DEOS VAV T4 RT User Manual Download Page 4

 

VAV T4 RT VAV Zone Controller  

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 3 

 

Configuration Options 

The following Configuration options enable you to configure and run the BACnet features of the controllers quickly. 

Quick Setup 

Configure the controller for BACnet communication without programming.  

 

1. 

Ensure that no other device on the network has a MAC address of 0 (the controller's default address).  

2. 

Connect the controller to the network and power it up.  

3. 

The controller automatically configures the baud rate and device instance allowing BACnet Property 
Configuration through the Write Property service. See Table 1 - BACnet Properties Configuration.  

4. 

Repeat the steps for each controller.  

Manual Setup 

Configure the controller for BACnet communication with programming.  

1. 

Access Operation Mode (jumper set to RUN position).  

2. 

Press and hold both function buttons for 5 seconds to access the Quick Access menu.  

3. 

Enter the password, 

637

4. 

Follow the instructions to configure the MAC Address, MAX Master, Device Instance, and Baud Rate, 
manually. 

5. 

Disconnect the power to the controller, connect the controller to the network, and connect the power 
again.  

MAC Address and Max_Master  

The MAC address must be unique on the entire MS/TP network. However, having a unique MAC address and a high 
baud rate does not guarantee efficient operation of the controller and other MS/TP units on the MS/TP network. Some 
MAC  address and Max_Master combinations are more efficient than  others. BACnet requires token-passing units to 
occasionally “poll” for other masters based on the MAC address and Max_Master. 
A  poor  combination  of  MAC  addresses  and  Max_Master  can  lead  to  a  slower  network  due  to  lost  time  polling  for 
masters that are not present. Unless there are 126 other units on the MS/TP network, the default Max_Master value of 
127  is  not  the  most  efficient  choice  for  the  controller.  The  Max_Master  default  value  of  127  was  selected  to  ensure 
that any master, specifically a BACnet client can be found when the controller is initially started. 

Examples of MAC Address and Max_Master Configurations 

The  following  are  some  of  the  examples  to  indicate  the  optimum  combination  of  Mac  address  and  Max_Master 
configurations to ensure a quick and efficient output.  

Example 1 

 

MAC=0. Max_Master=127 

 

MAC=1, Max_Master=127 

This configuration is slow and inefficient because every time either unit is required to find another master unit, it has to 
poll 126 units until it finds the right one to pass the token. 

Example 2 

 

MAC=0. Max_Master=5 

 

MAC=1 to MAC=4 are not used 

 

MAC=5, Max_Master=5 

This configuration is better than Example 1 but it is still not optimal. The Max_Master is set to the most efficient value 
but  the gap  between the  two  MAC addresses is high. Therefore, each unit must poll four units until  it finds the right 
one to pass the token. 

 

Summary of Contents for VAV T4 RT

Page 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Page 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Page 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Page 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Page 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Page 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Page 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Page 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Page 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Page 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Page 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Page 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Page 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Page 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Page 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Page 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Reviews: