VAV T4 RT VAV Zone Controller
BACnet Communication Module User Guide
www.deos-controls.com
Page | 11
ID
Name
List
Description
W?
Notes
AV.93
CurrentDamperPosition
Integrator Value that represents the current position of the damper.
Out of service
COV Increment (1)
0 to 100%, Resolution 1%
AV.101
Cfg_AirFlowKFactor
Integrator
Configuration value that represents the maximum airflow of the VAV box at 1"
W.C.
Present Value
COV Increment (5)
100 to 9,995 units, Resolution 5 units
AV.102
Cfg_AirFlowMin
Integrator
Configuration value used during airflow balancing sequence. Refer to VAV-
Airflow Balance Instructions.
Present Value
COV Increment (1)
0 to 9,995 units, Resolution 1 unit
Writable only if system is in balancing mode
AV.103
Cfg_AirFlowCoolMax
Integrator
Configuration value that represents the maximum cooling airflow when system
is in cooling mode.
Present Value
COV Increment (5)
(12.7%) Kfac to 9,995 units, Resolution 5 units
AV.105
Cfg_AirFlowHeatMax
Integrator
Configuration value that represents the maximum cooling airflow when system
is in heating mode.
Present Value
COV Increment (5)
(12.7%) Kfac to 9,995 units, Resolution 5 units
AV.107
Cfg_AirFlowReHeatMax
Integrator Maximum reheat airflow for pressure independent system.
Present Value
COV Increment (5)
AV.102 to AV.101, Resolution 1 unit
AV.110
ActualAirFlow
Integrator
Status value that represents the actual converted airflow measured by the
differential pressure transducer.
Out of Service
COV Increment (1)
0 to 9,995 units, Resolution 1 unit
Restricted by AV.103 and AV.105
AV.111
AirFlowSetPoint
Integrator Status value that represents the airflow calculated by demand.
Out of Service
COV Increment (1)
0 to 9,995 units, Resolution 1 unit
Restricted by AV.103 and AV.105
AV.112
Cfg_AdjustAirFlowMax
Integrator
Configuration value used during airflow balancing sequence.
Refer to VAV-Airflow Balance Instructions.
Present Value
COV Increment (1)
0 to 9,995 No units, Resolution 1 No unit
Writable only if system is in balancing mode
AV.113
Cfg_AdjustAirFlowMin
Integrator
Configuration value used during airflow balancing sequence.
Refer to VAV-Airflow Balance Instructions.
Present Value
COV Increment (1)
0 to 9,995 No units, Resolution 1 No unit
Writable only if system is in balancing mode
AV.114
Cfg_AirFlowOffset
Integrator
Configuration value used to adjust the calibration of the differential pressure
transducer. Refer to VAV Airflow Balance Instructions.
Present Value
COV Increment (1)
-500 to 500 No units, Resolution 1 No unit
AV.133
Cfg_Input3 Reading
Advanced
Status value that represents the voltage output value in mV of the pressure
sensor.
Out of Service
COV Increment (5)
250mV (0") to 4,000mV (1")
AV.150
MSTPBaudRate
Integrator
Status value that indicates the rate at which the Baud rate can be configured on
an MSTP network.
Present Value
(0) Auto, 9600, 19200, 38400, and 76800.
Resolution Auto
AV.151
MSTPAdd
Integrator
Status value that indicates the MAC address of the controllers on an MSTP
network.
Present Value
0 to 254, Resolution 1 unit
AV.152
DeviceInstance
Integrator
Status value that indicates the device identification instance. The instance is
configured as per the Auto Instance Setting.
Present Value
0 to 4194302, Resolution 1 unit
AV.160
Cfg_DuctOATHeatLock
Integrator
Configuration value that represents the use of duct reheat, as required. The
duct reheat value is not dependent on the outdoor air temperature value.
Setting a duct heat lockout setpoint prevents activation of the duct reheat when
outside air temperatures are above the setpoint.
Present Value
COV Increment (0.5)
-15°F to 120°F or -26°C to 50°C
Resolution 0.1°F /0.1°C
AV.161
Cfg_PerimeterOATHeatLock
Integrator
Configuration value that represents the use of perimeter (baseboard) reheat.
The perimeter value is not dependent on the outdoor air temperature value.
Setting a perimeter lockout setpoint prevents activation of the baseboard reheat
when outside air temperatures are above the setpoint.
Present Value
COV Increment (0.5)
-15°F to 120°F or -26°C to 50°C
Resolution 0.1°F /0.1°C
AV.165
CopyCfgStartAddress
Integrator
When using copy config, this value represents the first address in the range of
copied controllers.
Present Value
0 to 254 (AV.165 to 254), Resolution 1 unit
AV.166
CopyCfgEndAddress
Integrator
When using copy config, this value represents the last address in the range of
copied controllers.
Present Value
0 to 254 (AV.165 to AV.166), Resolution 1 unit