Periodic inspection and maintenance
GAW-185ES2
- 54 -
5-3 Inspection and maintenance of once every 50 hours
(1) Cleaning of air cleaner element
Remove the cover and element. Wash the element in a non-flammable or high point solvent and
squeeze thoroughly. Soak the element in the clean mixed oil and squeeze out of the excess oil,
then reinstall the element and cover.
【
Mixed oil ratio, kerosene 3 : engine oil 1
】
Air cleaner element
Part No.: 06020 46697
[Caution]
: Check the element for damage at the time of cleaning, and replace it if damaged.
Positively mount the element in such a manner that no air leakage will occur, with attention paid not
(2) Check hose joints for looseness, damage. Carry out repair or replacement, if any
abnormality is found.
(3) Check wiring and connector for looseness, damage. Carry out repair or replacement, if any
abnormality is found.
5-4 Inspection and maintenance of once every 100 hours
(1) Change of engine oil
(2) Cleaning of Fuel strainer
Remove the cup of the fuel strainer, cleaning inside the cup and strainer.
When remove the cup to be check for damage, oil leakage. Carry out repair or replacement, if any
abnormality is found.
5-5 Inspection and maintenance of once every 200 hours
WARNING:
High voltage and Electrical Hazard
・
Do not touch the electrical component such as internal wiring and output
Terminal during the operation. Need to stop the operation always when
do the maintenance and inspection of the connection cable.
・
Do not touch the machine when the body and the machine is wet
because it is very dangerous.
If you neglect the caution death or serious fatal accident occur .
(1) Check and cleaning of spark plug
Remove carbon build up on the spark plug with wire brush. Set the spark plug gap to 0.6-0.7mm.
Tighten with a spark plug wrench.
Spark plug maker : NGK
Model No.: BR6HS
(2) Measurement of insulation resistance
1) Measure the insulation resistance every 200 hours or per month by the insulation resistance