www.desatech.com
119426-01F
33
Figure 50 - Positioning the Thermostat
Sensing Bulb in the Vertical Position
with the Capillary at the Bottom
Capillary
Thermostat
Sensing Bulb
Do Not
Crimp
Capillary
Adhesive-
backed
Mounting
Clip
If your fireplace has glass doors, position
sensing bulb directly behind door gap on
right bottom side (see Figure 49).
4. The mounting clip must be a minimum
of 3" from bottom of fireplace to prevent
crimping of capillary. Once you have
decided on a location, clean the area
thoroughly. Remove the paper backing
from the adhesive on back of mounting
clip. Press the clip into the new location
so that the thermostat sensing bulb will
be positioned vertically with the capillary
at the bottom (see Figure 50). Slide the
thermostat sensing bulb into the clip.
IMPORTANT:
Do not crimp capillary.
OPTIONAL POSITIONING
OF THERMOSTAT SENSING
bULb
Continued
SPECIFICATIONS
VUL18PT, VUL18PR, VUL36PR
• Rating (Variable): 19,000/30,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Electronic
• Manifold Pressure: 7.9" W.C.
• Inlet Gas Pressure (in. of water):
Max - 14" W.C., Min* - 11" W.C.
VUL18NT, VUL18NR, VUL36NR
• Rating (Variable): 19,000/28,000 Btu/Hr
• Type Gas: Natural
• Ignition: Electronic
• Manifold Pressure: 3.4" W.C.
• Inlet Gas Pressure (in. of water):
Max - 10.5" W.C., Min* - 5" W.C.
VUL24PT, VUL30PT, VUL36PT,
HRB3624PT, VUL24PR, VUL30PR,
VUL36PR, HRB3624PR
• Rating (Variable): 25,000/36,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Electronic
• Manifold Pressure: 7.9" W.C.
• Inlet Gas Pressure (in. of water):
Max - 14" W.C., Min* - 11" W.C.
VUL24NT, VUL30NT, VUL36NT,
HRB3624NT, VUL24NR, VUL30NR,
VUL36NR HRB3624NR
• Rating (Variable): 25,000/36,000 Btu/Hr
• Type Gas: Natural
• Ignition: Electronic
• Manifold Pressure: 3.4" W.C.
• Inlet Gas Pressure (in. of water):
Max - 10.5" W.C., Min* - 5" W.C.
*For purpose of input adjustment
Figure 49 - Installing Thermostat Sensing
Bulb Behind Glass Doors
Adhesive-
backed
Mounting Clip
Glass Doors
Thermostat
Sensing Bulb