DEOS VAV T4 RT User Manual Download Page 10

 

VAV T4 RT VAV Zone Controller    

BACnet Communication Module User Guide 

 

 

www.deos-controls.com

 

Page | 9 

 

ID 

Name 

List 

Description 

W? 

Notes 

AV.15 

OccupiedTemperatureSetpoint 

Integrator

 

Configuration value used to set the actual user setpoint of the zone in 
occupied/day mode. 

Present Value 

COV Increment (0.5)  AV.16 to AV.17, Resolution 0.02ºF/0.01°C 

AV.16 

Cfg_MinSetpoint 

Integrator

 

Configuration value used to set the user minimum permitted setpoint of the 
zone in occupied/day mode. 

Present Value 

COV Increment (0.5) 

-40°F to 212°F or -40°C to 100°C (-40°F/-40°C to 
AV.17), Resolution 0.02ºF/0.01°C 

AV.17 

Cfg_MaxSetpoint 

Integrator

 

Configuration value used to set the user maximum permitted setpoint of the 
zone in occupied/day mode. 

Present Value 

COV Increment (0.5) 

-40°F to 212°F or -40°C to 100°C (AV.16 to 
212°F/100°C), Resolution 0.02ºF/0.01°C 

AV.18 

UnoccupiedCoolSetpoint 

Integrator

 

Configuration value of the cooling setpoint during no occupancy mode. The 
cooling setpoint is restricted by the heating setpoint.  

Present Value 

COV Increment 

50°F to 104°F or 10°C to 40°C (50°F/10°C to 
AV.12), Resolution 0.02ºF/0.01°C 

AV.19 

UnoccupiedHeatSetpoint 

Integrator

 

Configuration value of the heating setpoint during no occupancy mode for 
return air temperature. The heating setpoint is restricted by the cooling setpoint. 
Com lost RAT control setpoints. 

Present Value 

COV Increment 

50°F to 104°F or 10°C to 40°C (AV.11 to 
104°F/40°C), Resolution 0.02ºF/0.01°C 

AV.20 

HeatingDemand 

Integrator

 

Status value that represents the heating demand in percentage for the Heating 
Ramp. The heating demand value is based on zone temperature, zone setpoint 
and values set for the actual ramp (AV.21 and AV.22). 

Read only 

COV Increment (5) 

0 to 100%, Resolution 0.5% 

AV.21 

Cfg_HeatingPropBand 

Advanced 

Configuration value that represents the range through which the controller will 
modulate the heating output from 0 to 100%. 

Present Value 

COV Increment (0.5)  1ºF to 10ºF or 0.5ºC to 5ºC, Resolution 1ºF/0.5ºC 

AV.22 

Cfg_HeatingDeadBand 

Advanced 

Configuration value that represents the range where the controller will not take 
action when below the zone setpoint. 

Present Value 

COV Increment (0.1)  0°F to 10°F or 0°C to 5°C, Resolution 0.2ºF/0.1ºC 

AV.23 

DuctReheatDemand 

Integrator  Status value that represents the reheat demand. 

Read only 

COV Increment (0.1)   0 to 100%, Resolution 0.1% 

AV.24 

Cfg_DuctReheatPropBand 

Advanced 

Configuration value that represents the range through which the controller will 
modulate the reheat output from 0 to 100%. 

Present Value  

COV Increment (0.5)  1ºF to 10ºF or 0.5ºC to 5ºC, Resolution 1ºF/0.5ºC 

AV.25 

Cfg_DuctReheatDeadBand 

Advanced 

Configuration value that represents the range at which the controller will not 
take action when below the zone setpoint.  

Present Value  

COV Increment (0.3)  0°F to 10°F or 0°C to 5ºC, Resolution 0.2ºF/0.1ºC 

AV.26 

PerimeterReheatDemand 

Integrator  Status value that represents the perimeter (baseboard) reheat demand. 

Read only 

COV Increment (5) 

0 to 100%, Resolution 0.1% 

AV.27 

Cfg_PerimeterReheatPropBand 

Advanced 

Configuration value that represents the range through which the controller will 
modulate the perimeter (baseboard) reheat from 0 to 100%. 

Present Value  

COV Increment (0.5)  1ºF to 10ºF or 0.5ºC to 5ºC, Resolution 1ºF/0.5ºC 

AV.28 

Cfg_PerimeterReheatDeadBand  Advanced 

Configuration value that represents the range at which the controller will not 
take action when below the zone setpoint. 

