Unusually tight construction is defined as 

construction where:

a.  walls and ceilings exposed to the out

-

side  atmosphere  have  a  continuous 
water  vapor  retarder  with  a  rating  of 
one perm (6 x 10

-11

 kg per pa-sec-m

2

) or 

less with openings gasketed or sealed 

and 

b.  weather stripping has been added on 

openable windows and doors 

and 

c.  caulking  or  sealants  are  applied  to 

areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical and gas lines 
and at other openings.

If your home meets all of the three criteria 

above, you must provide additional fresh air. 

See 

Ventilation Air From Outdoors

, page 7. 

If your home does not meet all of the three 

criteria  above,  proceed  to 

Determining 

Fresh-Air Flow For Heater Location

Confined and Unconfined Space

The 

National Fuel Gas Code, ANSI Z223.1/NFPA 

54

 defines a confined space as a space whose 

volume is less than 50 cubic feet per 1,000 Btu 

per hour (4.8 m

3

 per kw) of the aggregate input 

rating of all appliances installed in that space and 

an unconfined space as a space whose volume is 

not less than 50 cubic feet per 1,000 Btu per hour 

(4.8 m

3

 per kw) of the aggregate input rating of 

all appliances installed in that space. Rooms com

-

municating directly with the space in which the 

appliances are installed*, through openings not 

furnished with doors, are considered a part of the 

unconfined space.

* Adjoining rooms are communicating only if 

there are doorless passageways or ventilation grills 

between them.

DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have a 

confined or unconfined space.

Space:

 Includes the room in which you will install 

heater plus any adjoining rooms with doorless pas

-

sageways or ventilation grills between the rooms.

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

AiR FoR CoMBuStion 

And VEntiLAtion

 WARNING: This heater shall 

not  be  installed  in  a  confined 

space  or  unusually  tight  con

-

struction unless provisions are 

provided for adequate combus

-

tion and ventilation air. Read the 

following instructions to insure 

proper  fresh  air  for  this  and 

other  fuel-burning  appliances 

in your home. 

Today’s homes are built more energy efficient 

than ever. New materials, increased insulation and 

new construction methods help reduce heat loss 

in homes. Home owners weather strip and caulk 

around windows and doors to keep the cold air out 

and the warm air in. During heating months, home 

owners want their homes as airtight as possible.

While it is good to make your home energy efficient, 

your home needs to breathe. Fresh air must enter 

your home. All fuel-burning appliances need fresh 

air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers and fuel 

burning appliances draw air from the house to 

operate. You must provide adequate fresh air for 

these appliances. This will insure proper venting 

of vented fuel-burning appliances.

PROVIDING ADEQUATE 
VENTILATION 

The following are excerpts from 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, 

Air for Combustion and Ventilation

.

All spaces in homes fall into one of the three fol

-

lowing ventilation classifications:

1.  Unusually Tight Construction

2.  Unconfined Space

3.  Confined Space

The information on pages 4 through 6 will help 

you classify your space and provide adequate 

ventilation. 

Unusually Tight Construction

The air that leaks around doors and windows 

may provide enough fresh air for combustion and 

ventilation. However, in buildings of unusually 

tight construction, you must provide additional 

fresh air.

Summary of Contents for FLAME-MAX VML27NR

Page 1: ...e any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and...

Page 2: ...RNING This appliance is for installation only in a solid fuel burning mason ry or UL127 factory built fireplace or in a listed vent less firebox enclosure It is design certified for these installation...

Page 3: ...eep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat ex...

Page 4: ...heated the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture safety information Continued 11 Thisheaterneedsfresh outsideairventilationto...

Page 5: ...no outside venting There is no heat loss out a vent or up a chimney Heat is generated by realistic dancing yellow flames This heater is designed for vent free operation with flue damper closed It has...

Page 6: ...Includes the room in which you will install heater plus any adjoining rooms with doorless pas sageways or ventilation grills between the rooms 1 Determine the volume of the space length x width x hei...

Page 7: ...Your options are as follows A Rework worksheet adding the space of an adjoin ingroom Iftheextraspaceprovidesanunconfined space remove door to adjoining room or add ventilation grills between rooms Se...

Page 8: ...oor or wall of fire place If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper WARNING Never install the heater in a bedroom or bathroom un le...

Page 9: ...REMENTS Log Minimum Firebox Size Height Depth Width 27 17 19 32 MINIMUM FIREPLACE CLEARANCE TO COMBUSTIBLE MATERIALS Log Size Side Wall Ceiling 27 16 42 Carefully follow the instructions below This wi...

Page 10: ...may need the hood accessory to deflect heat away from your mantel shelf See Figure 5 and 6 and Figure 7 page 9 for minimum clearances IMPORTANT If you cannot meet these minimum clearances you must ope...

Page 11: ...become hot to the touch If installed properly these tem peratures meet the requirement ofthenationalproductstandard Follow all minimum clearances shown in this manual INSTALLATION Continued NOTICE Ify...

Page 12: ...er Damper INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION Note When used as a vented heater appliance must be installed only in a solid fuel burning fireplace with a working flue and constructe...

Page 13: ...ill not work properly Installation Items Needed hardware package provided with heater approved flexible gas hose not provided if allowed by local codes sealant resistant to propane LP gas not pro vide...

Page 14: ...lips Bracket Battery Clip 9 Volt Battery Terminal Wires Pad Installing Batteries for Remote Receiver and Hand Held Remote Control Two 9 volt alkaline batteries not included are required to operate thi...

Page 15: ...n Continued For propane LP units the installer must supply an external regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of...

Page 16: ...r Connecting to Gas Supply page 14 pressure testing gas supply piping system Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve control valve and equ...

Page 17: ...es forming show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater page 19 Check all other internal joints for leaks 7 Turn off heater see To Turn Off Gas to Appli ance page 20 INS...

Page 18: ...f base log see Figure 26 6 Place lava rock around base of heater Installation Continued O F F P I L O T O N H I L O O F F P I L O T O N H I L O Figure 22 Installing Bottom Log 1 Bottom Log 1 Burner Gr...

Page 19: ...ualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water lighting instructions WARNING If fireplace has glass d...

Page 20: ...pilot with match see Manual Lighting Procedure on page 21 8 Keep control knob pressed in for30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop out when...

Page 21: ...ute TurncontrolknobtoONposition Adjust flameadjustmentknobanywherebetweenHIand LO Slide the selector switch to the REMOTE position see Figure 30 Note The burner may light if hand held remote was on wh...

Page 22: ...tigrade the hand held remote control will perform a safetyoverrideandshutthefireplaceoff This feature is not available in the MANU mode 2 The receiver continuously receives signals from the hand held...

Page 23: ...air inlet holes allow the proper amount of air to mix with the gas This provides a clean burning flame Keep these holes clear of dust dirt lint and pet hair Clean these air inlet holes prior to each...

Page 24: ...Warranty Contact authorized dealers of this product If they can t supply original replacement part s call DESA Heating Products Technical Service Department at 1 866 672 6040 When calling DESA Heatin...

Page 25: ...in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there is no spark at ODS pilot When igni...

Page 26: ...tter and receiver 1 Contact local natural or pro pane LP gas company 2 Clean burner see Cleaning and Maintenance page 23 or replace burner orifice 1 Clean burner see Cleaning and Maintenance page 23 o...

Page 27: ...n into white powder residue 1 Battery is not installed Bat tery power is low 1 Metal expanding while heat ing or contracting while cooling REMEDY 1 Check burner for dirt and debris If found clean burn...

Page 28: ...statement at top of page 1 Not enough fresh air is avail able 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve or gas control defec...

Page 29: ...tting can be selected on the wall thermostat and the log heater will automatically cycle from pilot to the heat setting selected WALL MOUNT ON OFF switch GWMS2 Not Shown For all Remote Ready Models Al...

Page 30: ...rated Parts Breakdown Models VML27PR and VML27NR 1 2 27 5 3 4 23 18 17 5 6 12 11 7 7 20 8 8 7 7 13 14 15 19 27 1 27 3 27 4 7 26 27 2 7 16 7 8 8 25 8 9 9 21 22 10 NG Only 24 NG Only O F F P I L O T O N...

Page 31: ...1 Piezo Ignitor 1 14 102334 01 Palnut Fastener 1 15 111022 01 Rear Burner Bracket 1 16 110792 01FB Rear Flat Burner Bracket 1 17 098249 01 ODS Nut 2 18 103778 01 ODS Pilot 1 19 110793 01 Piezo Bracket...

Page 32: ...e installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of nor...

Reviews: