background image

CMi4160 

– LoRaWAN

®

 Module 

 

19  

02/2021 

DIB 

Field 

Size 

Data type 

Description 

Rt temp 

4 bytes  

INT16 

Return temperature (°C) 
 

025Exxxx = °C, 1 decimal 

Meter 

address 

10 bytes  

According to 

M-Bus 
EN13757-3 

identification 
field 

Meter address 

 
Byte 0-1 = DIF/VIF code 

Byte 2-5 = Meter ID, BCD8 
Byte 6-7 = Meter manufacturer 
Byte 8 = Meter version 

Byte 9 = Device type 

Error flags 

4 bytes 

INT8 

Error and warning flags 

 
01FD17xx 
 

For further information about Error 
flags please refer to the meter’s user 

guide  

Table 13: Payload, message format Combined heat/cooling 

 

6.7.3

 

METER COMMUNICATION ERROR MESSAGE 

The payloads using M-Bus encoded data uses the Function field of the DIF to indicate errors. In this 
case it is set to  “value during  error state” (M-Bus standard  EN 13757-3:2013)  and  the value sent 

should not be used. A typical case for this is when the module is unable to communicate with the 
meter and retrieve meter values, in which case all the fields in the payload have the DIF indicating 
“value during error state”. 
In case of erroneous data or if the module is unable to communicate with meter, bit 4-5 of the bit of 

the DIF code (first byte of each index field) will be set to 11b. For example, a DIF code of 0x02 will 
be set to 0x32 in case of error. (This applies to all message format except JSON.) For message format 
JSON, the actual value will be replaced with “null” in case of error state. If no meter communication 

is possible at all, all fields have this error indication set. 
 

6.8

 

DOWNLINK 

CMi4160  supports  configuration  via  downlink,  i.e.  sending  commands  to  an  end-device  via  the 

LoRaWAN

®

 network. Note that this feature should only be used sparingly due to bandwidth 

consideration. Communication via downlink is sent on port 2 and can only be made in a short window 
after an uplink transmission from module to server. Therefore, time-critical communication should not 

be performed over downlink. 
 

 

 

Summary of Contents for LoRaWAN CMi4160

Page 1: ...CMi4160 LoRaWAN Module For Diehl Metering SHARKY 775 User guide...

Page 2: ...ection of battery pack 5 5 3 3 Connection of antenna 5 5 3 4 Network preparation 6 5 3 5 Activation 6 5 3 6 Switch off reboot module 7 6 Administration reference 7 6 1 Purpose 7 6 2 Security and acces...

Page 3: ...nnel and to incorporate these guidelines into all user guides supplied with the product Failure to comply with these precautions violates safety standards of design manufacture and intended use of the...

Page 4: ...ttery lifetime The module s EcoMode feature enables the module to achieve a battery lifetime of at least 11 1 years No meter installation needed As soon as the meter connectivity module has been mount...

Page 5: ...r interface ribbon cable 3 5 3 2 CONNECTION OF BATTERY PACK The CMi4160 is delivered with a battery pack Connect the battery pack to the module s power connector 4 and gently place it with in the mete...

Page 6: ...etwork join field in the Inspect tab of the OTC App Network join When activated CMi4160 will attempt to join the LoRaWAN network The phase is indicated by short flash on red light then green and red L...

Page 7: ...f CMi4160 6 2 SECURITY AND ACCESS CONTROL CMi4160 has a configuration lock feature which prevents unauthorized access to the module When configuration lock has been enabled a Product Access Key will b...

Page 8: ...attery life is guaranteed by adapting the transmit interval of the module to current signal conditions On Readable Writeable Readable Writeable Transmit interval Sets the number of minutes between eac...

Page 9: ...e meter is assumed to be in standard local time no DST When synchronizing time in the meter using the OTC App local standard time is always used even if DST is in effect The timestamped meter data sen...

Page 10: ...oMode table If a lower transmit interval is needed for the specific data rate in order to achieve 11 years of battery life the module will adjust the parameter accordingly Table 3 shows the transmit i...

Page 11: ...s presented Standard Figure 5 illustrates the structure of message format Standard For a detailed description of the payload see Table 5 Figure 5 Structure message format Standard DIB Field Size Data...

Page 12: ...m3 h 023Fxxxx xxxx 10 m3 h 5 Fw temp 4 bytes INT16 Forward temperature C 0258xxxx xxxx 0 001 C 0259xxxx xxxx 0 01 C 025Axxxx xxxx 0 1 C 025Bxxxx xxxx C 6 Rt temp 4 bytes INT16 Return temperature C 025...

Page 13: ...address 10 bytes According to M Bus EN13757 3 identification field Meter address Byte 0 1 DIF VIF code Byte 2 5 Meter ID BCD8 lsByte msByte Byte 6 7 Meter manufacturer lsByte msByte Byte 8 Meter vers...

Page 14: ...day and the data message at least regulated by transmit interval parameter or EcoMode once every day The transmit interval can only be set the values listed in Table 10 Note that although the meter r...

Page 15: ...INT32 Volume m3 0413xxxxxxxx xxxxxxxx 0 001 m3 0414xxxxxxxx xxxxxxxx 0 01 m3 0415xxxxxxxx xxxxxxxx 0 1 m3 0416xxxxxxxx xxxxxxxx m3 0417xxxxxxxx xxxxxxxx 10 m3 3 Meter address 10 bytes According to M...

Page 16: ...te to indicate that the value is not valid Table 11 Payload message format Scheduled daily redundant Scheduled Extended The data message of Scheduled mode Extended contains all the data fields from me...

Page 17: ...flags 13 bytes INT72 Byte 0 3 DIF VIF codes 0x0DFF21E9 Byte 4 Error flags Byte 5 8 Meter ID BCD8 lsByte msByte Byte 9 10 Meter manufacturer lsByte msByte Byte 11 Meter version Byte 12 Device type 5 M...

Page 18: ...040Fxxxxxxxx xxxxxxxx 10 MJ 04FB0Dxxxxxxxx xxxxxxxx MCal 04FB0Exxxxxxxx xxxxxxxx 10 MCal 04FB0Fxxxxxxxx xxxxxxxx 100 MCal 2 Cooling energy 8 9 bytes INT32 Energy consumption Wh J Cal 0483FF02xxxxxxxx...

Page 19: ...is unable to communicate with the meter and retrieve meter values in which case all the fields in the payload have the DIF indicating value during error state In case of erroneous data or if the modul...

Page 20: ...pact 0x20 Message format JSON 0x21 Message format Scheduled daily redundant 0x22 Message format Scheduled Extended 0x23 Message format Combined heat cooling 0x00070101F Sets the message format to comp...

Page 21: ...erating humidity 0 93 RH No condensation Operating altitude 2 000 m Usage environment Indoors Storage temperature 20 60 C Radio characteristics Operating Frequency Frequency Band 863 1 864 9 K 865 1 8...

Page 22: ...ion Description DIB Data Information Block DIF Data Information Field VIF Value Information Field MCM Meter Connectivity Module 9 2 NUMBER REPRESENTATION Decimal numbers are represented as normal numb...

Page 23: ...CMi4160 LoRaWAN Module 23 02 2021...

Page 24: ...www diehl com metering PfM 02 2021 Specifications subject to change without notice Diehl Metering GmbH Industriestra e 13 91522 Ansbach Phone 49 981 1806 0 Fax 49 9811806 615...

Reviews: