eZV-440 Version 2.1 Application Guide
Page 58 of 67
Document Edition 2.5
Appendix A: Database Configuration Objects
The following table lists the database objects used to configure the eZV-440 controller.
Programs are prevented from writing to algorithm configurable
MV objects, I/O configurable MV objects and network setting variables.
These include MV110-147 and MV1001-1006. See the eZV-440 controller
2.1 release notes for more information.
Input Configuration Objects
Also see these related sections in the document:
•
Set Up Hardwired Occupancy Input
on page
•
Set Up a Hardwired Temperature Sensor
•
Set up a Hardwired CO2 Sensor
on page
•
Set Up Damper Feedback
on page
•
Set Up Other Supporting Inputs
on page
Object Name
Object
Ref
Default
Units
Description
Options
SpaceTemp
AV1
°
C
Temperature. Default is
to average if multiple
inputs are configured.
Default = 0
SpaceCO2
AV3
ppm
Carbon dioxide levels.
Default = 0
SpaceHumidity
AV4
% RH
Humidity.
Default = 0
InletAirTemp
AV5
°
C
Duct temperature
upstream from local
heating or cooling stages
that supply the air to that
space.
Default = 0
DischargeAirTemp
AV6
°
C
Duct temperature
downstream from any
local heating or cooling
stages that supply the air
to that space.
Default = 0
OutdoorAirTemp
AV9
°
C
Outdoor air temperature
Default = 0
DifferentialPressure1
AV11
inH
2
O
Pressure reading from
the differential pressure
sensor used to measure
airflow in the VAV box.
Default = 0
Damper1Feedback
AV13
%
Position feedback signal
from a damper.
Default = 0
FanStatus
MV7
N/A
Status of the zone supply
fan.
NotUsed_, Off_, On_.
Default = NotUsed_