v1.0.1
17
Connect input wire
1. Install the copper wire as described. The section of copper wire
connected to terminal shall be reserved enough tolerance to
prevent any tension or stress from the external force.
Note:
Rated current
Copper wire type
48 A
4 AWG, 90
o
C
80 A
2 AWG, 90
o
C
2. Insert the input wire into the terminal accordingly. The cord end
terminal shall be inserted to the end without any deviation.
Note: Bottom-fed/rear-fed is available for indoor/outdoor
installation with cable gland.
3. Make sure the terminal block is secured correctly with
screwdriver.
Torque: 4.2 N·m (36.5 lb·in)
2.2.6.1 Wiring diagram