eZFC-424R4-24 Application Guide
Edition 2.6
Page 77 of 84
Object Name
Object
Ref
Default
Description
Fan1
AV810
0 %
First fan stage.
Fan2
AV811
0 %
Second fan stage.
Fan3
AV812
0 %
Third fan stage.
DemandCtrlVent
AV813
0 %
Demand Control Ventilation. Directly
controls ventilation damper position (fan
coil).
Custom1*
AV815
0 %
Custom stage associated with GCL
controlled output.
Custom2*
AV816
0 %
Custom stage associated with GCL
controlled output.
HeatCool ChangeOver-
Cmd
MV805
NotUsed_
Used to display the status of the reversing
valve in a heat pump.
ManualFanOccInterlock
BV104
Off
Select On if you want a manual fan
command to act as an occupancy signal.
Otherwise select Off if occupancy is
determined by schedule.
* Available only with enteliZONE programmable models.
Setpoint Configuration Objects
Object Name
Object
Ref
Default
Description
OccHeating Setpoint
AV100
21
Celsius
Base heating setpoint in occupied mode
OccCooling Setpoint
AV101
24
Celsius
Base cooling setpoint in occupied mode
UnOccHeating Set-
point
AV102
17
Celsius
Unoccupied heating setpoint
UnOccCooling Set-
point
AV103
21
Celsius
Unoccupied cooling setpoint
Summary of Contents for eZFC-424R4-24
Page 1: ...eZFC 424R4 24 Application Guide Edition 2 6...
Page 67: ...enteliZONE Sequence of Operations Page 66 of 84 eZFC 424R4 24 Application Guide Edition 2 6...
Page 70: ...eZFC 424R4 24 Application Guide Edition 2 6 Page 69 of 84...
Page 71: ...enteliZONE Sequence of Operations Page 70 of 84 eZFC 424R4 24 Application Guide Edition 2 6...