INSTALLATION

Continued

NOTICE: Manual control heaters 

may be used as a vented product. 

If so, you must always run heater 

with chimney flue damper open. 

If  running  heater  with  damper 

open, noncombustible material 

above fireplace opening is not 

needed. Go to 

Installing Damper 

Clamp  Accessory  for  Vented 

Operation

, page 12.

Minimum Noncombustible Material 
Clearances
If Not Using Mantel

Note: 

If using  a mantel  proceed  to If Using 

Mantel. If not using a mantel, follow the infor

-

mation on this page.
You  must  have  noncombust ble  material(s) 

above  the  fireplace  opening.  Noncombus

-

tible  materials  (such  as  slate,  marble,  tile, 

etc.) must be at least 1/2" thick. With sheet 

metal,  you  must  have  noncombustible  ma

-

terial  behind  it.  Noncombustible  material 
must extend at least 8" up (for all models). 

If noncombustible material is less than 12", 
you must install the fireplace hood accessory 

(24" and 30" Models Only). See Figure 5 for 
minimum clearances.

If Using Mantel

You  must  have  noncombust ble  material(s) 

above the fireplace opening. Noncombustible 
materials  (such  as  slate,  marble,  tile,  etc.) 
must be at least 1/2" thick. With sheet metal, 

you must have noncombustible material be-
hind it. Noncombustible material must extend 
at least 8" up (for all models). If noncombus-

tible material is less than 12", you must install 
the  fireplace  hood  accessory  (24"  and  30" 

Models Only). Even if noncombust ble mate-

rial is more than 12", you may need the hood 
accessory  to  deflect  heat  away  from  your 

mantel shelf. See Figure 5 and Figures 6 and 

7, page 9, for minimum clearances.

IMPORTANT:

 If you cannot meet these mini-

mum  clearances,  you  must  operate  heater 
with chimney flue damper open. Go to 

Install-

ing  Damper  Clamp  Accessory  for  Vented 
Operation

, page 12.

Heat Resistant
Material 

(A)

Figure 5 - Heat Resistant Material (Slate, 

Marble, Tile, etc.) Above Fireplace

Noncombustible 

Material 

Distance (A)

Requirements for Safe 

Installation

12" or more

Noncombustible mate-
rial OK.

Between 8" and 12"

24", 30" or 36" Models: 
Install fireplace hood 
accessory (GA6050, 

GA6052 or GA6053 see 

Accessories

, page 41). 

18" Model: Noncom-
bust ble material OK.

Less than 8"

Noncombustible mate-
rial must be extended 
to at least 8". See 

Between 8" and 12"

above. If you cannot ex-

tend material, you must 
operate heater with flue 

damper open.

MANTEL CLEARANCES

In addition to meeting noncombustible mate-

rial clearances, you must also meet required 
clearances  between  fireplace  opening  and 

mantel shelf. If you do not meet the clearances 

listed below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between man-

tel shelf and top of fireplace opening, a hood 
is not required (see Figure 6, page 11).

Determining Minimum Mantel Clearance 
When Using a Hood

If minimum clearances in Figure 6, page 11, 
are  not  met,  you  must  have  a  hood.  When 

using a hood there are still certain minimum 
mantel clearances required. Follow minimum 

clearances shown in Figure 7, page 11, when 

using hood.

Summary of Contents for VUL18NR

Page 1: ...ding Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performe...

Page 2: ...upplier WARNING This ap pliance is for installation only in a solid fuel burning masonry or UL127 fac tory built fireplace or in a listed ventless firebox en closure It is design certi fied for these...

Page 3: ...your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat exchanger insertorotheraccessorynot...

Page 4: ...eseproductsmay create a white powder residue within burner box or on adjacent walls and furniture 10 This heater needs fresh outside air ven tilation to run properly This heater has an Oxygen Depletio...

Page 5: ...s This heater may also be operated as a vented decorative ANSI Z21 60 product by opening the flue damper Non Thermostat Models Only Safety Device This heater has a pilot with an Oxygen Deple tion Sens...

Page 6: ...and ventilation However in buildings of un usually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed t...

Page 7: ...in the above example is a confined space because the actual Btu Hr used is more than the maximum Btu Hr the space can sup port You must provide additional fresh air Your options are as follows A Rewo...

Page 8: ...atthroughoutthe house In the event of a power outage you can use this heater as your primary heat source WARNING A qualified ser vice person must install heater Follow all local codes NOTICE Stateorlo...

Page 9: ...s but not both Gas type is indicated on the rat ingplate Fieldconversionisnot permitted INSTALLATION AND CLEARANCES For Vent Free Operation WARNING Maintain the minimum clearances If you can provide g...

Page 10: ...ombust ble mate rial is more than 12 you may need the hood accessory to deflect heat away from your mantel shelf See Figure 5 and Figures 6 and 7 page 9 for minimum clearances IMPORTANT If you cannot...

Page 11: ...antel Clearances When Using Hood Floor Clearances A If installing appliance on the floor level you must maintain the minimum distance of 14 to combustibles see Figure 8 B If combustible materials are...

Page 12: ...e vented operation see Fig ure 10 The damper clamp will keep damper open Installation instructions are included with clamp accessory See chart below for minimum permanent flue opening you must provide...

Page 13: ...lexible gas hose to gas regulator of heater see Figure 11 For Remote Ready models connect approved flexible gas hose to inlet side of gas con trol see Figure 12 IMPORTANT Hold gas regulator with wrenc...

Page 14: ...xternal regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of water If you do not re duce incoming gas pressure heater regula...

Page 15: ...all a sediment trap in supply line as shown in Figures 15 or 16 depending on your model Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and heat...

Page 16: ...ints from gas meter to equip ment shutoff valve for natural gas or propane LP supply to equipment shutoff valve for propane LP see Figure 18 or 19 Apply noncorrosive leak detection fluid to all joints...

Page 17: ...ws provided in hardware kit as shown in Figure 20 7 Disconnectjumperwirefromcontrolvalveat TPTH and TH locations see Figure 21 8 Install remote receiver into receiver bracket using pads and push butto...

Page 18: ...s will help you identify the log when installing It is very important to install these logs exactly as instructed Do not modify logs Only use logs supplied with heater Note Your appliance may vary fro...

Page 19: ...hole in middle left log seats over pin in front left log 7 For VUL36 models the front right and left logs are longer and are supported with brackets on each end see Figure 28 Place the left and right...

Page 20: ...e and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors clo...

Page 21: ...light Set control knob to any heat level between HI and LO 9 To leave pilot lit and shut off burners only turn control knob clockwise to the PILOT position CAUTION Do not try to ad just heating level...

Page 22: ...ARNING Burners will come onautomaticallywithinoneminute when the selector switch is in the ON position after the pilot is lit Remote Ready Models FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do...

Page 23: ...steps 4 through 8 page 22 and above 9 Slightly push in and turn control knob counterclockwise to the ON position 10 Wait one minute and switch selec tor switch to the ON position to light burners Not...

Page 24: ...control button on the hand held remote until burner turns on Hold the control button again until burner turns off see Figure 36 To Lock press both buttons on hand held remote control until light stops...

Page 25: ...he hand held remote to control the room temperature If the hand held remote is misplaced obstructed or for any reason cannot transmit to the receiver the receiver will shut off the fireplace This will...

Page 26: ...to excessive lint fromcarpeting pethair bedding material etc WARNING Failure to keep the primary air opening s of theburner s cleanmayresultin sooting and property damage Burner Injector Holder and Pi...

Page 27: ...hrough a drinking straw if compressed air is not available Cleaning AND MAINTENANCE Continued LOGS If you remove logs for cleaning refer to Installing Logs page 18 to properly replace logs Replace log...

Page 28: ...PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor...

Page 29: ...keep control knob pressed in 30 seconds 3 Wait one minute for safety interlock system to reset Repeat ignition operation 4 Fully open equipment shut off valve 5 A Contact local natural or propane LP...

Page 30: ...ntil air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installa tion clearances see pages 9 through 11 4 Clean burners see Clean ing and Maint...

Page 31: ...ter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Thermostat sensing bulb needs to be repositioned Thermostat Controlled Models Only 2 Hand held remote control is...

Page 32: ...he retain ing clamp see Figure 46 Note Do not remove the screw Make sure you tighten the screw after removing the thermostat sensing bulb IMPORTANT Do not force or bend the thermostat sensing bulb or...

Page 33: ...ing of Thermostat Sensing Bulb Continued Specifications VUL18PT VUL18PR VUL36PR Rating Variable 19 000 30 000 Btu Hr Type Gas Propane LP Ignition Electronic Manifold Pressure 7 9 W C Inlet Gas Pressur...

Page 34: ...llustrated Parts Breakdown Thermostat controlled Models VUL18NT VUL18PT VUL24NT VUL24PT VUL30NT VUL30PT VUL36NT VUL36PT HRB3624NT AND HRB3624PT PG 11 10 4 1 8 3 12 8 2 5 6 7 24 25 21 2 22 15 13 16 9 8...

Page 35: ...04 11 Front Burner Injector Natural 1 101004 10 Front Burner Injector Propane LP 1 101004 22 Front Burner Injector Natural 1 101004 06 Front Burner Injector Propane LP 1 13 112708 02 Thermostat Burner...

Page 36: ...STRATED PARTS BREAKDOWN Remote Ready Variable Control Models VUL18NR VUL18PR VUL24NR VUL24PR VUL30NR VUL30PR vul36nr vul36pr HRB3624NR HRB3624PR LPG 5 6 21 14 22 14 23 26 24 2 2 19 20 16 1 18 17 10 11...

Page 37: ...er Injector Natural 1 101004 10 Front Burner Injector Propane LP 1 101004 08 Front Burner Injector Natural 1 101004 06 Front Burner Injector Propane LP 1 13 112708 01 Remote Burner Tube 1 14 M12461 26...

Page 38: ...ight Log 1 4 113621 04 113621 10 113621 16 Middle Left Log 1 5 113621 05 113621 11 113621 11 Bottom Log Remote 1 113621 05 113621 19 113621 19 Bottom Log T stat 1 6 113621 06 113621 12 113621 18 Rear...

Page 39: ...6 113621 23 113621 23 Back Log 1 7 113621 24 113621 24 Left Small Front Log 1 8 113621 25 113621 25 Right Small Front Log 1 9 113621 26 113621 26 Left Control Cover Log 1 10 113621 27 113621 27 Right...

Page 40: ...hrb3624pt HRB3624NR HRB3624PR This list contains replaceable parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 41 of this manual 1 3 2 KEY NO...

Page 41: ...ually we will ask you to return the part to the factory Parts Not Under Warranty Contact authorized dealers of this product If they can t supply original replacement part s call DESAHearth Products at...

Page 42: ...ions such as stone or marble FB32C CIRCULATING FB32NC NON CIRCULATING SERIES Fireboxes Not Shown For 18 and 24 log models FB36CA FB42C SERIES CIRCULATING FB36NCA FB42NC SERIES fireboxes NON CIRCULATIN...

Page 43: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 44: ...2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 www desatech com 1 866 672 6040 NOT A UPC 119426 01 Rev F 03 07 119426 01...

Reviews: