36 9 4 7 69 8 4 4 4 3 K hl...

Page 17: ...r Betrieb 3 Diese Angaben charakterisieren die Gr e und die Leistungsf higkeit der Anlage nach EN 14511 F r wirtschaftliche und energetische Betrachtungen sind Bivalenzpunkt und Regelung zu ber cksich...

Page 18: ...eferer bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird...

Page 19: ...6 1 General EN 6 6 2 Sound Emissions EN 6 7 Assembly EN 6 7 1 General EN 6 7 2 Assembling the hydraulic 4 way reversing valve EN 6 7 3 Connection on heating side EN 9 7 4 Connection on heat source sid...

Page 20: ...is to be effected in accordance with the installation and operating manual of the heat pump manager ATTENTION Disconnect all electrical circuits from the power supply before opening the enclosure 1 2...

Page 21: ...he refrigeration cycle When so doing the brine cools so that it can again take up heat energy in the brine circuit The refrigerant is drawn in by the electrically driven compressor is compressed and p...

Page 22: ...g pumps brine and heating water side included in the scope of supply must be installed in accordance with the hy draulic diagrams see Cap 3 on page XI or the development documents The electrical conne...

Page 23: ...e interface The following network connections can be made on the heat pump manager Modbus EIB KNX Ethernet ATTENTION If the heat pump or circulating pump is controlled externally an flow rate switch i...

Page 24: ...w and return of the brine heat source system Assembly of the hydraulic 4 way reversing valve Y12 with the double nipples 2 provided all connections on the heat pump can also be used as external thread...

Page 25: ...e heat pump These pipe assemblies must be connected with the threaded flanges as shown in Fig 7 3 on page 7 7 2 3 Assembly Fig 7 3 The clearances shown in Fig 7 3 on page 7 must be achieved with the s...

Page 26: ...ow installation versions pointed downwards a suitable purging facility must be installed in the flow pipe or in the subsequent heating circuit Fig 7 6 hydraulic 4 way reversing valve HW flow and retur...

Page 27: ...stroyed Use of the optionally available four way reversing valve is recom mended A detailed installation description can be found in the in structions included with the valve Heating water minimum flo...

Page 28: ...luded in the scope of supply of the heat pump but have not yet been installed The strap on sensors can be fitted as pipe mounted sensors or installed in the immersion sleeve of the compact manifold Mo...

Page 29: ...important protection functions could be lost during a utility block 3 The utility blocking contactor K22 with 3 main contacts 1 3 5 2 4 6 and an auxiliary contact NO contact 13 14 should be dimension...

Page 30: ...o ensure that start up is performed correctly it should only be carried out by an after sales service technician authorised by the manufacturer These measures can also include an additional warranty u...

Page 31: ...e di rectly to the flow and return of the liquefier of the heat pump It is then important that the system be thoroughly flushed using appropriate neutralising agents to prevent any damage from being c...

Page 32: ...6 8 2 3 56 9 2 5 at B0 W55 47 kW 22 1 2 9 43 2 2 7 33 6 2 9 64 5 2 8 at B0 W45 40 kW 23 5 3 7 45 5 3 5 34 9 3 6 66 6 3 4 at B0 W35 30 kW 25 1 4 9 48 4 4 5 36 9 4 7 69 8 4 4 4 3 Cooling flow free compr...

Page 33: ...e and capacity of the system according to EN 14511 For an analysis of the economic and energy efficiency of the system the bivalence point and the regulation should be taken into consideration These f...

Page 34: ...EN 16 452237 66 38 FD 9705 www dimplex de English SI 50 70 TUR...

Page 35: ...ralit s FR 6 6 2 Emissions sonores FR 6 7 Montage FR 6 7 1 G n ralit s FR 6 7 2 Montage de la vanne m langeuse 4 voies FR 6 7 3 Raccordement chauffage et circuit d eau chaude FR 9 7 4 Raccordement c...

Page 36: ...aux instructions de montage et d utilisation du gestionnaire de pompe chaleur ATTENTION Avant d ouvrir l appareil assurez vous que tous les circuits lectriques sont bien hors tension 1 2 Utilisation c...

Page 37: ...vaporateur de la pompe chaleur dans lequel la chaleur est d livr e au fluide frigorig ne du circuit frigorifique Par cette op ration l eau glycol e se refroidit nouveau de mani re pouvoir de nouveau d...

Page 38: ...ures c t eau glycol e et c t eau de chauffage doivent tre install s conform ment aux sch mas hydrauliques voir Chap 3 page XI ou aux docu ments de projet Les branchements lectriques des circulateurs d...

Page 39: ...le gestionnaire de pompes chaleur Modbus EIB KNX Ethernet ATTENTION En cas de commande externe de la pompe chaleur ou des circulateurs pr voir un commutateur de d bit servant emp cher la mise en marc...

Page 40: ...niveau de la pompe chaleur sont les suivants D part et retour d eau glycol e installation de source de chaleur Montage de la vanne m langeuse 4 voies Y12 Les manchons doubles fournis 2 permettent d u...

Page 41: ...ment de t le Ces ensembles tuyaux doivent tre raccord s avec les brides filet es comme cela est repr sent dans la Fig 7 3 page 7 7 2 3 Montage Fig 7 3 Durant cette op ration veiller obtenir les cotes...

