3. To wire the Communicator to the panel, perform the following (See
a. Disconnect the AC power and the b connections from the panel.
b. Attach a wire from the Communicator’s left
PWR
terminal to the panel’s
BELL+
terminal.
NOTE: For ULC Commercial Fire Monitoring applications, do NOT connect any devices on the Bell+
terminal other than the GS2060/TL260GS.
c. Attach a wire from the Communicator’s
GND
terminal to the panel’s
AUX
-
terminal.
d. Attach a wire from the Communicator’s
SHLD
terminal to the panel’s
EGND
terminal. (Protective earth
ground).
e. If a Bell/Siren is used, attach a wire from the Communicator’s right
PWR
terminal to the positive (
+
) termi-
nal on the Bell/Siren. (See
f. If a Bell/Siren is used, attach the panel’s
BELL
-
terminal to the negative (
-
) terminal on the Bell/Siren.
NOTE: If a Bell/Siren is not used, install the 1K
½ W 5% resistor (Brown, Black, Red, Gold) (sup-
plied with the panel) between the panel’s Bell + and Bell - terminals, then only wire the BELL + to
the PWR terminal on the Communicator.
g. Confirm that the SIM card is inserted and locked. (See
Inserting and Removing the SIM Card on page 3
).
h. Insert the PC-LINK connector into the Communicator’s PC-LINK socket. (Black wire on Pin 1 on the
Communicator).
i. Route the CAT 5 Ethernet cable through back of the cabinet and plug it into the Communicator’s RJ45
jack.
NOTE: Before leaving the premises the Ethernet communication lines must first be connected to an
approved (acceptable to local authorities) type NID, (UL installations, UL 60950 listed NID, for ULC
installations CAN/CSA C22.2. No. 60950-1 Certified NID).
4. Perform the following for initial power on of the panel with Communicator installed:
a. Reconnect the AC power and b connector to the panel. (the Communicator and Panel will power
up together).
b. Observe that the Communicator’s red and yellow LEDs are flashing together while it initializes. The red
and yellow LEDs will continue to flash until the unit has successfully communicated to all programmed
receivers. If this is the first time the Communicator has been powered up, the module will request pro-
gramming from Connect24.
c. At the keypad, enter [*][8][Installer Code][382] and confirm that Toggle Option [5] is
ON
(GPRS/Ethernet
Module Enabled).
NOTE: Initialization may take several minutes to complete. Red and yellow LEDs will flash together
during initialization. Do not leave the installation until the red and yellow LEDs have stopped flash-
ing. (If only the yellow LED is flashing, there is a Communicator trouble and the Green LEDs are not
valid for Communicator Placement Test). Correct trouble before continuing. (See Table 6 for trou-
bleshooting assistance).
5. Perform the Communicator Placement Test on page 8.
PC1616/1832/1864 Programming
Perform the following steps to ensure that the Communicator and the panel work together as intended.
These Sections must be programmed at the panel keypad. Enter [*][8][Installer Code][Section Number]. Record
any values that are modified from their default, in the appropriate Worksheets for the Panel or Communicator.
NOTE: The toggle is ON when the number is displayed. Toggle is OFF when the number is not dis-
played. (e.g., [1---5---], Toggle Options 1 and 5 are ON, all others are OFF). Press the number on key-
pad to turn toggle ON/OFF.
Figure 3 GS2060/TL260GS Wiring Diagram
DG009391
A
UDIO/DEF
A
U
LT
DSC
U
A557
PC-LINK
PC-LINK
GND
PWR PWR GND GND
SHLD
TL260GS / GS2060
AC AC
RED BLK YEL GRN
Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z
8
AUX+
BELL+
AUX-
BELL-
PGM1 PGM3
EGND
TIP
T-1
PGM2 PGM4
RING R-1
PC1616/1832/1864
GSM R
a
dio
SIM C
a
rd
Holder
+
-
WARNING!
All connections to the
TL260GS/GS2060 module are power
limited. Do not route any wiring over the
circuit boards. Maintain at least 1”
(25.4mm) separation between circuit
board and wiring. A minimum of 1/4”
(7mm) separation must be maintained at
all points between non-power limited
wiring and power limited wiring.
UA503
NOTE:
For more det
a
il
s
, refer to the
control, p
a
nel In
s
t
a
ll
a
tion M
a
n
ua
l.
1
1
CON 4
To extern
a
l
a
ntenn
a
Network Connection
(Model TL260GS)
U
s
e only CAT5 c
ab
le
(300ft/100m m
a
x.) S
u
pervi
s
ed
Input Ratings (from Bell Out)
11.1V - 12.6 V
DC
100mA
s
t
a
nd
b
y; 400mA Al
a
rm
DSC Panel minimum
power requirements
16 V
AC
40 VA tr
a
n
s
former
12 V
DC
7Ah
ba
ttery
St
a
t
us
LED
s
+
-
External Bell/Siren
Black
Black
Hardware
Default
L
o
c
k