Appendix A: Database Configuration Objects
Page 61 of 67
eZV-440 Version 2.1 Application Guide
Document Edition 2.5
Setpoint Configuration Objects
Also see these related sections in the document:
•
Setpoints Tab
on page
•
Sequence of Operations
on page
Object Name
Object
Ref
Default
Units
Description
Options
OccHeatingSetpoint
AV100
°
C
Base heating setpoint in occupied
mode
Default = 21
OccCoolingSetpoint
AV101
°
C
Base cooling setpoint in occupied
mode
Default = 24
UnOccHeatingSetpoint
AV102
°
C
Unoccupied heating setpoint
Default = 17
UnOccCoolingSetpoint
AV103
°
C
Unoccupied cooling setpoint
Default = 28
HeatCoolChangeoverDelay
AV104
Minutes
Time delay between heating and
cooling to prevent overshoot
when the heating and cooling
setpoints are close together.
Default = 5, range
from 1 to 30.
CoolingMinimum
AV124
CFM (VAV)
% (VVT)
Minimum cooling airflow setpoint
(VAV)
Damper position at this setpoint
(VVT)
Default = 0
CoolingMaximum
AV125
CFM (VAV)
% (VVT)
Maximum cooling airflow
setpoint (VAV)
Damper position at this setpoint
(VVT)
Default = 0
HeatingMinimum
AV126
CFM (VAV)
% (VVT)
Minimum heating airflow setpoint
(VAV)
Damper position at this setpoint
(VVT)
Default = 0
HeatingMaximum
AV127
CFM (VAV)
% (VVT)
Maximum heating airflow
setpoint (VAV)
Damper position at this setpoint
(VVT)
Default = 0
StandbyMinimum
AV129
CFM (VAV)
% (VVT)
Minimum airflow setpoint in
standbymode where there is no
heating or cooling load (VAV)
Damper position at this setpoint
(VVT)
Default =
CoolingMinimum
AirflowFailureSetpoint
AV130
CFM (VAV)
% (VVT)
Airflow failure setpoint (VAV)
Damper position at this setpoint
(VVT)
Default = 80% of
CoolingMinimum
ParallelFanFlowSetpoint
AV131
CFM
The parallel fans turn on if
airflow falls below this setpoint to
maintain adequate air mixing.
Default =
HeatingMinimum
OATHeatLockoutSetpoint
AV160
°
C
Outside air temperature heat
lockout setpoint
Default = 99
DATHiLimitSetpoint
AV161
°
C
Discharge air temperature high
limit setpoint
Default = 35
DATHiLimitPropBand
AV162
°
C
Discharge air temperature high
limit proportional limit band
Default = 5