Chapter 5 Parameters
|
VFD-S Series
Revision August 2006, SE08, SW V2.61
5-7
Pr. Explanation
Settings
Factory
Setting
NOTE
5-02
3rd Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-03
4th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-04
5th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-05
6th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-06
7th Step Speed Freq.
d0.0 to d400 Hz
d0.0
5-07 PLC
Mode
d0: Disable PLC Operation
d1: Execute one program cycle
d2: Continuously execute program
cycles
d3: Execute one program cycle step
by step
d4: Continuously execute one
program cycle step by step
d5: Disable PLC operation, but can
set direction of 1st speed to 7th
speed
d0
5-08
PLC Forward/ Reverse Motion
d0 to d255 (0: FWD 1: REV)
d0
5-09
Time Duration of Zero Step Speed
d0 to d65500 Sec
d0
5-10
Time Duration of 1st Step Speed
d0 to d65500 Sec
d0
5-11
Time Duration of 2nd Step Speed
d0 to d65500 Sec
d0
5-12
Time Duration of 3rd Step Speed
d0 to d65500 Sec
d0
5-13
Time Duration of 4th Step Speed
d0 to d65500 Sec
d0
5-14
Time Duration of 5th Step Speed
d0 to d65500 Sec
d0
5-15
Time Duration of 6th Step Speed
d0 to d65500 Sec
d0
5-16
Time Duration of 7th Step Speed
d0 to d65500 Sec
d0
Group 6 Protection Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
6-00
Over-Voltage Stall Prevention
d0: Disable
d1: Enable
d1
115V/230V series: d350 to d410V
d390
6-01
Over-Voltage Stall Prevention Level
460V series: d700 to d820V
d780
6-02
Over-Current Stall Prevention Level
d20 to d150%
d130
d0: Disabled
d1: Enabled during constant speed
operation. After the over-torque
is detected, keep running until
OL1 or OL occurs.
d2: Enabled during constant speed
operation. After the over-torque
is detected, stop running.
d3: Enabled during running and
continues before Continuous
Output Time Limit (Pr.6-05) is
reached
6-03
Over-Torque Detection Mode
d4: Enabled during running. After
the over-torque is detected, stop
running.
d0
6-04
Over-Torque Detection Level
d30 to d200%
d150