M80/60 series models have the surge protection device (SPD) at both AC and
DC side as shown in
Figure 5-3
.
Table 5-1
summarizes the specifications of
AC and DC SPD.
5.2 Replacement of Surge Protection Devices (SPD)
Figure 5-3: AC and DC SPD modules
Table 5-1: SPD Specifications
Description
Value
AC Module
Working voltage:
DC Module
Working Current (8/20us)
Operating Ambient Temperature Range
Rated Current (IMAX – 8/20us)
895VRMS
1175VDC
10kA
-40°C to 85°C
20kA
Sichuan Zhongguang Lightning
Protection Technologies Co., Ltd
Manufacturer:
If it's necessary to remove the insulator cover of wiring box during Cabling or
maintenance, the insulator cover must be put back in to the wiring box before
re-install the cover, refer the figure.
WARNING
!
Insulator cover
* Screw torque required for assembling:
7 lbf-in (0.8 N
•
m)