- When 20A string fuses are utilized do not use input 3 or input 6 on
either MPPT channel.
CAUTION !
Input 1 Fuse holders
Input 2 Fuse holders
+01 +02 +03
+04 +05 +06
+07 +08
-01 -02 -03
-04 -05 -06
-07 -08
+01 +02 +03
+04 +05 +06
+07 +08
-01 -02 -03
-04 -05 -06
-07 -08
M80U
_120
version is compatible with 1000V/20A UL listed fuse, however, the
designer must be beware of the following requirements:
• The max Isc-stc of a connected array (sum of all paralleled strings) cannot exceed
the rated Isc limit of the inverter, that is no more than 108A/input or 216A total.
• Because of internal current limitations and higher string currents allowable with
20A fuses, inputs 3 and 6 must not be used.
Figure 3-26: Prohibited fuse location using 20A fuse
IN 1
IN 2
IN 1
IN 2
-
-
-
-
-
-
+
+
+
+
+
+
-
-
+
+
-
-
+
+
-
-
+
+
Input 1 Fuse holders
Input 2 Fuse holders
+01 +02 +03
+04 +05 +06
+07 +08
-01 -02 -03
-04 -05 -06
-07 -08
+01 +02 +03
+04 +05 +06
+07 +08
-01 -02 -03
-04 -05 -06
-07 -08
Input 1 Fuse holders
Input 2 Fuse holders
Figure 3-25: Wiring Box layout for M80/60U
_120
AC Switch
49
Installation
Summary of Contents for M60U
Page 2: ......
Page 89: ...Figure 5 6 Remove screws as indicated unplug connectors DC SPDs AC SPDs 89 Maintenance...
Page 128: ......
Page 129: ......