- 200 -
Technical Characteristics
Delaying Sel.1
Used for increasing trip delays for the selected protection functions while the
protection group is set to "1".
Start Wave Record
Used for triggering a 3 second record of the current waveform.
Cold Load Pickup
Used for increasing the threshold settings of the selected protection function for a
given time.
Spring Failure
Supervises the CB charging spring via auxiliary contacts.
Change Set.Group
Used for altering between protection settings groups 1 and 2.
Block ARCL
Used for disabling auto-reclose cycles.
Reset %Θ
Used for resetting the thermal image.
Trip Circuit Sup.
Supervises the trip circuit of circuit breaker.
Reset RL1-RL6
Resets all programmable outputs.
Reset LED
Used for resetting programmable LEDs and alarm records.
Pressure Trip
Evaluates the pressure trip auxiliary contact information.
Buchholz Alarm
Evaluates the Buchholz alarm auxiliary contact information.
Buchholz Trip
Evaluates the Buchholz trip auxiliary contact information.
Temp.Alarm
Evaluates the thermometer alarm auxiliary contact information.
Temp.Trip
Evaluates the thermometer trip auxiliary contact information.
Blocking Sel.2
Used for blocking selected protection functions while the protection group is set to
"2".
Delaying Sel.2
Used for increasing trip delays for the selected protection functions while the
protection group is set to "2".
Connection Cable
2-wire screened communications cable.
Connection Point
4 terminals at the rear side of the device: reference, sending, receiving and
termination resistance terminals.
Communications Protocols
DEMCOM (DEMA communications protocol), MODBUS and IEC60870-5-103.
Communications Speed
min. 1,200 baud, max. 38,400 baud.
Insulation Level
2,000 V / 1 min.
Connection Type
Between CPM 311 Control Unit and PC.
Connection Usage
USB serial port is used for establishing communications between CPM 311 and a
PC for using DEMA DigiConnect software.
Connection Point
On the rear side of the control unit, USB B-type connector under the cover.
Communications Protocols
DEMCOM (DEMA communications protocol) and MODBUS RTU.
Communications Speed
min. 1,200 baud, max. 38,400 baud.
S1, S2, S3, S4, S5 Buttons
Multifunctional buttons, functioning as described on the screen for each menu.
Reset Button
Reset button has cyclic duty over LED, Alarm and Ampermeter menus. While at
any menu; first hit heads to the "Programmable LEDs" menu, second hit heads to
the "Alarm Menu" if any alarms are available, or to the "Ampermeters" menu if
there are no alarms to display. Hitting further returns to the initial menu.
1.7 Command Interface Buttons
1.6 USB Serial Communications Port
1.5 RS485 Serial Communications Port
Programmable Input Setting Options (Continued)
Summary of Contents for CPM 311
Page 1: ......
Page 9: ... 9 INTRODUCTION ...
Page 31: ... 31 PACKING LABELING INFORMATION ...
Page 33: ... 33 OPERATING MANUAL ...
Page 49: ... 49 RELAY MENUS MANUAL ...
Page 51: ... 51 The Menu Tree ...
Page 52: ... 52 ...
Page 53: ... 53 ...
Page 54: ... 54 ...
Page 55: ... 55 ...
Page 56: ... 56 ...
Page 57: ... 57 ...
Page 124: ... 124 DIGICONNECT PC PROGRAM MANUAL ...
Page 181: ... 181 APPLICATION DIAGRAMS ...
Page 183: ... 183 Sample Power Transformer Protection Application Diagram ...
Page 185: ... 185 FUNDAMENTAL CABLING DIAGRAM ...
Page 195: ... 195 APPLICATION DIAGRAM NO 10 Function Function Activation Address RS485 Connection Settings ...
Page 196: ... 196 TECHNICAL DATA ...
Page 208: ... 208 GLOSSARY ...