background image

PosiTouch DALI - Lighting Controller 

User Manual 

7.0 - 23 November 2020 

 

 

digilin.com.au 

Page 3 of 6 

+617 3899 1267 

 

Specifications 

Physical 

 

 

U n i t s  

Dimensions 

75 x 11.5 x 10 

mm 

Protrusion into wall 

28.5 

mm 

Weight 

28 

Inputs 

 

 

U n i t s  

Voltage (as per IEC62386) 

 22.5 

Current 

10 

mA 

Communications 

DALI (IEC62386) 

 

Installation 

Prior to installation of the PosiTouch, it should be configured using the PosiTouch 

Configuration Tool.  This configures the DALI commands associated with each 

button.  

 

Installation merely requires the connection of the 2 DALI wires.  The PosiTouch 

draws power from the DALI bus, so there is nothing further to connect.  Refer to 

Appendix B.  DALI Networking Basics for further information regarding DALI wiring. 

 

Operation 

The PosiTouch is operated simply by touching the buttons marked on the wall 

plate.  When a button is active its corresponding LED will turn on, and the 

associated action will trigger accordingly. 

 

A c t i o n  

D e s c r i p t i o n  

Short Press 

A short press action occurs when a button is pressed and released in under 0.3s. 

Long Press 

A long press action occurs when a button is pressed for longer than 0.3s.  When some DALI 

commands are assigned to a long press they are repeated until the button is released. 

Release 

A release action occurs when the button is released following a long press. 

Table 1 Button Actions 

Default Configuration 

The PosiTouch comes configured by default for basic on/off and dimming control, with the configuration of 

fade rate and fade time disabled. 

B u t t o n  

A d d r e s s  

D e f a u l t   A c t i o n  

Short Press 

Long Press 

Release 

Broadcast 

Go to 100% 

Go to 100% 

Stop Dim 

Broadcast 

Go to 75% 

Go to 75% 

Disabled 

Broadcast 

Go to 50% 

Go to 50% 

Disabled 

Broadcast 

Go to 0% 

Go to 0% 

Stop Dim 

Broadcast 

Go to 25% 

Go to 25% 

Disabled 

Broadcast 

Go to 10% 

Go to 10% 

Disabled 

Table 2 Default button actions. 

DALI Connection 

MicroUSB for use with 

Configuration Tool 

Figure 1 Rear view of the PosiTouch

 

Summary of Contents for PosiTouch

Page 1: ... 2020 Digilin Technologies Document Rev 7 0 23 November 2020 Product specifications are subject to change without notice PosiTouch DALI Lighting Controller User Manual ...

Page 2: ...Down 5 Step Up Down 5 Appendix B DALI Networking Basics 6 Appendix C Wiring Diagram 6 Notes Install in a dry sheltered position Interior use only Installation should only be performed by a qualified professional Install in accordance with all appropriate wiring standards DALI is not SELV and installation must therefore follow appropriate standards Introduction The PosiTouch is capacitive touch sen...

Page 3: ...LED will turn on and the associated action will trigger accordingly Action Description Short Press A short press action occurs when a button is pressed and released in under 0 3s Long Press A long press action occurs when a button is pressed for longer than 0 3s When some DALI commands are assigned to a long press they are repeated until the button is released Release A release action occurs when ...

Page 4: ... on the DALI network these should only be set on 1 In order for these settings to take effect energise the DALI network with or after applying power to the fittings being controlled 5 Button Actions Here the action to perform for the 3 button states short press long press release can be configured 6 Selected Button Shows the button that is currently being configured You can also click on the butto...

Page 5: ...ination with the Go to Level command which uses the DALI Fade Time a reliable fade can be achieved Button Action To Dim Up To Dim Down Long Press Go to Level Go to Level Level 100 0 Release Stop Dim Stop Dim Dim up Down These commands will dim the level for a period of 200ms at the rate specified in DALI Fade Rate They cannot dim to off nor can they dim from off When these commands are assigned to...

Page 6: ... DALI control line input to a ballast is polarity insensitive meaning there is no or A DALI network can consist of up to 64 ballasts Wiring of the DALI network can be almost any fashion be it a daisy chain star or branch as per the below figure Figure 2 DALI Network Topologies Cable sizes should follow the guide given in the table below Lead Length Minimum Lead Diameter Up to 100m 0 5mm2 100 150m ...