Page 17
Figure 7: Top view of two concrete mounting blocks that allow the condensate to drain away via a gravel soak away.
Ventilation
The installation site must be an open location clear of any
obstacles which may cause a short circuiting of the
discharged air or increased resistance due to blocking of
the inlet or outlet. This includes walls and fences as well
as locations prone to blocking debris such as leaves or
snow.
Avoid installing the heat pump in a location where suction
side of the fan may be exposed directly to wind. If the
location is in open ground, the heat pump should be set
up so that the air outlet direction of the fan is
perpendicular to the main wind direction to allow
unrestricted defrosting of the evaporator.
Figure 8: Minimum distances to objects to ensure adequate
ventilation
Minimum maintenance clearances
It must be possible to carry out maintenance work without
hindrance the displayed in Figure 9 should be observed.
For example if the unit is installed on a balcony there must
be a space measuring 1000mm in front of the unit of
maintenance.
Figure 9: Minimum clearances for maintenance (not
including clearance for air circulation)
Sound insulation measures
The installation may also have to comply with the MCS
020 standard as detailed in the section on the next page.
Furthermore, the heat pumps should be installed in a
location considering the following:
the
occupant‟s
enjoyment of the garden and
outside spaces.
any windows that open close to the heat pump.
The effect on neighbouring properties.
The lowest noise emissions are achieved if an area of 3-
5m surrounding the heat pump does not have any hard
surfaces that can reverberate the sound. Additionally, the
foundation can be covered up to the level of sledge on the
heat pump with sound-absorbing material such as bark,
plants or grass. These must not affect the air flow or and
care must be taken so they don‟t
get sucked into the fan.
If the heat pump is installed above inhabited
rooms, measures to prevent solid-borne
sound should be considered.
Summary of Contents for LA 12 MI
Page 35: ...Page 34 Package 1 and 2 Plumbing Schematic...
Page 36: ......
Page 40: ...Page 39 CE declaration of conformity...
Page 41: ...Page 40 LA 6 MI performance...
Page 42: ...Page 41 LA 6 MI continued...
Page 43: ...Page 42 LA 9 MI performance...
Page 44: ...Page 43 LA 9 MI performance continued...
Page 45: ...Page 44 LA 12 MI performance...
Page 46: ...Page 45 LA 12 MI performance continued...
Page 47: ...Page 46 LA 16 MI performance...
Page 48: ...Page 47 LA 16 MI performance continued...
Page 49: ...Page 48 Product Dimensions LA 6 MI and LA 9 MI...
Page 50: ...Page 49 Product Dimensions LA 12 MI and LA 16 MI...
Page 61: ...Page 60 Information for DHW cylinder with buffer ECS125HP 580...
Page 62: ...Page 61 Information for DHW cylinder with buffer ECS150HP 75 580...
Page 63: ...Page 62 Information for DHW cylinder with buffer ECS210HP 75 580...