D
P M - C
5 2 0 / C 5 2 0W O p e r a t i o n M a n u a l
5 - 6
_5
4E
40079
exceeding this value
clears alarm)
Alarm – Over Active Power
5E
40095
Alarm enable
0: Disable
1: Enable
word
2
R/W
5F
40096
Pickup setpoint (total
active power value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
60
40097
61
40098
Reserved
62
40099
Dropout setpoint (total
active power value
below this value
clears alarm)
0.000 – 99999.999
float
kW
4
R/W
63
40100
64
40101
Reserved
Over Reactive Power
65
40102
Alarm enable
0: Disable
1: Enable
word
2
R/W
66
40103
Pickup setpoint (total
reactive power value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kVAR
4
R/W
67
40104
68
40105
Reserved
69
40106
Dropout setpoint (total
reactive power value
below this value
clears alarm)
0.000 – 99999.999
float
kVAR
4
R/W
6A
40107
6B
40108
Reserved
Alarm – Over Apparent Power
6C
40109
Alarm enable
0: Disable
1: Enable
word
2
R/W
6D
40110
Pickup setpoint (total
apparent power value
0.000 – 99999.999
float
kVA
4
R/W
Summary of Contents for DPM-C520
Page 1: ......
Page 8: ...Chapter 1 Product Introduction 1 3 1_ 1 2 Overview DPM C520 DPM C520W...
Page 11: ...DPM C520 C520W Operation Manual 1 6 _1 MEMO...
Page 18: ...Chapter 2 Specifications 2 7 2_ DPM C520W Front DPM C520 C520W Back...
Page 27: ...DPM C520 C520W Operation Manual 3 8 _3 _3 MEMO...
Page 49: ...DPM C520 C520W Operation Manual 4 22 _4 MEMO...
Page 50: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 75: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...