DEOS VAV T4 RT User Manual Download Page 9

 

VAV T4 RT VAV Zone Controller    

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 8 

 

Object Table Information 

The VAV T4 RT system uses the following BACnet object tables, categorized on the basis of their ID. The type is the BACnet Object type, the instance is the BACnet Object. 
Together, the type and instance form the 

BACnet Object_Identifier

 for an object according to the following C-language algorithm: 

 

object_identifier=(unsigned long)((unsigned long)type<<22)+instance 

Analog Input (AI) 

Table 4 - Object Table Information: Analog Input (AI) 

ID 

Name 

List 

Description 

W? 

Notes 

AI.2 

AI2_AuxIn 

Integrator 

Auxiliary input. Temperature or percentage 0 to 100% (0 to 100% = 0 to 10 
Vdc) or ON/OFF set by MSV.5 Cfg_AI2_Type. 

Out_of_Service 

COV Increment (0.5) 

Temp = -40°F to 212°F or -40°C to 100°C  
Resolution 0.2°F/0.1°C 

% = 0 Volts to 100 Volts, Resolution 0.1 Volt 

On/Off = 0, 1 

AI.3 

RoomTemperature 

Integrator  Room temperature read by the internal sensor.  

Out_of_Service 

COV Increment (0.1) 

32ºF to 122ºF or 0ºC to 50ºC 
Resolution 0.02ºF/0.01ºC 

Analog Output (AO) 

Table 5 - Object Table Information: Analog Output (AO) 

ID 

Name 

List 

Description 

W? 

Notes 

AO.1 

AnalogOutput1 

Integrator 

Status value that represents the modulation percentage of analog output 1 
based on demand. 

Present Value 

COV Increment (0.5)  0% to 100%, Resolution 0.1% 

AO.2 

AnalogOutput2 

Integrator 

Status value that represents the modulation percentage of analog output 2 
based on demand. 

Out_of_Service 

COV Increment (0.5)  0% to 100%, Resolution 0.1% 

Analog Value (AV) 

Table 6 - Object Table Information: Analog Value (AV) 

ID 

Name 

List 

Description 

W? 

Notes 

AV.3 

Local_AI1_SAT_CO 

Integrator  Local suply air temperature on analog input 3. 

Out_of_Service 

COV Increment (0.5) 

-40°F to 212°F or -40°C to 100°C 

Resolution 0.02ºF/0.01°C 

AV.6 

OAT 

Integrator

 

Outdoor air temperature from RTC 1010. 

COV Increment (0.5) 

-40°F to 212°F or -40°C to 100°C 

Resolution 0.02ºF/0.01°C 

AV.10 

Cfg_CalibRoomTemperature 

Integrator

 

Configuration value that represents the calibration of room temperature. Can be 
calibrated from the minimum to the maximum temperature.  

Present Value 

COV Increment 

-40°F to 212°F or -40°C to 100°C 

Resolution 0.02ºF/0.01°C  

Summary of Contents for VAV T4 RT

Page 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Page 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Page 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Page 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Page 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Page 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Page 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Page 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Page 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Page 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Page 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Page 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Page 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Page 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Page 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Page 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Reviews: