background image

PosiTouch DALI - Lighting Controller 

User Manual 

7.0 - 23 November 2020 

 

 

digilin.com.au 

Page 6 of 6 

+617 3899 1267 

 

Appendix B.  DALI Networking Basics 

DALI is very flexible in its network configuration, to the point that DALI control lines and mains voltage 

supply lines can be wired together. 

 

The DALI control line input to a ballast is polarity insensitive, meaning there is no + or -. 

 

A DALI network can consist of up to 64 ballasts. 

 

Wiring of the DALI network can be almost any fashion, be it a daisy chain, star or branch, as per the below 

figure 

 

      

      

 

Figure 2 DALI Network Topologies 

Cable sizes should follow the guide given in the table below.  

L e a d   L e n g t h  

M i n i m u m   L e a d   D i a m e t e r  

Up to 100m 

0.5mm

2

 

100 

 150m 

0.75mm

2

 

150 

 300m 

1.5mm

2

 

 

Appendix C. Wiring Diagram 

DALI Power Supply

PosiTouch

DALI Driver

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for PosiTouch

Page 1: ... 2020 Digilin Technologies Document Rev 7 0 23 November 2020 Product specifications are subject to change without notice PosiTouch DALI Lighting Controller User Manual ...

Page 2: ...Down 5 Step Up Down 5 Appendix B DALI Networking Basics 6 Appendix C Wiring Diagram 6 Notes Install in a dry sheltered position Interior use only Installation should only be performed by a qualified professional Install in accordance with all appropriate wiring standards DALI is not SELV and installation must therefore follow appropriate standards Introduction The PosiTouch is capacitive touch sen...

Page 3: ...LED will turn on and the associated action will trigger accordingly Action Description Short Press A short press action occurs when a button is pressed and released in under 0 3s Long Press A long press action occurs when a button is pressed for longer than 0 3s When some DALI commands are assigned to a long press they are repeated until the button is released Release A release action occurs when ...

Page 4: ... on the DALI network these should only be set on 1 In order for these settings to take effect energise the DALI network with or after applying power to the fittings being controlled 5 Button Actions Here the action to perform for the 3 button states short press long press release can be configured 6 Selected Button Shows the button that is currently being configured You can also click on the butto...

Page 5: ...ination with the Go to Level command which uses the DALI Fade Time a reliable fade can be achieved Button Action To Dim Up To Dim Down Long Press Go to Level Go to Level Level 100 0 Release Stop Dim Stop Dim Dim up Down These commands will dim the level for a period of 200ms at the rate specified in DALI Fade Rate They cannot dim to off nor can they dim from off When these commands are assigned to...

Page 6: ... DALI control line input to a ballast is polarity insensitive meaning there is no or A DALI network can consist of up to 64 ballasts Wiring of the DALI network can be almost any fashion be it a daisy chain star or branch as per the below figure Figure 2 DALI Network Topologies Cable sizes should follow the guide given in the table below Lead Length Minimum Lead Diameter Up to 100m 0 5mm2 100 150m ...

Reviews: