The DESA warranty will be voided by, and
DESA disclaims any responsibility for the
following actions:
A) Modification of the appliance or any of the
components.
B) Use of any component part not approved
by DESA in combination with this appli-
ance.
C) Installation and/or operation in a manner
other than instructed in this manual.
D) The burning of anything other than the
type of gas approved for use in this gas
appliance.
Installation must conform with local codes or,
in the absence of local codes, with the cur
-
rent
National Fuel Gas Code, ANSI Z223.1
or
with the current
CAN/CSA B149 Installation
Codes
.
This appliance complies with
ANSI Z21.50-
2000
and
CSA 2.22-2000 as Vented Gas
Fireplaces
and is listed and tested by the
Canadian Standards Association
to the above
test standards.
NOTICE: This appliance is not
intended to be used as a primary
source of heat.
INTRODUCTION
Continued
WARNING: Installation of
this appliance should be done
by a qualified service person
well trained in the installation of
such appliances. You will also
need a building permit from
your local Building and Safety
Commissioner before installing
this appliance; otherwise your
insurance co. may not cover this
appliance.
CAUTION: Do not connect
appliance before pressure test-
ing gas piping. Damage to gas
valve may result and an unsafe
condition may be caused.
The appliance and it’s individual shutoff valve
must be disconnected from the gas supply
piping system during any pressure testing of
that system at test pressures in excess of 1/
psig (3.5 kPa).
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shutoff valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/ psig
(3.5 kPa).
For the purpose of input adjustment two
pressure taps (for IN and OUT pressures)
are provided on the gas control valve for test
gauge connections to the appliance.