VAV T4 RT VAV Zone Controller    

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 10 

 

ID 

Name 

List 

Description 

W? 

Notes 

set for the actual ramp. 

AV.41 

Cfg_CoolingPropBand 

Advanced 

Configuration value that represents the range through which the controller will 
modulate the cooling output from 0 to 100%. 

Present Value 

COV Increment (0.5)  1ºF to 10ºF or 0.5ºC to 5ºC, Resolution 1ºF/0.5ºC 

AV.42 

Cfg_CoolingDeadBand 

Advanced 

Configuration value that represents the range at which the controller will not 
take action when above the zone setpoint. 

Present Value 

COV Increment (0.1)  0°F to 10°F or 0°C to 5°, Resolution 0.2ºF/0.1ºC 

AV.50 

Cfg_IntegralTimeCooling 

Advanced 

Configuration value that represents the reciprocal of the integral time in 
seconds (1/I or repeats per second). To obtain a slower reaction time, the value 
of the integral must be small. To obtain a quicker reaction, the integral must be 
bigger. 

Present Value 

COV Increment (5) 

0 to 250 seconds, Resolution 5 seconds 

AV.58 

Cfg_ChangeOverSetpoint 

Advanced 

Configuration value of the temperature at which the primary air from the central 
system is considered to be in cooling or heating. Note that there is a 1.5°C 
(2.7°F) dead band on each side of the setpoint. 

Present Value 

COV Increment (0.5) 

50°F to 104°F or 10°C to 40°C,  

Resolution 1ºF/0.5ºC 

AV.59 

Cfg_ChangeOverDelay 

Integrator  Configuration value that represents the delay in changeover.  

Present Value 

COV Increment (1) 

0 to 180 minutes, Resolution 15 minutes 

AV.61 

Cfg_NoOccOverrideDelay 

Integrator 

Configuration time in minutes when unoccupied and an override has been 
activated on the controller. 

Present Value 

COV Increment (1) 

0 to 180 minutes, Resolution 15 minutes 

AV.70 

Cfg_AnalogOutput1 Min 

Advanced 

This value represents the minimum control signal of the controlled element. If 
the signal is 0 to 10Vdc then the minimum value is 0 Volts and if the signal is 2 
to 10 Vdc then minimum value is 2 Volts. This value is the 0 position at 0% 
demand. If set at 2 Volts, a 2 Volt is applied continuously even when there is no 
demand. It cannot be used to set the minimum starting activation position. 

Present Value  

COV Increment (0.5)  0 Volt to AV.71, Resolution 0.1 Volt 

AV.71 

Cfg_AnalogOutput1 Max 

Advanced 

This value represents the maximum control signal of the controlled element. If 
the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts. It 
can also be used to limit the maximum output of the controller. If the control 
signal is 0 to 10Vdc and the maximum voltage value is set to 8 Volts, the 
controlled element will never go over 80% of its total capacity. 

Present Value  

COV Increment (0.5)  AV.70 to 10.0 Volt, Resolution 0.1 Volt 

AV.72 

Cfg_AnalogOutput2 Min 

Advanced 

This value represents the minimum control signal of the controlled element. If 
the signal is 0 to 10Vdc then the minimum value is 0 Volts and if the signal is 2 
to 10 Vdc then minimum value is 2 Volts. This value is the 0 position at 0% 
demand. If set at 2 Volts, a 2 Volt is applied continuously even when there is no 
demand. It cannot be used to set the minimum starting activation position. 

Present Value  

COV Increment (0.5)  0 Volt to AV.73, Resolution 0.1 Volt 

AV.73 

Cfg_AnalogOutput2 Max 

Advanced 

This value represents the maximum control signal of the controlled element. If 
the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts. It 
can also be used to limit the maximum output of the controller. If the control 
signal is 0 to 10Vdc and the maximum voltage value is set to 8 Volts, the 
controlled element will never go over 80% of its total capacity. 

Present Value  

COV Increment (0.5)  AV.72 to 10.0 Volt, Resolution 0.1 Volt 

AV.88 

Cfg_DamperMaxPositionCool 

Integrator 

Configuration value that represents the maximum damper position when the 
system is in cooling mode and the zone is in 100% cooling demand. 

Present Value  

COV Increment (1) 

AV.90 to 100%, Resolution 1% 

AV.89 

Cfg_DamperMaxPositionHeat 

Integrator 

Configuration value that represents the maximum damper position when the 
system is in heating mode and the zone is in 100% heating demand. 

Present Value  

COV Increment (1) 

AV.90 to 100%, Resolution 1% 

AV.90 

Cfg_DamperMinPosition 

Integrator 

Configuration value that represents the minimum damper position when the 
system is in cooling or heating mode (at all times). 

Present Value  

COV Increment (1) 

0% to 100%, Resolution 1% 

AV.92 

Cfg_DamperMaxPositionReheat 

Integrator 

Configuration value that represents the maximum damper position when the 
system is in cooling mode, but the zone is requesting heat. This configuration is 
only available if the zones are equipped with a modulating duct reheat. 

Present Value  

COV Increment (1) 

0% to 100%, Resolution 1% 

Summary of Contents for VAV T4 RT

Page 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Page 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Page 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Page 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Page 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Page 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Page 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Page 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Page 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Page 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Page 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Page 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Page 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Page 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Page 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Page 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Reviews: