Chapter 11 Description of Parameter Settings
|
C200 Series
11-121
(
7 , O , 1
)
Odd
parity
Start
bit
0
1
2
3
4
5
6
Stop
bit
7-data bits
10-bits character frame
11-bit character frame (For RTU):
(
8 , N , 2
)
Start
bit
0
1
2
3
4
5
6
Stop
bit
8-data bits
11-bits character frame
Stop
bit
7
(
8 , E , 1
)
Start
bit
0
1
2
3
4
5
6
Stop
bit
8-data bits
11-bits character frame
7
Even
parity
(
8 , O , 1
)
Start
bit
0
1
2
3
4
5
6
Stop
bit
8-data bits
11-bits character frame
7
Odd
parity
2. Communication Protocol
Communication Data Frame:
ASCII
mode
STX
Start character = ‘:’ (3AH)
Address Hi
Address Lo
Communication address:
8-bit address consists of 2 ASCII codes
Function Hi
Function Lo
Command code:
8-bit command consists of 2 ASCII codes
DATA (n-1)
…….
DATA 0
Contents of data:
Nx8-bit data consist of 2n ASCII codes
n<=16, maximum of 32 ASCII codes
LRC CHK Hi
LRC CHK Lo
LRC check sum:
8-bit check sum consists of 2 ASCII codes
END Hi
END Lo
End characters:
END1= CR (0DH), END0= LF(0AH)
Communication Data Frame:
RTU
mode
START
A silent interval of more than 10 ms
Address
Communication address: 8-bit address
Function
Command code: 8-bit command
Call 1(800)985-6929 for Sales
deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com