Breakdown service procedure:
The operator is not working:
•
Check the electrical power supply;
•
Check that the disconnecting switch on the operator is set to ‘’ON’’;
•
Check that the thermal relay is released;
•
Check the fuses on the control panel;
•
Check if a remote button shut off or a key switch is activated;
•
If the operator is still not working following all the previous verifications,
contact a specialized technician.
The gate is not automatically closing after completing the opening cycle:
•
Check if the gate has entirely completed the opening cycle by manually
pressing the limit switch;
•
Check if the security devices, such as detection loops, photoelectric cell or
any other equipment are not still activated;
•
Make sure that the automatic closing function is activated (the potentiometer
of the PLC is ‘’OFF’’).
Service call – minimum 2 hours (plus parts and taxes)
For maintenance, see on next page the recommended steps to follow.