background image

PMT2 Panel Mount Power Supply 

PMT2 150W series / PMT-

V150W2C

□□

 

TECHNICAL DATASHEET

 

 

  

All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated.

 

  www.DeltaPSU.com (September. 2022, Rev. 02)  

 

2

 

Specifications 

 

Model Number 

PMT-12V150W2C

☐☐

 

PMT-15V150W2C

☐☐

 

PMT-24V150W2C

☐☐

 

PMT-30V150W2C

☐☐

 

PMT-36V150W2C

☐☐

 

PMT-48V150W2C

☐☐

 

 

Input Ratings / Characteristics 

 

Nominal Input Voltage 

100-240 Vac 

Input Voltage Range 

90-264 Vac  

Nominal Input Frequency  50-60 Hz 
Input Frequency  Range 

47-63 Hz 

Input Current 

3 A typ. @ 115 Vac, 1.7 A typ. @ 230 Vac   

Efficiency at 100% Load @ 

230Vac 

88% typ. 

89% typ. 

90% typ. 

90% typ. 

90% typ. 

91% typ. 

No Load Power 

Consumption 

< 0.3 W  @ 230 Vac   

Max Inrush Current  

(Cold Start) 

60 A typ. @ 230 Vac  

Leakage Current 

< 0.5 mA @ 240 Vac / 50 Hz   

 

 

Output Ratings / Characteristics*

2

 

 

Nominal Output Voltage 

12 Vdc 

15 Vdc 

24 Vdc 

30 Vdc 

36 Vdc 

48 Vdc 

Factory Set Point 

Tolerance 

12 Vdc ± 1% 

15 Vdc ± 1% 

24 Vdc ± 1% 

30 Vdc ± 1% 

36 Vdc ± 1% 

48 Vdc ± 1% 

Output Voltage Adjustment 

Range 

10.8-13.2 Vdc 

13.5-16.5 Vdc 

21.6-26.4 Vdc 

27.0-33.0 Vdc 

32.4-39.6 Vdc 

43.2-52.8 Vdc 

Output Current 

0-12.5 A 

0-10.0 A 

0-6.5 A 

0-5.0 A 

0-4.3 A 

0-3.3 A 

Output Power 

150 W Max. 

150 W Max. 

156 W Max. 

150 W Max. 

154.8 W Max. 

158.4 W Max. 

Line Regulation 

 ± 0.5% typ. (@ 115Vac & 230Vac input) 

Load Regulation 

 ± 0.5% typ. (@ 115Vac & 230Vac input)

 

PARD*

3

 (20MHz) 

< 150 mVpp @ 0°C to 70°C, 
450 mVpp typ. @ -30°C to 0°C 

< 200 mVpp @ 0°C to 70°C,  
600 mVpp typ. @ -30°C to 0°C 

Rise Time 

30 ms typ. @ 115 Vac & 230 Vac  

Start-up Time 

500 ms typ. @ 115 Vac & 230 Vac

 

 

Hold-up Time

 

12 ms typ. @ 115 Vac &  55 ms typ. @230 Vac full load

 

Dynamic Response  
(Overshoot & Undershoot 

O/P Voltage) 

± 10% @ 115 & 230 Vac input, 10-100% load (Slew Rate: 2.5 

A/μS, 50% duty 

cycle @ 5 Hz & 10 KHz)

 

 

Start-up with Capacitive 

Loads 

8,000 µF Max 

8,000 µF Max 

8,000 µF Max 

6,000 µF Max 

3,000 µF Max 

2,000 µF Max 

*2 : For power de-rating from > 50°C to 70°C, see power de-rating on page 3. 
*3 : PARD is measured with an AC coupling mode, and in parallel to end terminal with 0.1µF ceramic capacitor & 47µF electrolytic capacitor

PSU need to burn in > 5 minutes 

when AMB 

 0

  

 

 

 

Summary of Contents for PMT-12V150W2C Series

Page 1: ...eneration PMT2 power supplies is designed in a low 30mm profile and accepts universal AC input The highly efficient convection cooling construction can operate from 30 C to 70 C The single output mode...

Page 2: ...Vdc 1 36 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 10 8 13 2 Vdc 13 5 16 5 Vdc 21 6 26 4 Vdc 27 0 33 0 Vdc 32 4 39 6 Vdc 43 2 52 8 Vdc Output Current 0 12 5 A 0 10 0 A 0 6 5 A 0 5 0 A 0 4 3 A 0 3...

Page 3: ...G for a duration of 11 ms 3 shocks for each 3 directions Operating IEC 60068 2 27 Half Sine Wave 10 G for a duration of 11 ms 3 shock for each 3 directions Vibration Non Operating IEC 60068 2 6 Rando...

Page 4: ...55014 2 EN BS EN 61000 6 1 Electrostatic Discharge IEC 61000 4 2 Level 4 Criteria A1 Air Discharge 15kV Contact Discharge 8kV Radiated Field IEC 61000 4 3 Level 3 Criteria A1 80 MHz 1 GHz 10V M with...

Page 5: ...EET All parameters are specified at 25 C ambient and nominal AC input unless otherwise indicated www DeltaPSU com September 2022 Rev 02 5 Block Diagram Device Descriptions 1 Input Output terminal bloc...

Page 6: ...l AC input unless otherwise indicated www DeltaPSU com September 2022 Rev 02 6 Dimensions L x W x H 159 x 97 x 30 mm 6 26 x 3 82 x 1 18 inch Wire AWG Table Current rating for PVC Wire AWG 6AWG 52 5A 2...

Page 7: ...mperature at 30 C 3 If the output capacity is not reduced when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off unti...

Page 8: ...is surface belongs to customer s end system or panel where the power supply is mounted Connector Base Mounting Horizontal If the device has to be mounted in any other orientation please contact info d...

Page 9: ...e terminals while power is being supplied Risk of electric shock Prevent any foreign metal particles or conductors from entering the device through the openings during installation It may cause Electr...

Page 10: ...e specifications It is not recommended to prolong the duration of Io when it is 110 but 100 since it may cause damage to the PSU Short Circuit Protection Auto Recovery The power supply s output OLP OC...

Page 11: ...ion for any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the product before placing an order wit...

Reviews: