LINKnet I/O Tab
Page 33 of 67
eZV-440 Version 2.1 Application Guide
Document Edition 2.5
Set Up a eZNS Network Sensor
The graphic supports all button overlays, and only enables the fields that are relevant to the
model number of the eZNS network sensor.
Configurable controllers can only connect to 1 LINKnet device at a time.
This LINKnet device has to have a device address of “1” in order for it to
work with the controller algorithm. Multiple LINKnet devices (up to 4) are
only supported by the programmable controllers.
To set up the temperature sensor:
1.
In the Sensor Options section, next to SpaceTemp sensor type, select the Function
option that is most appropriate for your needs:
Function
Select this option if:
None
The built-in temperature sensor on eZNS
network sensor is not used.
SpaceTempControl
The built-in temperature sensor is used to
control the space temperature. An input object
(AI1001) is created the sensor value which will be
used by the algorithm to control space
temperature.
MonitoringOnly
Input object AI1001 created but its value will not
be used by the internal algorithm for space
temperature control.
To set up the humidity sensor:
1.
In the Sensor Options section, next to SpaceHumidity sensor type, select the Function
option that is most appropriate for your needs:
Function
Select this option if:
None
The humidity sensor on eZNS network sensor is
not used.
DeHumidification
Turns on the dehumidification sequence in the
algorithm.
Note: Dehumidification is not available with VVT
and VAV applications.
MonitoringOnly
The input object AI1003 is created for monitoring
only. Dehumidification will not be enabled in this
case.