background image

PMT2 Panel Mount Power Supply 

PMT2 150W series / PMT-

V150W2C

□□

 

TECHNICAL DATASHEET

 

 

  

All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated.

 

  www.DeltaPSU.com (September. 2022, Rev. 02)  

 

9

 

 

 

Fig. 4  Mounting Screw 

 

 

Safety Instructions 

 

If user’s mounting orientation is not according to the recommended mounting orientations, please consult Delta for further 

information. 

 

To 

ensure sufficient convection cooling, always maintain a safety distance of ≥ 50

 mm (1.97 inch) from all ventilated surfaces while 

the device is in operation. 

 

The device is not recommended to be placed on low thermal conductive surface. For example, plastics. 

 

The enclosure of the device can become very hot depending on the ambient temperature and load of the power supply. Do not 

touch the device while it is in operation or immediately after power is turned OFF. Risk of burning! 

 

Do not touch the terminals while power is being supplied. Risk of electric shock. 

 

Prevent any foreign metal, particles or conductors from entering the device through the openings during installation. It may cause: 

Electric shock; Safety Hazard; Fire; Product failure 

 

The power supply must be mounted by metal screws onto a grounded metal surface. It is highly recommended that the Earth 

terminal on the connector be connected to the grounded surface. 

 

Functions 

Start-up Time 

The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied. 

 

Rise Time 

The time required for the output voltage to change from 10% to 90% of its final steady state set value. 

 

 

Hold-up Time 

Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value. 

 

 

Graph illustrating the Start-up Time, Rise Time, and Hold-up Time 

 

 

 

 

 

Only use M3 screw ≤ 3

 mm (0.20 inch) through the base mounting holes. 

This is to keep a safe distance between the screw and internal 

components.  

 

Recommended mounting tightening torque: 

4~7 Kgf.cm (3.47~6.08 lbf.in).

 

 

Summary of Contents for PMT-12V150W2C Series

Page 1: ...eneration PMT2 power supplies is designed in a low 30mm profile and accepts universal AC input The highly efficient convection cooling construction can operate from 30 C to 70 C The single output mode...

Page 2: ...Vdc 1 36 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 10 8 13 2 Vdc 13 5 16 5 Vdc 21 6 26 4 Vdc 27 0 33 0 Vdc 32 4 39 6 Vdc 43 2 52 8 Vdc Output Current 0 12 5 A 0 10 0 A 0 6 5 A 0 5 0 A 0 4 3 A 0 3...

Page 3: ...G for a duration of 11 ms 3 shocks for each 3 directions Operating IEC 60068 2 27 Half Sine Wave 10 G for a duration of 11 ms 3 shock for each 3 directions Vibration Non Operating IEC 60068 2 6 Rando...

Page 4: ...55014 2 EN BS EN 61000 6 1 Electrostatic Discharge IEC 61000 4 2 Level 4 Criteria A1 Air Discharge 15kV Contact Discharge 8kV Radiated Field IEC 61000 4 3 Level 3 Criteria A1 80 MHz 1 GHz 10V M with...

Page 5: ...EET All parameters are specified at 25 C ambient and nominal AC input unless otherwise indicated www DeltaPSU com September 2022 Rev 02 5 Block Diagram Device Descriptions 1 Input Output terminal bloc...

Page 6: ...l AC input unless otherwise indicated www DeltaPSU com September 2022 Rev 02 6 Dimensions L x W x H 159 x 97 x 30 mm 6 26 x 3 82 x 1 18 inch Wire AWG Table Current rating for PVC Wire AWG 6AWG 52 5A 2...

Page 7: ...mperature at 30 C 3 If the output capacity is not reduced when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off unti...

Page 8: ...is surface belongs to customer s end system or panel where the power supply is mounted Connector Base Mounting Horizontal If the device has to be mounted in any other orientation please contact info d...

Page 9: ...e terminals while power is being supplied Risk of electric shock Prevent any foreign metal particles or conductors from entering the device through the openings during installation It may cause Electr...

Page 10: ...e specifications It is not recommended to prolong the duration of Io when it is 110 but 100 since it may cause damage to the PSU Short Circuit Protection Auto Recovery The power supply s output OLP OC...

Page 11: ...ion for any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the product before placing an order wit...

Reviews: