background image

4  

P a g e

 

 

Product Specification 

 

Voltage 

220 – 240V @ 50Hz with 9V battery 

backup 

Optical Alarm Button – dual 

function 

 

Push to Test 

 

Activate Silence (hush) mode 

Current 

< 100mA 

Silence (Hush) Time (approx.) 

8 minute 

Battery Specification 

9V battery DC.  Brands: 

Gold Peak: GP1604S, GP1604A, or 

Raymax: 6LR61 

Long life - CR9V, EVE  

Sound Pattern 

 

ISO8201 (BI 0.5s - pause 0.5s - BI 

0.5s - pause 0.5s - BI 0.5s - pause 

1.5s, with the RED LED flash, then 

repeat) 

Battery Life 

Over one year – 1163 

10 year – 1164 

Alarm Volume 

> 85dB(A) at 3 meters 

Inter-linkable 

up to 12 detectors 

Alarm Sensitivity 

Optical:  0.114 - 0.160dB/m: 

Compliance 

 

Optical:  EN14604:2005/AC:2008 

Product Disposal 

These alarms come under the Waste Electrical & Electronic Equipment Regulations and must be disposed of in 

accordance to these Regulations. 

 
 

Testing the Alarm 

Important Safety Information: 

 

Test the alarm to ensure proper operation. 

1.

 

Test alarm by pressing and holding the test button until it sounds.  

The alarm will sound 3 short beeps – 1.5 seconds pause, and then 

repeat until the button is released. 

2.

 

If multiple alarms are installed within the dwelling, test each alarm.  

Each alarm should trigger other alarms connected within 10 seconds. 

 

Do not attempt to test the alarm with smoke or heat from a flame.  Do not 

ignite combustible materials and start a fire. 

 

If no alarm sounds, the unit has a defective battery or other failure.  Refer 

to “Trouble Shooting” section for a solution. 

 

Caution:  Due to the loudness (85 decibels) of the alarm, always stand an 

 

arms-length always from the unit when testing.  Test the alarm 

 

weekly to ensure proper operation. Erratic or low sound 

 

coming from your alarm may indicate a defective alarm. 

NOTE: WEEKLY TESTING IS REQUIRED 

 

 

1.

 

This alarm must not be connected to any other manufacturer alarms. 

2.

 

These alarms, item numbers, 1163,1165, 1164 and 1166 are only 

compatible with each other and CO alarm 1169; they are not 

compatible with previous generations. 

3.

 

Test alarm weekly to ensure proper operation.  The test button 

accurately tests smoke alarm functions. Do not use any other test 

method. 

4.

 

The alarm must not be exposed to dripping or splashing water. 

5.

 

These alarms are primarily intended for use in single family 

occupancy private dwellings.  In multifamily buildings, each individual 

living unit should have its own alarms. Do not install in non-

residential buildings.  This smoke alarm is not a substitute for a 

complete alarm system. 

6.

 

The alarm may not alert every household member every time. The 

alarm horn is loud in order to alert individuals to a potential danger. 

However, there may be some circumstances where a household 

member may not hear the alarm (e.g. excessive outdoor or indoor 

noise, sound sleepers, drug or alcohol usage, the hard of hearing).  If 

you suspect that this alarm may not alert a household member, 

install and maintain specialty alarms.  Household member must hear 

the alarms warning sound and quickly respond to it to reduce the risk 

of damage, injury, or death that may result from fire.  If a household 

member is hard of hearing, install special alarms with lights or 

vibrating devices to alert occupants. 

7.

 

The alarms are designed to give audible warning of a developing fire 

and can only sound their alarms when they detect smoke, 

combustion particles in the air or abnormal ambient temperature.  

Many fires, however, are fast burning and in these circumstances the 

alarm may not be triggered quick enough to ensure a safe escape. 

8.

 

The alarms have limitations.  This alarm is not fool proof and is not 

warranted to protect lives or property from fire.  The alarms are not 

a substitute for insurance.  Occupants should insure their lives and 

property.  In addition, it is possible for the alarm to fail at any time.  

For this reason, you must test the alarm weekly and replace unit 

after 10 years. 

9.

 

Do not paint the alarms. 

10.

 

Check the alarms on reoccupation of the premises after a vacation. 

 

Maintenance 

 

Cleaning 

The alarm should be cleaned on a monthly basis as a minimum. To do this: 

 

Turn off the electrical supply to the alarm. 

 

Use a vacuum cleaner with the soft brush to vacuum all sides and 

covers of alarm to remove dust, dirt, and debris.  Be sure all the 

vents are free of debris. 

 

Use a damp cloth to clean the alarms cover. 

 

Turn the electrical supply to the alarm on. 

 

Battery  

The battery should be replaced annually on 1163, see ‘Replacing the 

Battery’.  

1164 model has a sealed 10-year battery and must not be replaced.  

Trouble Shooting 

 

Problem 

Remedy 

Problem 

Remedy 

The green LED does not light up 

1.

 

Check electrical power supply 

is switched on 

2.

 

Check the electrical connector 

is properly connected to the 

alarm 

3.

 

If the problem still exists, 

replace the alarm 

The alarm chirp occurs every 32 

seconds approx. and goes into fault 

mode 

1.

 

Clean alarm.  Refer to 

“Maintenance ” 

2.

 

If the problem still exists, 

replace the alarm 

Alarm does not sound when tested.  

Note: push test button for at least 

five seconds while testing! 

1.

 

Ensure that the battery and 

electrical connector is 

properly connected 

2.

 

Clean alarm 

3.

 

If the problem still exists, 

replace the alarm 

The alarm sounds intermittently or 

when residents are cooking, taking 

showers, etc. (false alarming) 

1.

 

Press test button to pause 

alarm 

2.

 

Open window or fan alarm to  

3.

 

Clean alarm 

The alarm chirp occurs every 32 

second approx. at the same time as 

the red LED flashes once 

The battery needs replacing, refer 

to “Replacing the Battery” 

The alarm sounds different from its 

usual sound 

4.

 

Clean alarm 

5.

 

If the problem still exists, 

replace the alarm  

Warning: Do not disconnect battery to quiet an unwanted alarm. This will remove your protection. Fan the air or open window to remove smoke or dust. 

 

S24 

INS0093 V1.5    07/21   NPD 0648/0534/PI 0146

 

Deta Electrical Company Ltd 

UK: Panattoni Park  Luton Road  Chalton  Bedsfordshire  LU4 9TT 

EU: Unit 16 Ashbourne Ind. Est.  Ashbourne  Co. Meath  A84 W972 

deta.co.uk | Technical Helpline: +44(0)1582 544 548 

 

Summary of Contents for SILENT 100 12V

Page 1: ...ng rather than the electrical installation itself You will be reassured to know therefore that all fittings come with a minimum of a one year guarantee from ourselves and will be corrected or replaced promptly WELCOME If you require any further works to be carried out please do not hesitate to contact our Head Office on 0117 9090517 and we will be more than happy to deal with your enquiry Should y...

Page 2: ...r fuse board as it s commonly known It s usually in the hallway or under stairs cupboard The consumer unit is connected to the electricity meter by the meter tails and all the wiring in your home starts at this point You will see that the sockets cooker lights etc are all on different circuits This is so each circuit can be wired in the appropriate size cable larger cable for the cooker smaller ca...

Page 3: ...fails to reset unplug all plugs in the ring main TV Kettle toaster heater etc Try to reset the RCD RCBO If power is restored then plug in the appliances one by one until loss of power Leave faulty appliance unplugged and restore power Repair or replace faulty appliance If all trip switches are off and all appliances are unplugged and the RCD RCBO still won t reset please contact customer care WHAT...

Page 4: ...Deta Smoke Detector Datasheet 4 ...

Page 5: ...or 1155 Standards Optical BS EN 14604 2008 Heat BS 5446 2 2003 Carbon Monoxide CO BS EN 50291 1 2018 Safety Alarms DS 0242 V1 1 NPD 0648 PI 0146 02 2021 Deta Electrical Company Ltd UK Panattoni Park Luton Road Chalton Bedfordshire LU4 9TT UK EU Unit 16 Ashbourne Industrial Estate Ashbourne Co Meath A84 W972 Ireland Tel 44 1582 544 548 technical deta co uk Smoke Heat and Carbon Monoxide Alarms Desc...

Page 6: ...Deta Optical Detector User Instructions 6 ...

Page 7: ...entrally on a ceiling within a room it is recommended to locate it a minimum of 300mm 12 from the side wall see Diagram 2 If space restrictions prevent this e g narrow corridors landings it must not be located closer than 300mm 12 from the side wall Diagram 2 Put a smoke alarm at both ends of a hallway corridor or large room if it is more than 9000mm 30 long In rooms with an A shaped peaked ceilin...

Page 8: ...alarm from the base by using a screw insert into the slots and flexing outwards see diagram 4 Diagram 4 3 Remove the electrical connector from the alarm by squeezing the locking arms 4 Select the cable entry on the base and remove the cut out Cable entry can either be through the back of the base or via surface mounted mini trunking Leave the gasket in place to prevent dust ingress into the alarm ...

Page 9: ... of escape is developed and practiced A floor plan indicating doors and windows should be made and if possible that two routes of escape are established It is also recommended that fire extinguishers are installed and maintained DANGER If the alarm sounds and it is not being tested it means the unit is sensing smoke THE SOUND OF THE ALARM REQUIRES YOUR IMMEDIATE ATTENTION AND ACTION User Maintenan...

Page 10: ...hold member must hear the alarms warning sound and quickly respond to it to reduce the risk of damage injury or death that may result from fire If a household member is hard of hearing install special alarms with lights or vibrating devices to alert occupants 7 The alarms are designed to give audible warning of a developing fire and can only sound their alarms when they detect smoke combustion par...

Page 11: ...Deta Heat Detector User Instruction 11 ...

Page 12: ...12 ...

Page 13: ...13 ...

Page 14: ...14 ...

Page 15: ... 1 02 21 NPD0648 0532 Deta Electrical Company Ltd UK Pana oni Park Luton Road Chalton Beds LU4 9TT EU Unit 16 Ashbourne Ind Est Ashbourne Co Meath A84 W972 Ireland deta co uk Technical Helpline 44 0 1582 544 548 ...

Page 16: ...Deta CO Detector User Instructions 16 ...

Page 17: ...ng in the centre of the room places it closest to all points in the room Ceiling mounting is preferred in ordinary residential dwellings When mounting an alarm on the ceiling locate it at a minimum of 500mm 20 from the side wall See Diagram 2 500mm Minimum Diagram 2 In rooms with an A shaped peaked ceiling a sloped or cathedral ceiling install a CO alarm between 500mm and 1500mm from the highest p...

Page 18: ...se by using a screw insert into the slots and flexing outwards see diagram 4 Diagram 4 3 Remove the electrical connector from the alarm by squeezingthe locking arms 4 Select the cable entry on the base and remove the cut out Cable entry can either be through the back of the base or via surface mounted mini trunking Leave the gasket in place to prevent dust ingress into the alarm 5 Mount the base i...

Page 19: ... the presence of Carbon Monoxide can be fatal DANGER If the alarm sounds and it is not being tested it means the unit is sensing Carbon Monoxide gas THE SOUND OF THE ALARM REQUIRES YOUR IMMEDIATE ATTENTION AND ACTION Plan of Escape It is recommended that a plan of escape is developed and practiced A floor plan indicating doors and windows should be made and if possible that two routes of escape ar...

Page 20: ...ourne Ind Est Ashbourne Co Meath A84 W972 Ireland deta co uk Technical Helpline 44 0 1582 544 548 20 Testing the Alarm Important Safety Information Test the alarm to ensure proper operation 1 Test alarm by pressing and holding the test button until it sounds The alarm will sound 4 short beeps 5 seconds pause and then repeat until the button is released 2 If multiple alarms are installed within the...

Page 21: ...21 Envirovent 100 document ...

Page 22: ...ealed For Life Ball Bearings Silent Elastic Blocks Backdraught Shutter Adjustable Timer Intelligent Timer Operates after 50 seconds Adjustable Humidity Sensor PIR Pullcord Silver Finish Adjustable Timer After disconnection the shut off time can be delayed between 1 and 30 minutes This has a factory set level of 1 minute Intelligent Timer Operates after a 50 second delay Thereafter the fan operates...

Page 23: ...ly in advance if required Motor Is a 230V 50Hz or a 12V 50Hz A C motor which is assembled on silent elastic blocks and fitted with ball bearings for enhanced working life Fan The impeller is axial flow type Servicing Maintenance The extract fan only requires periodical cleaning using a cloth impregnated with a soft detergent Guarantee The SILENT 100 is covered by a 5 year warranty Compliance CE 40...

Page 24: ...24 Envirovent 150 document ...

Page 25: ...125S SIL125T SIL125HT SIL150S SIL150T SIL150HT SIL150P SIL150HTP Adjustable Timer After disconnection the shut off time can be delayed between 1 and 30 minutes Adjustable Humidity Sensor The level of humidity for the bathroom can be chosen from between 60 and 90 RH The extract fan will continue to work long enough to reach the selected level Pullcord Supplied with pullcord override MODEL A B C D Ø...

Page 26: ...Timer SILENTUB100 SILMV160 100S SILMV160 100T Adjustable Timer After disconnection the shut off time can be delayed between 1 and 30 minutes Installation SILENT MV 160 100 The low profile design of the SILENT MV 160 100 makes it the most effective solution for installations where space is restricted such as false ceilings The unique design of the support bracket allows the central cartridge holdin...

Page 27: ...27 Envirovent 100 and 150 ...

Page 28: ...28 SILENT Instruction leaflet 01 14 ...

Page 29: ...29 Fig 1a Fig 1b 1 2 3 4 5 1 2 3 4 5 6 3 02 14 ...

Page 30: ...30 03 14 Fig 4 Fig 3 Fig 2 L N L N Ls L N L N Ls 4 ...

Page 31: ...31 04 14 L N Fig 7 Fig 6 Fig 5 L N Ls L N Ls T min T min A 5 20 30 L N SILENT T SILENT IT SILENT PIR 5 ...

Page 32: ...32 05 14 Fig 10 Fig 9 Fig 8 L N L N Ls L N L N Ls 2 3 4 1 5 6 7 8 ON 2 2 3 3 4 4 1 1 5 5 6 6 7 7 8 8 ON OFF 6 ...

Page 33: ...33 06 14 Fig 1 1 L N L N Ls SILENT 100 SILENT 125 150 A B E D C ØF MODEL A B C D E ØF SILENT 100 158 158 109 3 84 6 79 98 9 SILENT 125 180 180 119 89 80 118 SILENT 150 214 214 149 113 5 95 147 SILENT 7 ...

Page 34: ...ered and that the details on the instruction plate fulfil your requirements The installation and the disconnection device of the fixed installation used must be in accordance with the installation regulations in force in each country Once the product has been installed pass this booklet to the end user Recommendations IMPORTANT Before installing and wiring the unit ensure that the mains supply is di...

Page 35: ...tmosphere or via a ducted system fig 2 The unit can be mounted on the wall or ceiling using the 4 raw plugs and the screws provided Make a hole in the wall or ceiling of diameter SILENT 100 105 to 107 mm SILENT 125 125 to 132 mm SILENT 150 160 to 158 mm If using the EnviroVent high rise wall kit please refer to kit for core drill size If the unit is to be installed in a ducted system use the follow...

Page 36: ...ighting circuit To set the timer turn the potentiometer on the printed circuit board as fig 7 To reduce the run on time turn anticlockwise min 1 minute To increase the run on time turn clockwise max 30 minutes SILENT 100 IT This version is only available as SILENT 100 This model is provided with an adjustable over run timer The timer allows the fan to continue to operate for the selected period aft...

Page 37: ...n for hours without stopping the Interval function allows the fan to switch off automatically one hour after it began to run The extractor keeps switched off during the set time for interval function If the humidity level is still above the set level when the time interval is over the extract fan switches on again and run during one hour To select this function put the dip switch 1 to position ON To...

Page 38: ...with the dip switch 8 Factory settings Interval function OFF Interval time 4h Humidistat 60 HR Timer 1 minute Start up timer function OFF SILENT 100 PIR This version is only available as SILENT 100 Models provided with a PIR detector The unit starts automatically when a movement is detected with maximum distance of 4 meters fig 9 They are also fitted with an adjustable run on timer 1 to 30 minutes a...

Page 39: ...tegories Steel and iron Plastics Electronic scrap After Sales Service We recommend you do not dismantle or remove any other parts than those mentioned as any tampering would automatically cancel the guarantee Thank you for choosing EnviroVent If you experience any problems please call our dedicated Technical Team on 0345 27 27 810 EnviroVent EnviroVent House Hornbeam Business Park Harrogate HG2 8P...

Page 40: ...e to the fitting wiring instructions relevant guidance documents and by a competent and qualified person proof may be required please return the product to the place of purchase for a replacement Warranty Conditions Exclusions Please note that a receipt will be required as proof of purchase Fans bought from an unapproved source including but not limited to auction websites are not covered by the war...

Page 41: ...41 14 14 Ref 9023065401 EnviroVent Ltd EnviroVent House Hornbeam Business Park Harrogate HG2 8PA 01423 810 810 info envirovent com www envirovent com ...

Reviews: