Alarm – Over Current
1F
40032
Alarm enable
0: Disable
1: Enable
word
2
R/W
20
40033
Pickup setpoint
(current value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
A
4
R/W
21
40034
22
40035
Reserved
23
40036
Dropout setpoint
(current value below
this value clears
alarm)
0.000 – 99999.999
float
A
4
R/W
24
40037
Alarm – Over Voltage L–L
34
40053
Alarm enable
0: Disable
1: Enable
word
2
R/W
35
40054
Pickup setpoint (line
voltage value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
V
4
R/W
36
40055
37
40056
Reserved
38
40057
Dropout setpoint (line
voltage value below
this value clears
alarm)
0.000 – 99999.999
float
V
4
R/W
39
40058
3A
40059
Reserved
Alarm – Under Voltage L–L
3B
40060
Alarm enable
0: Disable
1: Enable
word
2
R/W
Summary of Contents for DPM-C520
Page 1: ......
Page 8: ...Chapter 1 Product Introduction 1 3 1_ 1 2 Overview DPM C520 DPM C520W...
Page 11: ...DPM C520 C520W Operation Manual 1 6 _1 MEMO...
Page 18: ...Chapter 2 Specifications 2 7 2_ DPM C520W Front DPM C520 C520W Back...
Page 27: ...DPM C520 C520W Operation Manual 3 8 _3 _3 MEMO...
Page 49: ...DPM C520 C520W Operation Manual 4 22 _4 MEMO...
Page 50: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Page 75: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...