8 Maintenance / Cleaning

8.1 Maintenance

To protect the paintwork, avoid leaning anything against the de-
vice or putting objects on the device. External heat pump parts
can be wiped with a damp cloth and domestic cleaner.

ATTENTION!

Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.

To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
can not be contaminated. In the event that operating malfunc-
tions due to contamination still occur, the system should be
cleaned as described below.

8.2 Cleaning the Heating System

The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. These products enter the heating system
via the valves, the circulating pumps and/or plastic pipes. It is
therefore essential - in particular with respect to the piping of un-
derfloor heating systems - that only diffusion-proof materials are
used.

ATTENTION!

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.

Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in the
performance of the liquifier in the heat pump, the system must be
cleaned by a heating technician.
According to today’s state of knowledge, we recommend using a
5 % phosphoric acid solution for cleaning purposes. However, if
cleaning needs to be performed more frequently, a 5 % formic
acid solution should be used.
In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return flow of the liquifier of the heat pump.
It is important that the system be thoroughly flushed using appro-
priate neutralising agents to prevent any damage from being
caused by cleaning agent residue remaining in the system.
Acids must be used with great care and all relevant regulations of
the employers’ liability insurance associations must be adhered
to.
If in doubt, contact the manufacturer of the chemicals!

8.3 Cleaning the Air System

Evaporator, ventilator and condensate outflow should be cleaned
of contamination (leaves, twigs, etc.) before the heating period.
Do this by opening the front of the heat pump. The bottom should
be opened first followed by the top.

ATTENTION!

Before opening the device, ensure that all circuits are isolated from the
power supply.

Remove and rehang the side panel assemblies as described in
Chapter 4.
To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects for cleaning.
Under extreme weather conditions (e.g. snow drifts), ice may
form on the air intake and exhaust air outlet grids. If this happens,
the ice must be removed in the vicinity of the air intake and ex-
haust air outlet grids to ensure that the minimum air flow rate is
maintained.

9 Faults / Trouble-

Shooting

This heat pump is a quality product and is designed for trouble-
free operation. In the event that a fault should occur, it will be
shown on the heat pump manager display. Simply consult the
Faults and Trouble-shooting page in the operating instructions of
the heat pump manager. If you cannot correct the fault yourself,
please contact your after-sales service technician.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians. 

10 Decommissioning/

Disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. Observe all environmentally-relevant
requirements regarding the recovery, recycling and disposal of
materials and components in accordance with all applicable
standards. Particular attention should be paid to the proper dis-
posal of refrigerants and refrigeration oils.

Summary of Contents for LA 11ASR

Page 1: ...r Heat Pump for Outdoor Installation Pompe chaleur air eau r versible pour installation ext rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation...

Page 2: ......

Page 3: ...Schaltkasten DE 4 3 3 W rmepumpenmanager DE 4 4 Transport DE 4 5 Aufstellung DE 4 5 1 Allgemein DE 4 5 2 Kondensatleitung DE 4 6 Montage DE 5 6 1 Allgemein DE 5 6 2 Heizungs und Warmwasser Anschluss D...

Page 4: ...eingehalten siehe CE Konformit tserkl rung Beim elektrischen Anschluss der W rmepumpe sind die entspre chenden VDE EN und IEC Normen einzuhalten Au erdem m ssen die Anschlussbedingungen der Versorgung...

Page 5: ...abgegeben ber den vorgeschalteten Enthitzer kann gleichzeitig oder auch separat Brauchwasser bereitet werden Dabei wird die elektrische Energie eingesetzt um die W rme der Umwelt auf ein h heres Tempe...

Page 6: ...run gen fest verbunden Diese m ssen entfernt werden Zur Nutzung der Transportbohrungen im Rahmen ist es notwen dig die unteren Fassadierungsteile abzunehmen Dazu werden jeweils zwei Schrauben am Socke...

Page 7: ...ildung in Warmwasserheizungsanlagen kann nicht vollst ndig vermieden werden ist aber bei Anlagen mit Vorlauf temperaturen kleiner 60 C vernachl ssigbar gering Bei Mittel und Hochtemperatur W rmepumpen...