Page 42: ...lation du d part eau de chauffage vers le bas un dispositif de purge appropri doit tre mont dans le tuyau de d part ou dans le circuit de chauffage qui suit Fig 7 6 Vanne m langeuse 4 voies d part et...

Page 43: ...haleur Il est indiqu d utiliser la vanne d inversion 4 voies disponible en option Les instructions de montage jointes la vanne contien nent une description pr cise de son montage D bit d eau de chauff...

Page 44: ...des sont comprises dans les fournitures de la pompe chaleur mais non mont es Les sondes d applique peuvent tre mont es sur les tuyauteries ou ins r es dans le doigt de gant du distributeur compact Mon...

Page 45: ...r es de blocage 3 Le contacteur de blocage de la soci t d lectricit K22 avec 3 contacts principaux 1 3 5 2 4 6 et un contact au xiliaire contact NO 13 14 doit tre dimensionn en fonction de la puissanc...

Page 46: ...une mise en service en r gle cette derni re doit tre effectu e par un service apr s vente agr par le construc teur Une garantie suppl mentaire est ainsi associ e sous cer taines conditions voir Garan...

Page 47: ...tallation de chauffage nous vous re commandons de raccorder l appareil de nettoyage directement sur l aller et le retour du condenseur de la pompe chaleur Il faut ensuite soigneusement rincer les tuya...

Page 48: ...puissance 1 2 1 2 pour B0 W55 kW 19 5 2 5 38 1 2 4 26 8 2 3 56 9 2 5 pour B0 W55 47 kW 22 1 2 9 43 2 2 7 33 6 2 9 64 5 2 8 pour B0 W45 40 kW 23 5 3 7 45 5 3 5 34 9 3 6 66 6 3 4 pour B0 W35 30 kW 25 1...

Page 49: ...t risent la taille et la puissance de l installation selon EN 14511 Lors de consid rations conomiques et nerg tiques le point de bivalence et la r gulation doivent tre pris en compte Ces donn es sont...

Page 50: ...FR 16 452237 66 38 FD 9705 www dimplex de Fran ais SI 50 70 TUR...

Page 51: ...2 6 Einsatzgrenzendiagramm K hlen Operating limits diagram cooling Diagramme des seuils d utilisation rafra chissement A X 3 Einbindungsschemen Integration diagram Sch mad int gration A XI 3 1 Reversi...

Page 52: ...A II 452237 66 38 FD 9705 www dimplex de Anhang Appendix Annexes SI 50 70 TUR 1 Ma bild Dimension drawing Sch ma cot 1 1 Ma bild Dimension drawing Sch ma cat SI 50TUR...

Page 53: ...www dimplex de 452237 66 38 FD 9705 A III SI 50 70 TUR Anhang Appendix Annexes 1 2 Ma bild Dimension drawing Sch ma cot SI 70TUR...

Page 54: ...eur Rp 2 1 2 1 5 W rmequelle Eingang in W rmepumpe Rp 2 1 2 Heat source Input into heat pump Rp 2 1 2 Source de chaleur Entr e dans la pompe chaleur Rp 2 1 2 1 6 W rmequelle Ausgang aus W rmepumpe Rp...

Page 55: ...HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ...

Page 56: ...QJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWU...

Page 57: ...QJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWX...

Page 58: ...XQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQW...

Page 59: ...Heizen Operating limits diagram heating Diagramme des seuils d utilisation chauffage HL ZDVVHUWHPSHUDWXU HDWLQJ ZDWHU WHPSHUDWXUH 7HPSpUDWXUH G HDX GH FKDXIIDJH lUPHTXHOOHQHLQWULWWVWHPSHUDWXU HDW VRXU...

Page 60: ...perating limits diagram cooling Diagramme des seuils d utilisation rafra chissement KOZDVVHUWHPSHUDWXU RROLQJ ZDWHU WHPSHUDWXUH 7HPSpUDWXUH G HDX GH UDIUDvFKLVVHPHQW lUPHVHQNHQHLQWULWWVWHPSHUDWXU HDW...

Page 61: ...anlage mit 3 Heizkreisen Warmwasserbereitung und Schwimmbadbereitung Reversible heat pump system with three heating circuits domestic hot water preparation and swimming pool water Installation r versi...

Page 62: ...izkreisen Warmwasserbereitung und Schwimmbadbereitung Electrical circuit diagram for reversible heat pump system with three heating circuits domestic hot water preparation and swimming pool water Sch...

Page 63: ...www dimplex de 452237 66 38 FD 9705 A XIII SI 50 70 TUR Anhang Appendix Annexes 3 3 Elektroschema K hlmodul Electrical circuit diagram cooling module Sch ma lectrique module de rafra chissement...

Page 64: ...d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 2 l Gaskessel Oil gas boiler Chaudi re fuel gaz M11 Prim rumw lzpumpe Primary circulating pump...

Page 65: ...Druckger terichtlinie 2014 68 EU EU Verordnungen Verordnung EU Nr 813 2013 EU Directives Low voltage directive 2014 35 EU EMC directive 2014 30 EU Pressure equipment directive 2014 68 EU EU Regulation...

Page 66: ...A XVI 452237 66 38 FD 9705 www dimplex de Anhang Appendix Annexes SI 50 70 TUR...

Page 67: ...www dimplex de 452237 66 38 FD 9705 A XVII SI 50 70 TUR Anhang Appendix Annexes...

Page 68: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: