![background image](http://html1.mh-extra.com/html/delta/dpm-c520/dpm-c520_operation-manual_2472679054.webp)
C h a p t e r 5 P a r a m e t e r s a n d F u n c t io n s
5 - 5
_5
3C
40061
Pickup setpoint (line
voltage value below
this value triggers
alarm)
0.000 – 99999.999
float
V
4
R/W
3D
40062
3E
40063
Reserved
3F
40064
Dropout setpoint (line
voltage value
exceeding this value
clears alarm)
0.000 – 99999.999
float
V
4
R/W
40
40065
41
40066
Reserved
Alarm – Over Voltage L–N
42
40067
Alarm enable
0: Disable
1: Enable
word
2
R/W
43
40068
Pickup setpoint
(phase voltage value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
V
4
R/W
44
40069
45
40070
Reserved
46
40071
Dropout setpoint
(phase voltage value
below this value
clears alarm)
0.000 – 99999.999
float
V
4
R/W
47
40072
48
40073
Reserved
Alarm – Under Voltage L–N
49
40074
Alarm enable
0: Disable
1: Enable
word
2
R/W
4A
40075
Pickup setpoint
(phase value below
this value triggers
alarm)
0.000 – 99999.999
float
V
4
R/W
4B
40076
4C
40077
Reserved
4D
40078
Dropout setpoint
(phase voltage value
0.000 – 99999.999
float
V
4
R/W
Summary of Contents for DPM-C520
Page 1: ......
Page 8: ...Chapter 1 Product Introduction 1 3 1_ 1 2 Overview DPM C520 DPM C520W...
Page 11: ...DPM C520 C520W Operation Manual 1 6 _1 MEMO...
Page 18: ...Chapter 2 Specifications 2 7 2_ DPM C520W Front DPM C520 C520W Back...
Page 27: ...DPM C520 C520W Operation Manual 3 8 _3 _3 MEMO...
Page 49: ...DPM C520 C520W Operation Manual 4 22 _4 MEMO...
Page 50: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 75: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...