Page 8: ...ensatablauf muss sichergestellt sein 7 3 Vorgehensweise Die Inbetriebnahme der W rmepumpe erfolgt ber den W rme pumpenmanager Die Einstellungen m ssen gem dessen An weisung vollzogen werden Wird der M...

Page 9: ...e anzuschlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigungsmittelreste zu verhindern Die S uren...

Page 10: ...0 6 2 0 bei A35 W18 kW 9 5 2 5 9 5 2 5 14 3 2 3 14 3 2 2 3 6 Schall Leistungspegel dB A 63 64 3 7 Schall Druckpegel in 10 m Entfernung Ausblasseite 3 dB A 3 Der angegebene Schalldruckpegel entspricht...

Page 11: ...bezo gene Teile und Ger te Anlagenm ngel die auf nicht vom Liefe rer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die N...

Page 12: ...DE 10 Deutsch 12...

Page 13: ...EN 3 3 3 Heat pump manager EN 4 4 Transport EN 4 5 Set up EN 4 5 1 General Information EN 4 5 2 Condensate pipe EN 4 6 Installation EN 5 6 1 General Information EN 5 6 2 Heating and Hot Water Connect...

Page 14: ...IN VDE regulations see CE declaration of conformity When connecting the heat pump to the power supply the rele vant VDE EN and IEC standards are to be fulfilled Any further connection requirements sti...

Page 15: ...xtracted from the air is transferred to the heating water this type of device is called an air to water heat pump The air to water heat pump consists of the main components evaporator ventilator and e...

Page 16: ...base and then withdrawing the panels by unhooking them from above Rehang the panels by gently pushing them in an upwards direction Be careful not to damage any components when inserting the pipes thr...

Page 17: ...the plate steel exchanger in the refrigerating cycle can freeze which can lead to total loss of the heat pump NOTE The use of an overflow valve is only recommended for panel heating and a max heating...

Page 18: ...ally means the heating circuits of the rooms on the south and west sides of the building At least one heating circuit must remain open e g bathroom The overflow valve should be opened far enough to pr...

Page 19: ...ce di rectly to the flow and return flow of the liquifier of the heat pump It is important that the system be thoroughly flushed using appro priate neutralising agents to prevent any damage from being...

Page 20: ...at A35 W18 kW 9 5 2 5 9 5 2 5 14 3 2 3 14 3 2 2 3 6 Sound power level dB A 63 64 3 7 Sound pressure level at a distance of 10m 3 The specified sound pressure level corresponds to the operating noise o...

Page 21: ...e de pompe chaleur FR 4 4 Transport FR 4 5 Installation FR 4 5 1 Remarques d ordre g n ral FR 4 5 2 Conduite d coulement des condensats FR 5 6 Montage FR 5 6 1 Remarques d ordre g n ral FR 5 6 2 Racco...

Page 22: ...ondan tes sont respecter lors du branchement lectrique de la pompe chaleur D autre part les prescriptions de branchement des ex ploitants de r seaux d alimentation doivent tre respect es Lors du racco...

Page 23: ...e soit simultan ment soit s pa r ment via le d surchauffeur mont en amont Il est fait appel l nergie lectrique pour faire passer la chaleur de l environnement un niveau de temp rature plus lev Comme...

Page 24: ...aide d une palette en bois L appareil de base propose plusieurs possibilit s de transport avec un chariot l vateur un diable ou l aide de tubes 3 4 que l on passe travers les orifices pr vus dans la...

Page 25: ...de l installation l eau de remplissage et l eau additionnelle non trait es doi vent tre de m me qualit que l eau potable incolore claire et sans d p t l eau de remplissage et l eau additionnelle doiv...

Page 26: ...nte agr par le construc teur Ceci permet de prolonger la garantie sous certaines condi tions La mise en service doit s effectuer en mode chauffage 7 2 Pr paration Avant la mise en service il est imp r...

Page 27: ...r s 8 2 Nettoyage c t chauffage L oxyg ne est susceptible d entra ner la formation de produits d oxydation rouille dans l eau de chauffage notamment lorsque des composants en acier sont utilis s Ces p...

Page 28: ...he de pannes Cette pompe chaleur est un produit de qualit et elle devrait fonctionner sans dysfonctionnements Si un dysfonctionnement devait quand m me survenir celui ci sera affich sur l cran du gest...

Page 29: ...10 6 2 0 pour A35 W18 kW 9 5 2 5 9 5 2 5 14 3 2 3 14 3 2 2 3 6 Niveau de puissance sonore dB A 63 64 3 7 Niveau de pression sonore une distance de 10 m c t vacuation 3 dB A 3 Le niveau de pression son...

Page 30: ...FR 10 Fran ais 11...

Page 31: ...4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique A XII 4 1 Monoenergetische Anlage mit stiller K hlung und Warmwasserbereitung ber Abw rmenutzung Mono energy system with si...

Page 32: ...WpULHXU OOHU HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU RQGHQVDWDEODXI QQHQ PP OHNWUROHLWXQJHQ 6RFNHO lUPHSXPSH HUHLFK XUFKI KUXQJHQ HL NUHLV RQGHQVDWDEODXI OHNWURNDEHO RQGHQVDWH RXWIORZ LQVLGH...

Page 33: ...HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU RQGHQVDWDEODXI QQHQ PP OHNWUROHLWXQJHQ 6RFNHO lUPHSXPSH HUHLFK XUFKI KUXQJHQ HL NUHLV RQGHQVDWDEODXI OHNWURNDEHO RQGHQVDWH RXWIORZ LQVLGH PP OHFWULF O...

Page 34: ...RQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU...

Page 35: ...WHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RH...

Page 36: ...UH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLH...

Page 37: ...IWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO R...

Page 38: ...Diagrams Sch mas lectriques 3 1 Steuerung Control Commande OOH 4XHUVFKQLWWH PP OO FURVV VHFWLRQV PP 7RXWHV OHV VHFWLRQV PP 6WHXHUOHLWXQJ PP RQWURO OHDG PP LJQH GH FRPPDQGH PP SRO SROH S OHV lUPHSXPSH...

Page 39: ...de A IX Anhang Appendix Annexes 3 2 3 2 Last Load Charge 1HW 0DLQV 5pVHDX JH JQ H JQ MD YH JH JQ H JQ MD YH 3 9HUWHLOHU 3 GLVWULEXWRU LVWULEXWHXU 3 OOH 4XHUVFKQLWWH PP OO FURVV VHFWLRQV PP 7RXWHV OHV...

Page 40: ...URO OHDG LJQH GH FRPPDQGH GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUR...

Page 41: ...stionnaire de pompe chaleur N7 Sanftanlaufsteuerung Soft start control Commande de d marrage progressif R2 R cklauff hler Heizwasser Return flow sensor heating water Sonde de retour eau de chauffage R...

Page 42: ...g und Warmwasserbereitung ber Abw rmenutzung Mono energy system with silent cooling and domestic hot water via waste heat recovery Installation mono nerg tique avec rafra chissement silencieux et prod...

Page 43: ...with silent and dynamic cooling domestic hot water and swimming pool water preparation via waste heat recovery Installation mono nerg tique avec rafra chissement silencieux et dynamique production d e...

Page 44: ...hauffante ECS E10 1 Tauchheizk rper Immersion heater R sistance immerg e M13 Heizungsumw lzpumpe Hauptkreis Heat circulating pump for main circuit Circulateur de chauffage circuit principal M14 Heizun...

Page 45: ...s LA 16ASR Type s EG Richtlinien Niederspannungsrichtlinie 2006 96 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directive 2004 108 EC...

Page 46: ...A XVI Anhang Appendix Annexes 5...

Page 47: ...www dimplex de A XVII Anhang Appendix Annexes 5...

Page 48: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: