⑧
⑤
NO Location
Screw torque
10
Grounding point
69.4 lbf-in (7.8N
•
m)
9
Mounting bracket
40.0 lbf-in (4.5N
•
m)
1
1
Communication cover
7.00 lbf-in (0.8N
•
m)
8
Wiring box cover
21.0 lbf-in (2.37N
•
m)
7
Grounding bar
26.0 lbf-in (3.0N
•
m)
6
DC bus bar
52.0 lbf-in (5.9N
•
m)
5
SPD board
14.6 lbf-in (1.6N
•
m)
4
Ground of SPD board
6.90 lbf-in (0.8N
•
m)
2
Grounding screw terminal
80.0 lbf-in (9.0N
•
m)
1
AC switch
31.0 lbf-in (3.5N
•
m)
Conductor cross-section
-
-
-
-
6~4 AWG (14~22mm²)
1~3/0 AWG (35~70mm²)
13
DC wiring terminal
159.3 lbf-in (18N
•
m)
1/0~3/0 AWG (50~70mm²)
12
Mounting screw of grounding bar
22.0 lbf-in (2.5N
•
m)
-
14
Insulator cover
7.00 lbf-in (0.8N
•
m)
-
-
-
1~2/0 AWG (35~50mm²)
1~2/0 AWG (35~50mm²)
3
Communication port
-
20 AWG (0.5mm²)
Appendix C-3: Assembly Note for 121 model (With RSD)
①
⑥
⑦
⑬
⑩
⑥
⑦
⑭
121 Model WB
(With RSD)
④
②
③
⑪
⑫
⑫
⑨
125
Appendix C: Assembly Note