VAV T4 RT VAV Zone Controller
BACnet Communication Module User Guide
www.deos-controls.com
Page | 14
Multi State Value (MSV)
Table 10 - Object Table Information: Multi State Value (MSV)
ID
Name
List
Description
W?
Notes
MSV.5
Cfg_AI2_Type
Integrator
Configuration of Auxiliary input on analog input 2.
Percentage
: 0 to 10Vdc input converted to 0 to 100%.
Temperature
:
10kΩ temperature sensor
OnOff
: Binary Input
Present Value
Percentage
Temperature
OnOff
MSV.11
OccCommand
Integrator
Occupancy status from Master Unit (RTC 1010).
OccCommand
is
commandable, Relinquish Default will be saved to non-volatile memory
Off
: Forces the VAV T4 RT Off. Signal sent via BMS.
Occupancy
: Forces the VAV T4 RT to occupied or day mode. Signal sent via
BMS.
NoOccupancy
: Forces the VAV T4 RT to unoccupied or night setback mode.
Signal sent via BMS.
Relinquish Default
Off
Occupancy
NoOccupancy
MSV.12
EffectiveOccupancy
Integrator
Status that indicates the actual occupancy mode.
NoOccupancy
: Zone is not occupied.
Occupancy
: Zone is occupied.
Override
: Zone is unoccupied but put back to occupied mode for a maximum
pre-determined time set at AV.61.
Present Value
NoOccupancy
Occupancy
Override
MSV.41
Cfg_AirFlowScale
Integrator
Configuration value of the airflow scale used to get a better resolution when
small airflows are configured.
Scale1
: No scale is used.
Scale 10
: Airflow is multiplied by 10. This scale is used for low airflows up to
999.
Scale 100
: Airflow is multiplied by 100. This scale is used for very low airflows
up to 99.
Present Value
Scale1
Scale10
Scale100
MSV.42
AirFlowBal_Mode
Integrator
Position the damper actuator to preset positions. This object is used when
balancing mode (BV.45) is activated
Closed
: The damper actuator moves to a fully closed position. Position used to
calibrate airflow offset (AV.114).
Min Flow
: The damper actuator moves to the minimum airflow position of the
actual mode it is in. Position used to calibrate the minimum airflow (AV.113).
Max Flow
: The damper actuator moves to the maximum airflow position of the
actual mode it is in (AV.105 in heat or AV.103 in cool). Position used to
calibrate the maximum airflow (AV.112).
Full Open
: The damper actuator moves to a fully opened position. Position
used to calibrate the maximum airflow (AV.112).
Present value if BV.45
is set to Enable
.
Closed
Min Flow
Max Flow
Full Open
MSV.50
Cfg_FanPowerBox
Integrator
Select the configuration of the FAN Output (BO4).
No
: Fan output is not used.
Series
: BO4 is always energized during occupied or override periods. BO4 is
energized with demand during Unocc periods.
Parallel
: BO4 is always energized with heating demand during all periods.
Present Value
No
Series
Parallel
MSV.51
Cfg_DuctReheat
Integrator
Select the configuration of duct reheat output (AO1 or BO1, BO2, BO3).
No
: Duct reheat is not used.
AnalogOutputDA
: Direct Acting analog output is used.
AnalogOutputRA
: Reverse Acting analog output is used.
Present Value
No
AnalogOutputDA
AnalogOutputRA
1StageOnOff