Present Value  

COV Increment (0.1)  0°F to 10°F or 0°C to 5ºC, Resolution 0.2ºF/0.1ºC 

AV.30 

Cfg_IntegralTimeHeating 

Advanced 

Configuration value that represents the reciprocal of the integral time in 
seconds (1/I or repeats per second). To obtain a slower reaction time, the value 
of the integral must be small. To obtain a quicker reaction, the integral must be 
bigger. 

Present Value 

COV Increment (5) 

0 to 250 seconds, Resolution 5 seconds 

AV.36 

Cfg_HeatingDemandBalance 

Integrator  Configuration value that represents the heating demand balance for a zone. 

Present Value 

COV Increment (0.1)  0 to 100%, Resolution 0.1% 

AV.37 

HeatingWeightedDemand 

Integrator  Heating weighted demand for a zone (value sent to RTC 1010). 

COV Increment (0.1)  0 to 100%, Resolution 0.1% 

AV.38 

Cfg_CoolingDemandBalance 

Integrator  Configuration value that represents the cooling demand balance for a zone. 

Present Value 

COV Increment (0.1)  0 to 100%, Resolution 0.1% 

AV.39 

CoolingWeightedDemand 

Integrator  Cooling weighted demand for a zone (value sent to RTC 1010). 

COV Increment (0.1)  0 to 100%, Resolution 0.1% 

AV.40 

CoolingDemand 

Integrator 

Status value that represents the cooling demand for the Cooling Ramp. The 
cooling demand value is based on zone temperature, zone setpoint and values 

Read only 

COV Increment (5) 

0 to 100%, Resolution 0.5% 

Summary of Contents for VAV T4 RT

Page 1: ...VAV T4 RT BACnet Guide 170602 docx VAV Zone Controller VAV T4 RT BACnet Communication Module User Guide Zoning System...

Page 2: ...y of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to t...

Page 3: ...y through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decim...

Page 4: ...ot guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing...

Page 5: ...figuration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for...

Page 6: ...Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6 000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 01 Jan 2015 Thu W UtC_Offset 300 minu...

Page 7: ...lity Description Min_Present_Value Max_Present_Value Resolution COV Increment Out_of_Service COV Increment Object will automatically return to Normal after a programmable period Refer to Proprietary p...

Page 8: ...w firmware File Description Archive File Size Only 0 is the accepted value to be written into file size Schedule Description Weekly Schedule Effective Period Weekly Schedule Schedule Default Priority...

Page 9: ...32 F to 122 F or 0 C to 50 C Resolution 0 02 F 0 01 C Analog Output AO Table 5 Object Table Information Analog Output AO ID Name List Description W Notes AO 1 AnalogOutput1 Integrator Status value th...

Page 10: ...that represents the reheat demand Read only COV Increment 0 1 0 to 100 Resolution 0 1 AV 24 Cfg_DuctReheatPropBand Advanced Configuration value that represents the range through which the controller...

Page 11: ...ue represents the maximum control signal of the controlled element If the signal is 0 to 10Vdc or 2 to 10Vdc then the maximum value is 10 Volts It can also be used to limit the maximum output of the c...

Page 12: ...low Balance Instructions Present Value COV Increment 1 0 to 9 995 No units Resolution 1 No unit Writable only if system is in balancing mode AV 114 Cfg_AirFlowOffset Integrator Configuration value use...

Page 13: ...1 unit Binary Input BI Table 7 Object Table Information Binary Input BI ID Name List Description W Notes BI 1 DigitalInput1 Integrator Contact status of the input 0 Open 1 Close Out_of_Service 0 Open...

Page 14: ...tuator is configured to open from 0 to 90 When set to 1 Reverse the damper actuator is configured to open from 90 to 0 When this value is changed the controller will execute an auto stroke to reset th...

Page 15: ...ale is used for low airflows up to 999 Scale 100 Airflow is multiplied by 100 This scale is used for very low airflows up to 99 Present Value Scale1 Scale10 Scale100 MSV 42 AirFlowBal_Mode Integrator...

Page 16: ...and Demand Temp only Setpoint only Off MSV 100 Cfg_ObjectList Integrator Configuration value of the object list Integrator Object list restricted to Integrator Object List Advanced Object list restric...

Reviews: