background image

www.desatech.com

107886-01J

6

AIR FOR COMBUSTION 

AND VENTILATION

Continued 

DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have a con-

fined or unconfined space.

Space:

 Includes the room in which you will install 

heater plus any adjoining rooms with doorless pas-

sageways or ventilation grills between the rooms.
1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

  Space  size  20  ft.  (length)  x  16  ft. 

(width) x 8 ft. (ceiling height) = 2560 cu. ft. 

(volume of space)

 

If  additional  ventilation  to  adjoining  room  is 

supplied with grills or openings, add the volume 

of these rooms to the total volume of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support. 

 

 _______ (volume of space) x 20 = (Maximum 

Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (volume of space) x 20 = 

51,200 (maximum Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in 

the space.

 

Vent-free heater    ______________ Btu/Hr

 

Gas water heater*    ______________ Btu/Hr

 

Gas furnace 

  ______________ Btu/Hr

 

Vented gas heater    ______________ Btu/Hr

 

Gas fireplace logs    ______________ Btu/Hr

 

Other gas appliances*  + __________ Btu/Hr

 

Total                             = __________ Btu/Hr

 

* Do not include direct-vent gas appliances. Di-

rect-vent draws combustion air from the outdoors 

and vents to the outdoors.

 

Example:

 

Gas water heater    ______________ Btu/Hr

 

Vent-free heater      + _____________ Btu/Hr

 

Total                       = _____________ Btu/Hr

40,000
20,000
60,000

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 _______________Btu/Hr (maximum the space 

 

 

can support) 

 

 _______________Btu/Hr (actual amount of 

 

 

Btu/Hr used)

 

Example:

 

 

51,200 Btu/Hr (maximum the space can support) 

 

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space 

because the actual Btu/Hr used is more than the maxi-

mum Btu/Hr the space can support. You must provide 

additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between rooms. See 

Ventilation 

Air From Inside Building

, page 7.

B.  Vent room directly to the outdoors. See 

Ventila-

tion Air From Outdoors

, page 7.

C.  Install a lower Btu/Hr heater, if lower Btu/Hr size 

makes room unconfined. 

If the actual Btu/Hr used is less than the maximum 

Btu/Hr the space can support,

 

the space is an uncon-

fined space. You will need no additional fresh air 

ventilation.

 

  WARNING:  If  the  area  in 

which the heater may be oper-

ated is smaller than that defined 

as an unconfined space or if the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes. 

Summary of Contents for VP20BT

Page 1: ...other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s ph...

Page 2: ...ng plate This appliance is not convert ible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer TABLE OF CONTENTS Safety Information 3 Local Codes 4...

Page 3: ...o high temperatures the appliance should be located out oftraf candawayfromfurniture and draperies Do not place clothing or other ammable material on or near the appliance Never place any objects on t...

Page 4: ...o cal codes In the absence of local codes use the latest edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 Available from American National Standards Institute Inc 1430 Broadway New York NY 10018...

Page 5: ...e air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusual...

Page 6: ...rect vent draws combustion air from the outdoors and vents to the outdoors Example Gas water heater ______________ Btu Hr Vent free heater _____________ Btu Hr Total _____________ Btu Hr 40 000 20 00...

Page 7: ...t air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent Figure 3 Ventilation Air from Outdoors Figure 2 Ventilation Air from Inside...

Page 8: ...es of the heater as a replace insert in high traf c areas in windy or drafty areas CAUTION This heater cre ates warm air currents These currents move heat to wall sur faces next to heater Installing h...

Page 9: ...Attaching to Wall Stud This method provides the strongest hold Insert mounting screws through mounting bracket and into wall studs Attaching to WallAnchor This method allows you to attach mounting bra...

Page 10: ...r ush to wall 4 For thin walls 1 2 or less insert red key into wall anchor Push red key to pop open anchor wings see Figure 10 IMPORTANT Do not hammer key For thick walls over 1 2 thick or solid walls...

Page 11: ...3 For carpeted oors make a small cut with a sharp knife at marked locations prior to drill ing If mounting base to a wood oor drill 1 8 inch diameter hole 3 4 inch deep Do not use anchors in wood oor...

Page 12: ...in Figure 15 Locate sediment trap where it is within reach for cleaning Locate sediment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps the...

Page 13: ...by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter for n...

Page 14: ...de Pilot Burner Thermocouple OPERATING HEATER FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a re or explosion may result causing property damage per son...

Page 15: ...lbetween1 and 5 Selecting the 5 setting will cause the burner to remain fully on without modulating down in most cases Note The thermostat sensing bulb measures the temperature of air near the heater...

Page 16: ...e of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compressed air in a can You can use a...

Page 17: ...25 x 7 24 25 x 25 75 x 7 Carton 26 25 x 21 25 x 9 26 25 x 29 x 9 Weight pounds Heater 20 28 Shipping 25 33 SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burner will have delayed i...

Page 18: ...on 4 Air in gas lines when in stalled 5 Depleted gas supply propane LP gas only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there is n...

Page 19: ...Burner back ring during combustion Yellow ame during burner combustion Slightsmokeorodorduringinitial operation REMEDY 1 Press in control knob fully 2 AfterODS pilotlights keepcon trol knob pressed in...

Page 20: ...ly propane LP gas only 3 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged OBSERVED PROBLEM Heaterproducesawhistlingnoise wh...

Page 21: ...0 When calling DESA Heating Products have ready your name your address model and serial numbers of your heater how heater was malfunctioning type of gas used propane LP or natural gas purchase date Us...

Page 22: ...www desatech com 107886 01J 22 ILLUSTRATED PARTS BREAKDOWN MODELS VN20BT VP20BT VN30BT VP30BT 2 3 5 6 8 9 10 10 11 12 13 14 16 18 19 4 7 1 15 17 20...

Page 23: ...01 Nut M5 2 11 110803 01 110803 02 110803 01 110803 02 ODS Pilot Assembly 1 110186 01 110186 01 110186 01 110186 01 Thermocouple Kit 1 12 103446 01 103446 01 103447 01 103447 01 Burner 1 13 099387 03...

Page 24: ...intenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of...

Reviews: