background image

 

 

 

Page 13 

 

 

 

Section 5: DHW preparation with inverter heat pumps 

Dimplex EC-Eau cylinder range 

EC-Eau,  the  new  range  of  unvented  stainless  steel 
cylinders  from  Dimplex  can  supply  all  the  hot  water 
required for the modern home, providing rapid fill baths 
and  invigorating  showers  to  en-suite  bathrooms  and 
other domestic appliances simultaneously. Offering low 
running  costs,  reliable  hot  water  and  fantastic  flow 
rates,    EC-Eau  cylinders  are  available  in  a  range  of 
capacities,  so  there  is  size  to  suit  even  the  most 
demanding household.

 

EC-Eau  heat  pump  cylinders  are  specified  with  large, 
high surface area heat exchangers, specifically sized to 
match  the  requirements  of  Dimplex  heat  pumps, 
optimising  heat  pump  efficiency  and  reducing  running 
costs.  The  diameter  of  the  EC-eau  range  has  been 
specifically picked for the UK market with a diameter or 
580mm unlike many other cylinders available. 

Supplied  with  an  external  expansion  vessel  for 
improved  reliability  and  reduced  cylinder  height,  EC-
Eau  standard  cylinders  are  flexible  to  site  and  easy  to 
install. 

Environmental  sensitivity and efficient  performance are 
key  attributes  across  the  EC-Eau  range,  which  boasts 
60mm  of  low  GWP  insulation  foam  and  innovative 
measures 

such 

as 

recessed 

immersions 

and 

thermostats  to  reduce  energy  wastage.  This  combined 
with  the  use  of  100%  recyclable  stainless  steel  inner 
components and a sleek black, hard wearing outer shell 
manufactured  from  completely  recycled  materials 
ensures  the  EC-Eau  range  looks  as  good  as  it 
performs. 

Dimplex  ECS  Combination  DHW  and  Buffer 
Cylinders 

In  addition  to  all  the  benefits  of  the  standard  cylinder 
Dimplex  can  also  offer  a  combination  cylinder  with  a 
DHW  cylinder  and  buffer  cylinder.  This  makes  is  easy 
to retrofit a heat pump as the new combination cylinder 
takes up the same space as the old cylinder. 

The  EC-eau  range  of  combined  buffer  and  DHW 
cylinders  have  the  buffer  cylinder  on  top  which  gives 
the following benefits: 

 

The  buffer  acts  as  an  excellent  air  separator, 
and putting at the top of the cylinder means it 
is  likely  to  be  one  of  the  highest  points  in  the 
system allowing air to easily be removed. 

 

The heat loss is reduced from the combination 
cylinder because there is less of a temperature 
gradient between the cylinder/buffer compared 
to the cylinder/ambient air. 

Volume 

Outer 

diameter 

Cylinder 

only 

Combined 
buffer and 

cylinder 

125 

580mm 

 

 

150 

580mm 

 

 

175 

580mm 

 

 

210 

580mm 

 

 

250 

580mm 

 

 

300 

580mm 

 

 

Table 7: EC-eau cylinders for use with the LA MI range 

Heat pump power for hot water preparation  

In addition to the space heating, the demand placed on 
the  heat  pump  for  hot  water  production  must  be  taken 
into account when selecting the heat pump. 

To meet normal comfort requirements, a peak hot water 
consumption  of  approximately  60-70  litres  per  person, 
per  day,  should  be  allowed,  based  on  a  hot  water 
temperature of 45°C.  

 

 

Selecting a DHW cylinder 

A  standard  DHW  cylinder  is  not  suitable  for  use  with 
heat  pumps  due  to  the  small  coil  size.  A  heat  pump 
provides  lower  hot  water  temperatures  compared  to  a 
boiler.  For  this  reason  a  heat  pump  cylinder  needs  a 
larger  coil  to  ensure  that  the  heat  can  be  transferred 
from  the  heat  pump  in  to  the  water  within  cylinder  as 
efficiently as possible. 

For all heat pumps, the achievable cylinder temperature 
is  affected  by  the  maximum  flow  temperature  and  also 
the  kW  output  of  the  heat  pump.  Since  the  kW  heat 
output of an inverter air source heat pump does not rise 
with air temperature the LA  MI heat pump can achieve 
45°C in all of the cylinders shown in Table 8. 

If  a  different  cylinder  temperature  is  required  the 
following  must  be  taken  into  account.  For  each  of 

Dimplex‟s heat pump cylinders, a graph of kW input vs 

 

The  sizing  should  be  based  on  the  worst 
day,  with  the  coldest  possible  weather  and 
the  maximum  possible  number  of  persons 
using  DHW.  If  this  sizing  method  is  not 
suitable because it causes over sizing of the 
heat  pump,  the  end  user  should  be  made 
aware that they may sometimes need to use 
the  immersion  DHW  boost  which  can  be 
activated from the wall mountable heat pump 
controller. 

 

Summary of Contents for LA 12 MI

Page 1: ...may be of use to you and is available 24 hours a day It includes Operating and installation instructions Easy How to use guides for storage heaters Service and repairs Where to buy our products Liter...

Page 2: ...LA 6 MI LA 9 MI LA 12 MI LA 16 MI Inverter air to water heat pump for outdoor installation Technical planning manual 08 60393 0...

Page 3: ...at pump system packages LA MI settings function programming overview EC eau cylinders SmartRad User guides Contains the necessary information for the user for operation and maintenance of the system A...

Page 4: ...example 2 10 Section 3 System controls in a domestic setting 11 Boiler inter lock 11 Horstmann PRT thermostat 11 Heat Pump Controller 11 Weather compensation 11 Section 4 Selection of heat emitters an...

Page 5: ...lushing the system 22 Filter 23 Filling the system 23 De aeration 23 Adjusting the water flow rate 23 Expansion vessel sizing 23 2 port valves 24 Controlling DHW temperature 24 Section 8 Electrical Co...

Page 6: ...9 LA 6 MI performance 40 LA 9 MI performance 42 LA 9 MI performance continued 43 LA 12 MI performance 44 LA 16 MI performance 46 Product Dimensions LA 6 MI and LA 9 MI 48 Product Dimensions LA 12 MI a...

Page 7: ...y due to their physical sensory or mental abilities or due to their inexperience or lack of knowledge must not operate this device without supervision or instruction by the person in charge Air as a h...

Page 8: ...k in the optimum zone because it modulates its output to match the heat demand The over driving of an inverter compressor causes it efficiency to drop Since the output of both the fixed and inverter c...

Page 9: ...ement the heat load Integration of another boiler such as gas oil or LPG is not possible with the LA MI but is possible with Dimplex s WPM range Accurately determining the building s heat loss It is e...

Page 10: ...request this service a form can be downloaded from our website that should be sent in with the following information Plan and elevation drawings scale 1 50 or 1 100 Construction U values Type of schem...

Page 11: ...14511 for the LA 6 MI for a heat loss of 4 5kW at a design temperature of 3 C Sizing example 2 Design temperature The property is in Birmingham England NHBC recommend 3 C and MIS 3005 recommend 3 4 C...

Page 12: ...lap the blue standby button will put the control into frost protection mode until reactivated Heat Pump Controller The heat pump s safe and efficient operation is regulated by the built in controller...

Page 13: ...h a flow temperature of 60 C as a flow temperature of 50 C would give the necessary output without causing the radiator to become excessively large Red areas show that this technology is not suitable...

Page 14: ...ing benefits The buffer acts as an excellent air separator and putting at the top of the cylinder means it is likely to be one of the highest points in the system allowing air to easily be removed The...

Page 15: ...hould be noted that the cylinder reheat times will be longer with a heat pump compared to a typical gas boiler This is because a gas boiler is often drastically oversized compared to the space heating...

Page 16: ...r does not remain stagnant for long period of time If the property is not occupied for a long period upon reoccupation it would be prudent to raise the cylinder temperature to 60 C and open the water...

Page 17: ...s that are capable of taking the unit s weight and draining the condensate To prevent tipping the heat pump must be suitably fixed The fixing should be strong enough to prevent the unit from tipping o...

Page 18: ...d in Figure 9 should be observed For example if the unit is installed on a balcony there must be a space measuring 1000mm in front of the unit of maintenance Figure 9 Minimum clearances for maintenanc...

Page 19: ...I 61 5 dB A 2m 3m 4m LA 12 MI 62 0dB A 2m 3m 4m LA 16 MI 64 0dB A 3m 4m 5m Table 10 Minimum distances to achieve 42dB if there is a wall between the heat pump and assessment position A weighted sound...

Page 20: ...than the property The heat pump is installed above the level of the ground storey The heat pump is used solely for heating purposes external unit is greater than 0 6 m 3 in size all LA MI units pass...

Page 21: ...conservation area or would be within a World Heritage Site or the curtilage of a listed building In addition before beginning the development the developer must apply to the planning authority to det...

Page 22: ...on the pump should run of the lowest speed possible whilst still achieving the correct flow rate The resistance of all the pipe fittings filter heat emitters and condenser must be taken into account F...

Page 23: ...perature and the installer should ensure the glycol is vented to a suitable place to prevent contamination of the environment or sewage system in the event the pressure relief valve activating Condens...

Page 24: ...water flow around the system Every high point in the system should have a means of bleeding out air which is supplied by the installer The pressure relief valve shown in Figure 17 can be used to purg...

Page 25: ...tion thermostat and high limit stat are wired in series To keep the contacts closed on the regulation stat the dial must be set to maximum The contacts on the high limit stat will remain closed during...

Page 26: ...munication cable for 2 way valves high limit stat etc room thermostat 4 Domestic hot water sensor 5 Domestic hot water immersion heater booster heater Ducting should be used to ensure that the enclose...

Page 27: ...inity of the heat pump The isolating device must have a contact gap of at least 3mm In addition to the maintenance isolator an automatic 2 pole automatic circuit breaker should be installed The maximu...

Page 28: ...13A 47 50 34 50 LA 9 MI 23A 26A 13A 49 50 36 50 RCCD 1 RCCD 2 RCCD 3 MCB Compressor controller In line flow boiler DHW immersion switched by heat pump DHW immersion switched by a relay controlled by...

Page 29: ...shown in Figure 23 This would mean that the cable from the heat pump to the cylinder could have a lower current rating and therefore could be combined with the multi core cable rather than run a separ...

Page 30: ...the scope of supply The power for the controller is supplied from the heat pump Figure 24 Connection terminals on the controller cable to controller inside the property The controller cable is connect...

Page 31: ...able is essential to provide boiler interlock to comply with building regulations Tank OLP If the heat pump is doing DHW the over load protection is connected to the manually resettable high limit sta...

Page 32: ...mp efficiency Section 10 Standard packages To assist with the design and installation of a system Dimplex have collated wiring and hydraulic schematics for the following designs Package 1 and 2 Heatin...

Page 33: ...PK2LA 12 MI 300 PK2LA 16 MI 250 PK2LA 16 MI 300 PK3LA 6 MI PK3LA 9 MI PK3LA 12 MI PK3LA 16 MI Component parts of kits LA 6 MI 1 1 1 1 LA 9 MI 1 1 1 1 LA 12 MI 1 1 1 1 1 1 LA 16 MI 1 1 1 1 1 1 PRT1 wal...

Page 34: ...ng centre to heat pump 2 core cable for connection of DHW sensor No 3 core cable for connection of DHW immersion heater to heat pump Depends upon schematic Either cable or relay required Depends upon...

Page 35: ...Page 34 Package 1 and 2 Plumbing Schematic...

Page 36: ......

Page 37: ...g circuit for efficient and safe operation Pressure relief valve A safety device that relieves the pressure in the heating circuit if it exceeds 3 bar Inline flow boiler Additional heating capacity fo...

Page 38: ...8 61 5 3 4 Sound pressure level at 1m with Q 2 to MCS 020 dB A 54 54 3 5 Heating water flow rate m h 1 1 6 3 6 Air flow m h 2800 3100 3 7 Refrigerant total filling weight Type kg R410A 1 45 R410A 1 45...

Page 39: ...cant total filling quantity Type Litre FV50S PVE 1 2 FV50S PVE 1 2 4 Dimensions connections and weight 4 1 Device dimensions without connections H x W x L mm 1410 x 1280 x 320 1410 x 1280 x 320 4 2 De...

Page 40: ...Page 39 CE declaration of conformity...

Page 41: ...Page 40 LA 6 MI performance...

Page 42: ...Page 41 LA 6 MI continued...

Page 43: ...Page 42 LA 9 MI performance...

Page 44: ...Page 43 LA 9 MI performance continued...

Page 45: ...Page 44 LA 12 MI performance...

Page 46: ...Page 45 LA 12 MI performance continued...

Page 47: ...Page 46 LA 16 MI performance...

Page 48: ...Page 47 LA 16 MI performance continued...

Page 49: ...Page 48 Product Dimensions LA 6 MI and LA 9 MI...

Page 50: ...Page 49 Product Dimensions LA 12 MI and LA 16 MI...

Page 51: ...Page 50 LA 6 MI and LA 9 MI Spare parts Note the non numbered parts are not kept as standard service parts...

Page 52: ...Page 51 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 53: ...Page 52 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 54: ...Page 53 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 55: ...Page 54 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 56: ...Page 55 LA 12 MI and LA 16 MI Spare parts Note the non numbered parts are not kept as standard service parts...

Page 57: ...Page 56 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 58: ...Page 57 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 59: ...Page 58 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 60: ...Page 59 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Page 61: ...Page 60 Information for DHW cylinder with buffer ECS125HP 580...

Page 62: ...Page 61 Information for DHW cylinder with buffer ECS150HP 75 580...

Page 63: ...Page 62 Information for DHW cylinder with buffer ECS210HP 75 580...

Reviews: