air For ComBUsTioN aNd VeNTilaTioN

Continued

 

Example:

 Space size 16 ft. (length) x 14 ft. 

(width) x 8 ft. (ceiling height) = 1792 cu. ft. 
(volume of space)

 

If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

  ________ (volume of space) x 20 = (Maxi

-

mum Btu/Hr the space can support)

 

Example:

 1792 cu. ft. (volume of space) x 

20 =  35,840  (maximum  Btu/Hr  the  space 

can support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free fireplace 

 __________Btu/Hr

 

Gas water heater* 

 __________Btu/Hr

 

Gas furnace 

 __________Btu/Hr

 

Vented gas heater 

 __________Btu/Hr

 

Gas fireplace logs 

 __________Btu/Hr

 

Other gas appliances* + _________Btu/Hr

 

Total 

= _________Btu/Hr

 

* Do not include direct-vent gas appliances. 
Direct-vent  draws  combustion  air  from  the 
outdoors and vents to the outdoors.

 

Example:

 

 

Gas water heater 

 __________Btu/Hr

 

Vent-free fireplace 

 __________Btu/Hr

 

Total 

 __________Btu/Hr

4. 

Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.

 

 ________Btu/Hr (maximum space can support) 

 

  ______ Btu/Hr (actual amount used)

 

Example:

  35,840  Btu/Hr  (maximum  the 

space can support) 

 

 

56,000 Btu/Hr (actual amount of 
Btu/Hr used)

The space in the previous example is a confined 
space because the actual Btu/Hr used is more 
than  the  maximum  Btu/Hr  the  space  can  sup

-

port. You must provide additional fresh air. Your 
options are as follows:
A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides 
an unconfined space, remove door to adjoin

-

ing  room  or  add  ventilation  grills  between 
rooms.  See 

Ventilation  Air  From  Inside 

Building.

B.  Vent  room  directly  to  the  outdoors.  See 

Ventilation Air From Outdoors

, page 8

.

C.  Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maxi

-

mum Btu/Hr the space can support,

 

the space is 

an unconfined space. You will need no additional 
fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus-

tion and ventilation air shall be 

provided by one of the methods 

described  in  the 

National  Fuel 

Gas Code, ANSI Z223.1/NFPA 54, 

the

 International Fuel Gas Code,

 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 
adjoining unconfined space, you must provide 
two permanent openings: one within 12" of the 
ceiling and one within 12" of the floor on the 
wall connecting the two spaces (see options 
1 and 2, Figure 2). You can also remove door 
into adjoining room (see option 3, Figure 2). 
Follow  the 

National  Fuel  Gas  Code, ANSI 

Z223.1/NFPA  54,  Air  for  Combustion  and 
Ventilation

  for  required  size  of  ventilation 

grills or ducts.

  30,000
+  26,000
=  56,000

Figure 2 - Ventilation Air from Inside 

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills  

Into Adjoining Room, 

Option 2 

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12" 

12" 

Summary of Contents for CCFPDFT

Page 1: ...U SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier INSTALLER Leave this ma...

Page 2: ...convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING This product contains and or generates chemicals known to the State of California to cause cancer or birth defects or other reproduc tive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble op erate or service this fireplace Improper use of...

Page 3: ...burner patterns can cause sooting Due to high temperatures the appliance should be located out oftrafficandawayfromfurniture and draperies Do not place clothing or other flammable material on or near the appliance Never place any objects on the heater Fireplace front and screen be come very hot when running heater Keepchildrenandadults away from hot surfaces to avoid burns or clothing ignition Fir...

Page 4: ...r furniture 10 This fireplace needs fresh air ventilation to run properly This fireplace has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the fire place if not enough fresh air is available See Air for Combustion and Ventilation page 6 If fireplace keeps shutting off see Troubleshooting page 24 11 Do not run fireplace where flammable liquids or vapors are used or stored...

Page 5: ...Controlled models have a ther mostat sensing bulb and a control valve The thermostat will automatically modulate the heat output to maintain a consistent room tempera ture This results in greater fireplace comfort This can also result in lower gas bills Dual gas type Simple conversion from propane LP to natu ral gas by a qualified installing agency Unpacking 1 Remove fireplace and hood from carton...

Page 6: ...stall fireplace plus any adjoining rooms with door less passageways or ventilation grills between the rooms 1 Determine the volume of the space length x width x height Length x Width x Height __________cu ft volume of space Air for Combustion and Ventilation WARNING This heater shall notbeinstalledinaroomorspace unlesstherequiredvolumeofin door combustion air is provided by the method described in...

Page 7: ...he space can sup port You must provide additional fresh air Your options are as follows A Rework worksheet adding the space of an adjoining room If the extra space provides an unconfined space remove door to adjoin ing room or add ventilation grills between rooms See Ventilation Air From Inside Building B Vent room directly to the outdoors See Ventilation Air From Outdoors page 8 C Install a lower...

Page 8: ...tion grills or ducts You must provide two perma nent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not pr...

Page 9: ...lied by installer for propane LP units only piping check local codes sealant resistant to propane LP gas equipment shutoff valve test gauge connection ground joint union sediment trap tee joint pipe wrench A CSA design certified equipment shutoff valve with 1 8 NPT tap is an acceptable al ternative to test gauge connection Purchase the optional CSA design certified equipment shutoff valve from you...

Page 10: ...Example The face of a mantel bookshelf etc is made of combustible material and protrudes 3 1 2 from the wall This com bustible material must be 4 from the side of the fireplace opening see Figure 5 B Clearances from the top of the fireplace opening to the ceiling should not be less than 36 INSTALLATION Continued Figure 5 Minimum Clearance for Combustible to Wall Minimum 16 from Side Wall Example C...

Page 11: ...y local codes after the equipment shutoff valve The flexible gas line must be the last item installed on the gas piping 4 If you have not installed hood follow instructions on page 9 5 Carefully set fireplace in front of rough opening with back of fireplace inside wall opening 6 Attach flexible gas line to fireplace gas regulator See Connecting Equipment Shutoff Valve to Heater Control page 16 7 B...

Page 12: ...installed properly these tem peratures meet the requirement ofthenationalproductstandard Follow all minimum clearances shown in this manual INSTALLATION Continued Figure 9 Minimum Mantel Clearances for Built In Installation Mantel Shelf Side of Firebox NOTICE Ifyourinstallationdoes not meet the minimum clear ances shown you must do one of the following raise the mantel to an accept able height rem...

Page 13: ...propane LP regulator see Figure 12 INSTALLATION Continued Figure 11 Removing Floor Assembly Figure 12 Changing Gas Type Floor Assembly Flex Line Pipe Plug Flex Line Propane LP Regulator Natural Gas Regulator Brass Male Fitting Screw 4 Remove pipe plug from natural gas regu lator see Figure 12 5 Apply pipe sealant to 3 8 NPT pipe plug and install in propane LP regulator 6 Apply pipe sealant to bras...

Page 14: ...decal will indi cate correct setting for propane LP gas 12 Place floor assembly inside firebox Con nect to gas supply and check for leaks see Connecting to Gas Supply page 16 Replace screws securing floor assembly to firebox 13 Replace logs into firebox 123571 02 LP N G Gas Type Selection Disk Disco de selección del tipo de gas Push in and turn clockwise Presione y gire en el sentido de las maneci...

Page 15: ...itch requires reset ting press button see Figure 14 Do not reset until unit has been checked by a qualified service installer Figure 14 Temperature Switch Reset Button Temperature Switch CAUTION Never connect propane LP fireplace directly to the propane LP supply This fireplace requires an external regulator not supplied Install the external regulator between the fireplace and propane LP supply Fo...

Page 16: ...ternal Regulator 11 W C to 14 W C Pressure Natural From Gas Meter 5 W C to 10 5 W C Pressure Sediment Trap Installation must include an equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 16 IMPORTANT Install equipment shutoff valve in an accessible location The equipment shutoff valve is for turni...

Page 17: ...uip ment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 4 Check all joi...

Page 18: ...ing Gas Joints Natural Gas Only Propane LP Supply Tank Equipment Shutoff Valve Equipment Shutoff Valve Gas Meter Gas Regulator Gas Regulator Installing log set and screen 1 Remove log packaging material and dis card Gently place log over burner Place front of log onto pin on firebox floor see Figure 22 Do not allow log to contact flame as this will create sooting 2 Insert each rod through ten ring...

Page 19: ...crews 10 x 6 25 shoulder into holes in cabinets Place the assembled trim onto fireplace cabinet OPTIONAL MANTEL Installation Refer to instructions provided with the mantel for assembly instructions Installing Optional Blower Accessory GA3450TA Refer to instructions provided with the blower for assembly instructions Figure 24 Assembling Trim Top Trim Mitered Edge Side Trim Slot Shim Adjusting Plate...

Page 20: ...through 7 8 Turn control knob counterclockwise to desired heating level The burner should light Set control knob to any heat level between HI and LO 9 To leave pilot lit and shut off burners only turn control knob clockwise to the PILOT position CAUTION Do not try to ad just heating levels by using the equipment shutoff valve LIGHTING INSTRUCTIONS WARNING Youmustoperate this fireplace with the scr...

