- 199 -
Technical Specification Tables
Technical Characteristics
Nominal Current (I
n
)
1 A / 5 A (via dip-switch settings).
Nominal Frequency (f
n
)
50 Hz / 60 Hz (via menu settings).
Secondary Circuit Loads
Phase Current Inputs
for 1 A : 0.01 V∙A
for 5 A : 0.2 V∙A
Earth Current Inputs
for 1 A : 0.01 V∙A
for 5 A : 0.2 V∙A
Current Circuit Thermal Withstand
100 I
n
/ 1 s
4 I
n
(20 A) / continuous
Current Circuit Dynamic Withstand
250 I
n
/10 ms
Current Transformer Recommendation
In = 1 A : 1 V∙A, 5P10 or 5P20 (Additional secondary loads should be taken into
consideration.)
In = 5 A : 1 V∙A, 5P10 or 5P20 (Additional secondary loads should be taken into
consideration.)
Supply Voltage Range (Nominal)
(24-250) V
DC
, (100-250) V
A C
Supply Voltage Range (Limits)
(21-275) V
DC
, (80-275) V
A C
DC Consumption
P
aux min
: 6 W
P
aux max
: 10 W
AC Consumption
S
aux min
: 7.5 V∙A
S
aux max
: 10 V∙A
Trip Relay
SPDT (N/C + N/O), 1 relay.
Internal Fault & Auxiliary Failure Relay
SPDT (N/C + N/O), 1 relay.
Programmable Relays
SPST (N/O), 2 relays.
Relay Contact Characteristics
Rated Values
8 A / 250 V
A C
ohmic, 8 A / 24 V
DC
ohmic.
Short Time Withstand Current
16 A / 3 s, 30 A / 0.5 s
Max. Switching Voltage
440 V
A C
Max. Switching Current
16 A
Max. Switching Power
On making: 2.2 kW / 2.2 kV∙A
On breaking: 50 W / 2.2 kV∙A
Programmable Input Quantity
5 inputs with optic-coupling.
Rated Excitation Voltage
(24-250) V
DC
, (110-250) V
A C
Extended Excitation Voltage Interval
(21-275) V
DC
, (80-275) V
A C
Input Activation Delay
≤
15 ms
Max. current per input
3 mA
Passive
Input is passive.
Unlatch
Latched relays are reset and released.
52a
Watches the normally open auxiliary contact of circuit breaker.
52b
Watches the normally closed auxiliary contact of circuit breaker.
CB Position
Used for displaying the circuit breaker position on the relevant menu.
Start tAux1
Triggers the first auxiliary timer.
Start tAux2
Triggers the second auxiliary timer.
Blocking Sel.1
Used for blocking selected protection functions while the protection group is set to
"1".
1 - Input and Output Characteristics
1.1 - Measuring Units
1.3 Output Relays and Relay Contact Characteristics
1.4 Programmable Inputs
Programmable Input Setting Options
1.2 Auxiliary Supply Voltage (Uaux)
Summary of Contents for CPM 311
Page 1: ......
Page 9: ... 9 INTRODUCTION ...
Page 31: ... 31 PACKING LABELING INFORMATION ...
Page 33: ... 33 OPERATING MANUAL ...
Page 49: ... 49 RELAY MENUS MANUAL ...
Page 51: ... 51 The Menu Tree ...
Page 52: ... 52 ...
Page 53: ... 53 ...
Page 54: ... 54 ...
Page 55: ... 55 ...
Page 56: ... 56 ...
Page 57: ... 57 ...
Page 124: ... 124 DIGICONNECT PC PROGRAM MANUAL ...
Page 181: ... 181 APPLICATION DIAGRAMS ...
Page 183: ... 183 Sample Power Transformer Protection Application Diagram ...
Page 185: ... 185 FUNDAMENTAL CABLING DIAGRAM ...
Page 195: ... 195 APPLICATION DIAGRAM NO 10 Function Function Activation Address RS485 Connection Settings ...
Page 196: ... 196 TECHNICAL DATA ...
Page 208: ... 208 GLOSSARY ...