4
XR2500F User’s Guide
Introduction
Introduction
XR2500F User’s Guide
5
User Options
The User Options allow you to make adjustments to your keypad to
best fit your environment and needs.
To access the User Options portion of the keypad, press and hold
the Back Arrow and COMMAND keys for two seconds. The keypad
display changes to SET BRIGHTNESS. Press the COMMAND key to
display the next option or the Back Arrow key to exit.
Backlighting Brightness
Sets the keypad LCD, AC LED, and the Green keyboard backlighting
brightness level. At the SET BRIGHTNESS display, use the left Select
key to lower the keypad brightness. Use the right Select key to
increase the brightness.
Note:
If the brightness level is lowered, it temporarily reverts back
to maximum intensity whenever a key is pressed.
Internal Speaker Tone
Sets the keypad internal speaker tone. At the SET TONE display,
use the top left Select key to make the tone lower. Use the right
Select key to make the tone higher.
Volume level
Sets the keypad internal speaker volume level for key presses and
prewarn conditions. During alarm, trouble, and prewarn conditions,
the volume is always at maximum level. At SET VOLUME LEVEL,
use the left Select key to lower the keypad volume. Use the right
Select key to raise the volume.
Model Number
The keypad model number, firmware version, and date display, but
cannot be changed.
Four Function Keys
The Fire Command Center is designed with four additional keys on
the left side of the keypad. After turning the keyswitch, you can
quickly perform vital functions using these four keys.
SILENCE Key
Pressing the SILENCE key silences the alarm bells.
RESET Key
Pressing the RESET key performs a sensor reset and silence the
alarm bells.
TEST Key
Pressing the TEST key performs a system test.
DRILL Key
Pressing the DRILL key displays a prompt “SURE? YES NO”. Press
YES to begin the fire drill. Press NO to return to the status list.