eZFC-424R4-24 Application Guide
Edition 2.6
Page 81 of 84
Physical Output
Control Types
Universal
Analog, binary, time proportioned, tri-state open, tri-state close
Relay
Binary, tri-state open, tri-state close
TRIAC
Binary, time proportioned, tri-state open, tri-state close
Analog
Analog, binary
As another example, the physical outputs of the eZFC-424R4-24 controller support specific control
types. See the screenshot below for more details. In this case, outputs 1 to 4 do not support analog
control because they are TRIAC physical outputs. If you select
HydronicDuct
as a Function option
in outputs 1 to 4 in enteliWEB, the analog Control Type option is absent.