D P M - C
5 2 0 / C 5 2 0W O p e r a t i o n M a n u a l
6 - 2
_6
6.1
Error Codes
When an error occurs during operation, the power monitor sends an error code through Modbus. The following
table lists the error codes and causes.
Error Code
Name
Description
0x01
Illegal function
Incorrect function code
0x02
Illegal data address
Incorrect data address to read or write
0x03
Illegal data value
Incorrect data format (for example, data length)
0x04
Slave device failure
Slave cannot execute the command.
6.2
Alarm Types
The power meter supports 10 types of alarms. You can activate the alarm in the registers 0x1F–0xB7. When an
alarm is triggered, the data (such as alarm type and alarm triggered time) are stored in registers 0x400–0x483.
The following table lists the details and descriptions for the alarm types.
Number
Alarm Type
Description
1
Over Current
The measured current exceeds the setting value.
2
Over Voltage LL
The measured line voltage exceeds the setting value.
3
Under Voltage LL
The measured line voltage is below the setting value.
4
Over Voltage LN
The measured phase voltage exceeds the setting value.
5
Under Voltage LN
The measured phase voltage is below the setting value.
6
Over Active power
The measured total active power exceeds the setting value.
7
Over Reactive Power
The measured total reactive power exceeds the setting value.
8
Over Apparent Power
The measured total apparent power exceeds the setting value.
9
Over Frequency
The measured frequency exceeds the setting value.
10
Under Frequency
The measured frequency is below the setting value.
Summary of Contents for DPM-C520
Page 1: ......
Page 8: ...Chapter 1 Product Introduction 1 3 1_ 1 2 Overview DPM C520 DPM C520W...
Page 11: ...DPM C520 C520W Operation Manual 1 6 _1 MEMO...
Page 18: ...Chapter 2 Specifications 2 7 2_ DPM C520W Front DPM C520 C520W Back...
Page 27: ...DPM C520 C520W Operation Manual 3 8 _3 _3 MEMO...
Page 49: ...DPM C520 C520W Operation Manual 4 22 _4 MEMO...
Page 50: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 75: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...