Page 21: ...atch Hold match to pilot until pilot lights 3 Keep control knob pressed in for 30 sec onds after lighting pilot After 30 seconds release control knob Now follow step 8 under Lighting Instructions page 20 Figure 28 AUTO OFF ON Blower Switch AUTO OFF ON Switch Operating Optional Blower This blower has three settings ON OFF and AUTO In the ON position the blower will operate constantly In the OFF pos...

Page 22: ...4 Figure 34 shows an incorrect pilot flame pat tern when using the wrong gas type Turn off heater and call a qualified service person to make corrections Inspecting Burners Check pilot flame pattern and burner flame patterns often PILOT FLAME PATTERN Figure 29 shows a correct pilot flame pattern Figure 30 shows an incorrect pilot flame pat tern The incorrect pilot flame is not touching the thermoc...

Page 23: ...d service person We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compressed air in a can If using compressed air in a can please follow the directions on the can If you don t follow directions on the can y...

Page 24: ...e in PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Replace ignitor cable 4 Replace piezo ignitor 5 Replace pilot assembly 6 Replace pilot assembly 1 Turn on gas supply or open equipm...

Page 25: ...lights keep control knob pressed in 30 seconds 3 Fully open equipment shut off valve 4 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance page 23 or replace ODS pilot assembly 5 Hand tighten until snug then tighten 1 4 turn more 6 Replace pilot assembly 7 Replace control valve 1 Contact local natural or propane LP gas company 2 Clean burner see Cleanin...

Page 26: ... minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas company 3 Observeminimuminstallation clearances see page 10 4 Clean burner see Cleaning and Maintenance page 23 or replace burner orifice 1 Turn fireplace off when using furniture polish wax carpet cleaners or similar products 1 Refer to Air for Combustion and Ventilation require ments page 6 1 Make ...

Page 27: ...ning statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page REMEDY 1 Open window to venti late room Stop using odor causing products while fireplace is running 2 Refill ...

Page 28: ...www desatech com 123721 01E 28 8 10 8 14 14 14 14 1 9 9 10 16 17 10 6 3 11 12 13 19 20 15 16 18 16 16 16 16 2 5 16 7 4 Parts Firebox Model CCFPDFT ...

Page 29: ... 2 Screw SLTD HWH TPG 6 32 x 0 38 6 12 104313 01 Right Pin Hinge 1 13 104313 02 Left Pin Hinge 1 14 099230 02 Screw HWH SHLDR AB 10 x 0 63 10 15 111038 02 Remote Blower Bracket 1 16 M11084 26 Screw HWH AB 10 16 x 0 38 47 17 111633 01 Box Cover 1 18 111200 01 Support Bracket 1 19 105440 01 Screen Assembly 1 20 103452 03 Screen Rod 2 Not a field replacement part Parts Firebox Model CCFPDFT This list...

Page 30: ...www desatech com 123721 01E 30 Parts Burner Assembly MODEL CCFPDFT 4 19 18 15 16 17 9 8 11 14 3 13 20 35 1 22 24 23 26 25 10 2 7 37 5 21 30 29 27 28 33 34 18 32 31 6 12 36 ...

Page 31: ...16 101381 01 Valve Cover with Piezo 1 17 101628 03 Flexible Connector 1 18 099211 01 Screw HWH AB 10 16 x 2 50 2 19 098544 01 Thermobulb Clip 1 20 098271 01 Ignitor Cable 1 21 123618 01 3 8 NPT Hex Pipe Plug 1 22 123685 01 Valve Tube 1 23 123683 01 Pilot Tube 1 24 123683 02 Pilot Tube 1 25 122750 03 Dual Fuel Valve 1 26 123686 01 Selector Valve Bracket 1 27 123714 01 Dual Fuel Linkage 1 28 NPC 3C ...

Page 32: ...is product If they can t supply original replacement part s call DESA Heating LLC at 1 866 672 6040 When calling DESA Heating LLC have ready your name your address model and serial numbers of your heater how heater was malfunctioning purchase date Service Hints When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not produce specified heat for prop...

Page 33: ...mati cally turns off and on as needed CORNER MANTEL WITH Full HEARTH BASE GMC83F Oak Finished Georgian Design CS26CP Black Red Oak Cottage Design CMA208FB Light Oak Finished Traditional Design For all models Space saving mantel and hearth base corner design features clean classic lines Complete assembly instruc tions included Three sided perimeter trim kit included CABINET MANTEL and full hearth b...

Page 34: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________...

Page 35: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______________________________________...

Page 36: ...pproved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs associated with warranty repairs unless expressly covered by this warran...

Reviews: