Chapter 5 Parameters
|
VFD-S Series
5-62
Revision August 2006, SE08, SW V2.61
Group 9: Communication Parameters
9-00
Communication Address
Settings
d1 to d254
Factory Setting: d1
If the AC drive is controlled by RS-485 serial communication, the communication address
must be set via this parameter.
S1
Computer
S1
S1
RS485
d1
d3
d2
9-01
Transmission Speed
Factory Setting: d1
Settings
d0
Baud rate 4800 bps (bits / second)
d1
Baud rate 9600 bps
d2
Baud rate 19200 bps
d3
Baud rate 38400 bps
Users can set parameters and control the operation of the AC drive via the RS-485 serial
interface of a personal computer. This parameter is used to set the transmission speed
between the computer and AC drive.
9-02
Transmission Fault Treatment
Factory Setting: d0
Settings
d0
Warn and keep operating
d1
Warn and RAMP to stop
d2
Warn and COAST to stop
d3
No warning and keep operating