To modify settings, press the
ENTER
key until the desired set point is selected
and use the arrow keys until the desired value is shown. Press the
ENTER
key to accept set point value. See the graphs in Figures 32 through 34 for an
illustration of the operation of the deadbands and differentials. Figure 32
details the humidity control. Figure 33 details the heating and cooling control.
Figure 34 details the pool heating control.
Press
the
DOWN
key for the next Tuning screen. To return to the Service
Menu, press the
Esc
key.
Figure 31
50%
49%
Zone Relative Humidity
LC/LV Humidity Control
Setpoint: 50% RH
Differential: 1% RH
Compressor is required when RH is over 50%. Compressor is off under 49% RH, but
between 50% & 49% a requirement for the compressor depends on a rising or sinking RH.
Time
Compressor Required for Dehumidification
Compressor Off
Figure 32