Appendix A-5: CA R21 Settings – Specified Power Factor
a) Apparent Power Rating (VA)
b) Output Power Rating (W)
c) DC Input voltage range with function enabled (V)
d) Nominal AC voltage (V)
e) AC voltage range with function enabled (V)
f) AC voltage measurement accuracy (V)
g) DC voltage measurement accuracy (V)
h) Active power range of function, e.g., 20-100% of nameplate
i) Power Factor Accuracy
j) Power Factor Settling Time
k) Minimum Inductive (Underexcited) Power Factor
l) Minimum Capacitive (Overexcited) Power Factor
m) PF, the inductive or capacitive signed power factor
commanded for test
n) PFmid,cap = (1 + PFmin,cap)/2, middle of the EUT
capacitive range.
o) PFmid,ind = (1 + PFmin,ind)/2, middle of the EUT
inductive range.
p) POutlimit, the maximum output power either limited by the
input supply or by a command to the inverter.
q) PFtarget, the target power factor. This will differ from the
commanded power factor in ‘Active Power Priority’ modes
for input power greater than PX
[200V, 1000V]
277V
[249.3V, 304.7V]
± 2.77V
± 10V
± 0.01
10s
0.8
0.8
[0.8cap, 0.8ind]
0.9
0.9
[0.8cap, 0.8ind]
M80U
83000VA
83000W
[16.6kW,
83kW]
83000W
M60U
66000VA
66000W
[13.2kW,
66kW]
66000W
a) Output Current Rating (A)
b) Minimum normal ramp-up rate (%Irated /sec)
c) Maximum normal ramp-up rate (%Irated /sec)
d) Minimum output current
e) Ramp Rate Accuracy MSARR(%Irated /sec)
1.11%/sec
0.4%/sec
0.1A
2%
Irated
RRnorm_up_min
RRnorm_up_max
Ilow
-
100A
80A
Appendix A-4: CA R21 Settings – Soft-start ramp rate test
a) Output Current Rating (A)
b) Minimum soft start ramp-up rate (%Irated /sec)
c) Maximum soft start ramp-up rate (%Irated /sec)
d) Ramp Rate Accuracy MSARR(%Irated /sec)
0.167%/sec
3.33%/sec
2%
M60U
80A
M80U
100A
Appendix A-3: CA R21 Settings – Normal Ramp Rate (RR)
& Soft-Start Ramp Rate (SS)
M80U
Alias
Srated
Prated
Vdc_range
Vnom
Vac_range
MSAVac
MSAVdc
[Plow, Prated]
MSAPF
(s)
PFmin,ind
PFmin,cap
PFdesird
PFmid,cap
PFmid,ind
POutlimit
PFtarget
Alias
Irated
RRss_min
RRss_max
-
Alias