2
P a g e
Installation
This alarm should be installed as late as possible within the schedule of
works, particularly in new build properties, e.g. after decorating and
making good works.
•
This alarm must not be connected to any other manufacturer alarms.
•
These alarms, item numbers, 1163, 1165, 1164 and 1166 are only
compatible with each other and 1169 CO alarm; they are not
compatible with previous generations.
Important
The circuit powering the safety alarms must be unswitched, i.e.
permanently live. The electrical supply for mains powered alarms with
battery back-up, as required by BS 5839-6 Grade D1 and D2 systems, must:
i)
Be an independent circuit from the consumer unit where no other
electrical equipment is connected, or
ii)
A separately electrically protected, regularly used local lighting circuit
Also, where alarms are interlinked, they must be connected to a single
circuit.
Safety Instructions
•
Ensure the power supply is switched off before installation and
during maintenance.
•
These alarms should be installed by a competent person, e.g. a
qualified electrician.
•
These alarms must be installed in accordance with the current
edition of the IET Wiring Regulations BS7671 and the Code of
Practice for the design, installation, commissioning and maintenance
of fire detection and fire alarm systems in domestic premises
BS 5839-6.
•
Important:
Remove the alarm from the circuit for insulation
resistance testing.
If in doubt, contact a qualified electrician.
Installation
1.
Remove the dust cover.
2.
Release the alarm from the base by using a screw insert into the slots
and flexing outwards, see diagram. 4
Diagram 4
3.
Remove the electrical connector from the alarm by squeezing the
locking arms.
4.
Select the cable entry on the base and remove the cut out. Cable
entry can either be through the back of the base or via surface
mounted mini-trunking. Leave the gasket in place to prevent dust
ingress into the alarm.
5.
Mount the base in the desired location using the wall plugs and
screws, as required. See Diagram 5.
Diagram 5
6.
Terminate the live, neutral and earth supply cables and interlink cable
if alarms are interlinked. See Diagram 6.
Diagram 6.
L (Live):
Brown conductor
N (Neutral):
Blue conductor
E (Earth):
Green / Yellow
I (Interlink):
Grey (if using 6243Y cable)
7.
A maximum of 12 alarms can be interlinked. If more than 12 alarms
are interlinked it may result in permanent damage.
8.
For multiple alarm installations use three core and earth cable
between all the alarms to be interlinked and connect the third core of
that cable to terminal marked I. DO NOT use the earth wire for the
interlink wire. This must be treated as live, i.e. insulated and sleeved.
9.
Connect the battery:
•
On 1163 by opening the battery cover and inserting it.
•
On 1164 by pulling tab on the sealed battery cover.
Test the alarm by pressing the TEST button. See Diagram 7.
10.
Refit the electrical connector.
Diagram 7
11.
Attached the alarm to the base
12.
Replace the dust cap
13.
Turning on the electrical power. The green LED should be lit when the
alarm is operating from the power supply.
14.
Test the alarm, including the interlink feature if more than one alarm is
installed.
Important:
Remove the alarm from the circuit for insulation
resistance testing.
8
Summary of Contents for SILENT 100 12V
Page 4: ...Deta Smoke Detector Datasheet 4 ...
Page 6: ...Deta Optical Detector User Instructions 6 ...
Page 11: ...Deta Heat Detector User Instruction 11 ...
Page 12: ...12 ...
Page 13: ...13 ...
Page 14: ...14 ...
Page 16: ...Deta CO Detector User Instructions 16 ...
Page 21: ...21 Envirovent 100 document ...
Page 24: ...24 Envirovent 150 document ...
Page 27: ...27 Envirovent 100 and 150 ...
Page 28: ...28 SILENT Instruction leaflet 01 14 ...
Page 29: ...29 Fig 1a Fig 1b 1 2 3 4 5 1 2 3 4 5 6 3 02 14 ...
Page 30: ...30 03 14 Fig 4 Fig 3 Fig 2 L N L N Ls L N L N Ls 4 ...